285 Issue 1 - Service Manual - Iceberg
39
14.0 Evaporator Module – Primary Drain
Brivis recommend the drain outlet be plumbed to a suitable point in order to disperse the waste
water away adequately without causing damage or nuisance i.e. no overflowing.
Ensure that all field supplied drainage pipe is rigid (not flexible) and UV stabilised if exposed to
the external environment.
Ensure any drain has a continuous fall, the joints and fittings are adequately sealed, and that all
penetrations in and out of the roof cavity are sealed against water entry into the building, i.e.
must be compliant with local plumbing regulations.
The drain pipe must also be properly supported along its entire run, and must not place strain on
the Evaporator Modules outlet fitting or base.
The drain connection size at the Evaporator Module is a 20mm socket to suit
20mm pressure
pipe
Check the water drains completely…….
14.1 Safety Tray – Secondary Drain
The Safety Tray must be drained independently of the Evaporator Module and be assembled
using
40mm DWV
with no reduction in size. This drain must be terminated in a position where
the end user can see if water is dripping from the outlet. Please instruct the home owner to call
their Installer or Brivis Service should they notice water dripping from the Safety Tray drain
outlet.
Check the safety tray drains correctly.
Note:
The “
Evaporator Module
” drain and “
Safety Tray
” drain must not be joined.
Evaporator Module
Primary Drain
connection.
Safety
Secondary Drain
connection.