background image

2

Damper and outside air duct connected directly to a ceiling, floor, or wall register.

INTERIOR WALL

WALL

REGISTER

REGISTER BOX ADAPTED

WITH SLIDE-IN FILTER (optional)

MOTORIZED DAMPER

WALL CAP WITH

BIRD SCREEN

INSULATED OUTSIDE

AIR DUCT (slope toward wall cap)

EXTERIOR WALL

VENTILATION AIR INTAKE

(locate away from pollutant sources)

TYPICAL INSTALLATIONS

Installations will vary according to the location in the home where the unit is installed 

and which model Damper is used. Use the following illustrations and notes as guidance 

for your own installation.  Always comply with local code requirements and in any 

instance where a detail shown below conflicts with local code, the local code provision 

shall apply.

Damper connected to return side of central duct system.

AIR HANDLER UNIT

AIR DISTRIBUTION FAN

THERMOSTAT

CENTRAL SYSTEM SUPPLY AIR

REGISTER BOX ADAPTED

WITH SLIDE-IN FILTER (optional)

AUTO. MAKE-UP AIR DAMPER

FIELD MEASUREMENT OF AVAILABLE

STATIC PRESSURE. (See “Install The

Damper” section on page 3 for damper

balancing instructions.)

FRESH AIR INLET WALL CAP

WITH BIRD SCREEN

INSULATED OUTSIDE

AIR DUCT (slope toward wall cap)

EXTERIOR WALL

VENTILATION AIR INTAKE

(locate away from pollutant sources)

CENTRAL SYSTEM RETURN AIR

CENTRAL DUCT SYSTEM FILTER

INSTALL THE DAMPER

OUTSIDE AIR

TO CENTRAL SYSTEM

RETURN AIR OR INTERIOR

WALL REGISTER 

DAMPER FLAP (Install in

vertical position shown.)

AIR FLOW

AIR FLOW

SET SCREW

Install the damper as shown. Make sure damper flap is in a vertical position when 

closed and power is off. The set screw can be used to adjust the damper opening - 

thereby balancing the inside and outside air pressure when the range hood exhausts 

at high speed.

PRESSURE SWITCH OPERATION

The pressure switch is designed to operate when the static pressure increases to 0.05” 

Ps or more. It may not operate at low speeds since the pressure is below this limit.

MULTIPLE DAMPERS

More than one damper may be required to balance the system. If more than one is 

required use (1) MD6TU or MD8TU and then use the MD6 or MD8 dampers as ad-

ditional dampers.

INSTALLATION OF PRESSURE SWITCH 

AND PROBE

For the probe & pressure switch to work effectively the roof or wall cap must have a 

spring loaded damper. The following Broan products are recommended:

TYPICAL INSTALLATION WITH

INTERNAL BLOWER AND ROOF VENT

RANGE
HOOD

PROBE

EXHAUST
DUCT

ROOF CAP
w/DAMPER

PRESSURE
SWITCH

HOOD
FLUE

IN-LINE
DAMPER

TYPICAL INSTALLATION WITH

INTERNAL BLOWER AND WALL VENT

RANGE
HOOD

PROBE

EXHAUST
DUCT

PRESSURE
SWITCH

HOOD
FLUE

WALL CAP

w/DAMPER

IN-LINE
DAMPER

TYPICAL INSTALLATION WITH

INTERNAL BLOWER AND HORIZONTAL

DUCTING w/ WALL VENT

RANGE
HOOD

WALL CAP
w/DAMPER

PROBE

TUBING

PRESSURE
SWITCH

KITCHEN
CABINET

TYPICAL INSTALLATION WITH INLINE BLOWER

RANGE
HOOD

PROBE

EXHAUST
DUCT

PRESSURE
SWITCH

HOOD
FLUE

ROOF CAP
w/DAMPER

INLINE
BLOWER

TYPICAL INSTALLATION

WITH EXTERIOR BLOWER

RANGE
HOOD

PROBE

EXHAUST
DUCT

PRESSURE
SWITCH

HOOD
FLUE

EXTERIOR
BLOWER

Wall Cap models:

WC638 – For 3¼” x 14” duct
639 / 649 – For 3¼” x 10” duct
647 – For 7” round duct
843BL / 641 – For 6” round duct
643 / 643FA – For 8” round duct
613 – For 12” round duct
441 – For 10” round duct.

Roof Cap models:

437 – High capacity up to 

1200 cfm
634 / 644 – For 3¼” x 10” and 

up to 8” round
634M – For 6” round

LOCATION OF PROBE AND 

PRESSURE SWITCH

The probe must be mounted between the range hood damper and the wall cap, roof 

cap, in-line blower or external blower. Mount the probe as close to the hood outlet as 

possible but make sure the hood damper operation is not affected.
The pressure switch should be mounted so it is accessible for any future service. 

The switch can mounted no more then 72” away from the probe. If longer tubing is 

required then what is supplied, purchase 1/4” I.D. PVC tubing from a local source. 

See the illustrations below for possible installation scenarios.

Summary of Contents for MD10TU

Page 1: ...Insulate the duct and damper to prevent build up of condensation in cold weather climates Vapor barriers on both sides of insulation are recommended PLAN THE INSTALLATION Planning the installation first requires selecting the most appropriate installation ap proach The chart below offers suggestions for the most effective installation approach by considering a few important factors Further details...

Page 2: ...re It may not operate at low speeds since the pressure is below this limit MULTIPLE DAMPERS More than one damper may be required to balance the system If more than one is required use 1 MD6TU or MD8TU and then use the MD6 or MD8 dampers as ad ditional dampers INSTALLATION OF PRESSURE SWITCH AND PROBE For the probe pressure switch to work effectively the roof or wall cap must have a spring loaded d...

Page 3: ...ion and venting of all combustion equipment in the home FALSE TRIPPING Under certain extreme conditions there could be false tripping of the damper opening when the range hood blower is off If false tripping is encountered place an in line backdraft damper 7 model no 97 8 model no 438 10 model no 421 between the probe and the roof or wall cap SERVICE PARTS 97018853 Pressure Switch Kit 97013273 24V...

Page 4: ... the home by a range hood Range hoods are designed to pull out pollutants like cooking odors or moisture at the source so they don t linger in the home Because these fans pull air out of the house this air needs to be replaced with new air from outdoors Normally this make up air enters the home through cracks and holes in the shell of the building But modern homes are air sealed much more thorough...

Page 5: ...SERVER POUR USAGE RÉSIDENTIEL SEULEMENT MODÈLES MD6TU MD8TU MD10TU EMPLACEMENT DE LA PRISE D AIR EXTÉRIEUR La conception et l emplacement adéquats de la prise d air extérieur sont indispensables au bon fonctionnement et à la fiabilité du clapet pour faire pénétrer de l air frais dans la maison Il importe de respecter les exigences suivantes lors du positionnement de la prise d air La prise d air e...

Page 6: ...me Si vous utilisez plusieurs clapets choisissez un 1 clapet MD6TU ou MD8TU puis utilisez les modèles MD6 ou MD8 comme clapets additionnels INSTALLATION DU MANOCONTACTEUR ET DE LA SONDE Pour que la sonde et le manocontacteur fonctionnent correctement le capuchon mural ou de toit doit avoir un clapet à ressort Les produits Broan suivants sont recommandés MODÈLES DE CAPUCHON DE TOIT 437 Haute capaci...

Page 7: ...stion Effectuez le câblage tel qu illustré NOIR LIGNE BLANC NEUTRE VERT TERRE CLAPET D AIR DE COMPENSATION TRANSFORMATEUR 24V MANOCONTACTEUR DIAGRAMME DE CÂBLAGE CLAPETS MULTIPLES CLAPET D AIR DE COMPENSATION 24V 24V 24V 24V 20V BORNES 24V CÂBLAGE DUTRANSFORMATEUR DÉCLENCHEMENT INDÉSIRABLE Dans certaines conditions extrêmes le clapet peut se déclencher alors qu il ne le devrait pas s ouvre alors q...

Page 8: ...e stagnent pas dans la maison Puisque ces ventilateurs évacuent l air de la maison celui ci doit être remplacé par de l air neuf de l extérieur Normalement cet air de compensation entre dans l habitation par les ouvertures et les fentes de l enveloppe de l édifice Or les maisons modernes sont beaucoup plus étanches et ne présentent plus autant de fentes et d ouvertures De plus certains ventilateur...

Page 9: ...our éviter la condensation Il est conseillé de placer un coupe vapeur des deux côtés de l isolant REGULADOR DE AIRE AUTOMÁTICO DE REPUESTO CON TRANSFORMADOR E INTERRUPTOR DE PRESIÓN LEA Y CONSERVE ESTAS INSTRUCCIONES SOLO PARA USO RESIDENCIAL UBICACIÓN DE LA ENTRADA DEL AIRE EXTERIOR El diseño y el sitio adecuados de la ubicación de la entrada de aire exterior son vitales para garantizar que el re...

Page 10: ...ADORES Tal vez se requiera más de un regulador para equilibrar el sistema Si se requiere más de uno use 1 MD6TU o MD8TU y luego use los reguladores MD6 o MD8 como reguladores adicionales INSTALACIÓN DEL INTERRUPTOR DE PRESIÓN Y SONDA Para que la sonda y el interruptor de presión funcionen con eficacia la tapa para techo o pared debe tener un regulador cargado por resorte Se recomiendan los siguien...

Page 11: ... que se abre el regulador Apague la campana y compruebe que se cierra el regulador Un contratista calificado en HVAC también debe asegurarse la operación adecuada y la ventilación de todo el equipo de combustión en la casa Cablee el sistema como se ilustra 24V 20V CONTACTOS DE 24 V CABLEADO DELTRANSFORMADOR DISPARO EN FALSO Bajo ciertas condiciones extremas podría haber el disparo en falso del reg...

Page 12: ...as están diseñadas para extraer contaminantes como olores de cocinado o humedad en la fuente de tal manera que no perduren en la casa Debido a que estos ventiladores extraen el aire de la casa es necesario reemplazar este aire con aire nuevo del exterior Normalmente este aire de repuesto entra a la casa a través de grietas y orificios en la armazón del edificio Pero las casas modernas están mucho ...

Reviews: