background image

Cat. No.

SC1000B

SMOKE & CARBON

MONOXIDE ALARM

9V BATTERY POWERED

1. Permanently installed smoke and CO sensors meeting sensitivity

requirements of Underwriters Laboratories, Inc. UL 2034 and UL 217.

2. The unit shall be capable of self-restoring.
3. A silence button that silences the alarm while the occupant(s) respond. If

significant levels of Smoke an/or CO are present after the initial silenced
period, or if they continue to rise, the detector will alarm again.

4. The unit shall be powered by a single 9V battery (included).
5. A flashing green LED to indicate the unit is receiving power; flashes yellow

when battery is low. “Flame” and “CO” LED icons that flash respectively
when the unit has detected enough smoke and/or CO to trigger an alarm for
easy alarm identification. A flashing yellow LED to indicate the unit needs to
be serviced or replaced. 

6. Different horn patterns to identify which alarm, smoke or CO, is in alarm.
7. A manual test button to test all functions by electronically simulating the

presence of smoke and CO.

8. A solid state piezo alarm horn rated at 85dB at 10ft.
9. The unit shall be capable of operating between 40F and 100F (4-38C)

and relative humidity of 30% and 70%.

10. The unit shall be capable of surface mount on walls and ceilings.
11. The unit shall be listed by Underwriters Laboratories, Inc. Single and

Multiple Station Carbon Monoxide Detectors UL 2034 and Multiple
Station Carbon Monoxide Detectors UL 2034, Underwriter’s Laboratories
Single and Multiple Station Smoke Alarm UL 217, and the State of
California Fire Marshal.

12. The unit shall meet the requirements NFPA72, NFPA101, ICBO, BOCA,

SBCCI, and CABO.

13. A five year manufacturers limited warranty.

TECHNICAL SPECIFICATIONS

Alarm Circuit

100% Solid State

Operating Voltage

9V DC

Operating Ambient Temp. Range

40°F(4°C) to 100°F(38°C)

Operating Humidity Range

30% to 70% RH

Alarm Horn Rating

85dB at 10Ft.

Alarm Reset

Automatic when Smoke and/or CO clears

Single Test/Silence Button

Tests all functions by electronically simulating the
presence of smoke and CO.

Silences the alarm while the occupant(s)
respond. If significant levels of smoke and/or
CO are present after the initial silenced
period, or if they continue to rise, the alarm
will alarm again.

Alarm Status Indicators

Battery Status Indicator

Flashes green when unit is receiving power. 

Flashes yellow when battery is low. 

Service Status Indicator

Flashes yellow when the unit needs 
service or replacement.

Smoke and CO Alarm Status Indicator

”Flame” and “CO” LED icons flash red
respectively when the unit has detected
enough CO and/or smoke to trigger an
alarm.

Unit Dimensions

5

8

"Dia x 1 

13

16

"H (w/ bracket)

Unit Weight

.7 lbs.

NAED #

85614

Units Per Case

3 units

MANUFACTURED BY:

DISTRIBUTED BY:

FOR TECHNICAL HELP OR REPRESENTATIVE NEAREST YOU
PHONE 1-888-777-5599 

CM2019

BRK

®

Electronics

3901 Liberty Street Road
Aurora, IL 60504-8122

©1997 BRK Brands, Inc.

Printed in USA

APPLICATION

BRK Electronics Model SC1000B is a 9V battery operated single station
Combination Smoke & Carbon Monoxide (CO) Alarm specifically designed
for residential and institutional applications including single family homes,
multifamily homes, sleeping rooms of hospitals, hotels, motels, dormitories,
and other mixed occupancy dwellings as defined in standard NFPA 101.
Model SC1000B has been fully tested and complies with Underwriters
Laboratories, Inc. Single and Multiple Station Carbon Monoxide Detectors UL
2034, with Underwriters Laboratories, Inc. Single and Multiple Station Smoke
Alarms UL 217, the California State Fire Marshal, and with model building
codes published by ICBO, SBCCI, BOCA and CABO.

Model SC1000B combines Smoke Alarm and CO Alarm technologies in one
unit. As a Carbon Monoxide alarm, Model SC1000B measures CO levels in
the air and alerts the occupant(s) to a potentially dangerous build-up of CO
over time. It will alarm if CO levels rise quickly (if the heat exchanger on a
furnace breaks, for example), or if CO is consistently present (a slow CO leak
on a fuel-burning appliance). The unit measures CO levels by passing an
infrared beam of light through two self-restoring sensor discs to a photo-
sensitive receiver. The sensor discs darken when exposed to CO. When
exposed to potentially dangerous levels, the sensor discs block the beam of
light triggering an 85dB alarm. The unit is designed to alarm before
10%COHb exposure at levels of 30% to 70% Relative Humidity (RH) as
required by Underwriters Laboratories, Inc. Single and Multiple Station
Carbon Monoxide Detectors UL 2034. It has been tested to alarm at the
following exposures:400 ppm CO before 15 minutes, 200 ppm CO before 35
minutes, 100 ppm CO before 90 minutes. This CO Alarm is not designed to
detect CO levels below 15ppm typically. 

As a Smoke Alarm, Model SC1000B provides early warning of fire when
smoke reaches its Ionization Sensor Chamber. The sensor consists of two
electrically charged plates and a source of Americium 241 to ionize the air
molecules in the space between the plates. As particles of combustion enter the
ionization chamber, they collide and combine with ionized air molecules
resulting in a decrease in current between the two plates. Electronic circuitry
monitors the change in current. When smoke inside the chamber reaches a
threshold level the unit triggers an audible alarm. 

Model SC1000B features four colored indicator lights and an 85dB alarm horn
for alarm notification. A flashing green LED indicates the unit is receiving power;
flashes yellow when battery is low. For easy alarm identification “Flame” and
“CO” LED icons flash red respectively when the unit has detected enough smoke
and/or CO to trigger an alarm. A flashing yellow LED indicates the unit needs to
be serviced or replaced. Different horn patterns make it easy to determine which
alarm, smoke or CO, is sounding. It also has a silence feature to temporarily
quiet the alarm horn.

Refer to NFPA 72, NFPA101, and with model building codes published by ICBO,
SBCCI, BOCA, and CABO for information on the proper location, placement, of
Smoke Alarms. The Consumer Product Safety Commission (CPSC) recommends
the use of at least one CO Alarm per household, located near the sleeping area.
For added protection, install additional CO Alarms in each separate bedroom,
and on every level of the home. Also, refer to Model SC1000B - User’s Manual
for more information on the proper location, placement, and installation of this
Combination Smoke and Carbon Monoxide Alarm. 

Mounting hardware and 9V alkaline battery are included with the unit.

ARCHITECTURAL AND ENGINEERING SPECIFICATIONS

The Combination Smoke and Carbon Monoxide (CO) Alarm shall be 
BRK Electronics Cat. No. SC1000B or approved equal and shall provide, 
at a minimum, the following features and functions.