G730-Install-IG100 Installation Guide
Brocade
®
G730 Switch Hardware Installation Guide
Precautions Specific to the Fan Assemblies
CAUTION
Disassembling any part of the power supply and fan assembly voids the warranty and regulatory certifications.
There are no user-serviceable parts inside the power supply and fan assembly.
CAUTION
Ensure that the airflow direction of the power supply unit matches that of the installed fan tray. The power
supplies and fan trays are clearly labeled with either a green arrow with an "E" or an orange arrow with an "I."
CAUTION
If you do not install a module or a power supply in a slot, you must keep the slot filler panel in place. If you run
the chassis with an uncovered slot, the system will overheat.
CAUTION
To prevent damage to the chassis and components, never attempt to lift the chassis using the fan or power
supply handles. These handles were not designed to support the weight of the chassis.
NOTE
The equipment installation must meet NEC/CEC code requirements. Consult local authorities for regulations.
Identifying the Direction of the Fan Assembly Airflow
The fan assemblies are identified by the following airflow directions:
•
Intake fan assembly with an orange "I" label or without any label
: Pulls air from the nonport side of the switch and
exhausts it out the port side.
•
Nonport-side air intake
•
Port-side air exhaust
•
Back-to-front (nonport-side to port-side) airflow
•
Part numbers ending with -R
•
Exhaust fan assembly with a green "E" label
: Pulls air from the port side of the switch and exhausts it out the
nonport side.
•
Port-side air intake
•
Nonport-side air exhaust
•
Front-to-back (port-side to nonport-side) airflow
•
Part numbers ending with -F
Fan Assembly Fault Indicators
Use one of the following methods to determine the status of the fan assemblies:
•
Check the fan assembly status LED. See
to interpret the meaning of LED operation.
•
In Web Tools, click the
Fan Status
icon.
•
Enter the
fanShow
command at the prompt to display fan assembly status, as shown in the following example:
Device:admin> fanshow
Fan 1 is Ok, speed is 11695 RPM
Fan 2 is Ok, speed is 11695 RPM
Fan 3 is Faulty