34
Brocade ServerIron ADX Installation Guide
53-1002405-01
Installing ServerIron ADX
2
CAUTION
When making the primary ground connection, a star washer must be used for anti-rotation. When
connecting the device to the rack frame, use thread-forming screws and paint-piercing washers.
CAUTION
AC and DC power supplies can be grounded to a common bonding network or to an isolated
bonding network.
Connecting DC power to ServerIron ADX chassis devices
To connect a DC power source to the ServerIron ADX 4000, ServerIron ADX 8000 or ServerIron ADX
10000, follow these steps.
1. Use a flat-blade screwdriver to remove the two screws holding the transparent cover over the
power supply lugs.
FIGURE 31
The ServerIron ADX 4000, ServerIron ADX 8000 and ServerIron ADX 10000 DC Power Supply
2. Use a Phillips head screwdriver to remove each of the power lugs.
3. Crimp #8 AWG power supply wire into the power lugs and reconnect the power lugs to the
power supply unit.
CAUTION
For the NEBS compliant installation of a ServerIron ADX device with AC and DC system use a
ground wire of at least 6 American Wire Gauge (AWG). The ground wire should have an
agency-approved crimped connector (provided with the chassis) attached to one end, with the
other end attached to building ground. The connector must be crimped with the proper tool,
allowing it to be connected to both ground screws on the enclosure. Before crimping the ground
wire into the provided ground lug, (Panduit LCD6-10AF-L), insure the bare copper wire has been
cleaned and antioxidant is applied to the bare wire.(ADX-1000 only)
1 Screws Holding Power Lugs 2 Screws Holding Transparent Cover
DC OUT
2
1
ALM
DC IN
Summary of Contents for SERVERIRON ADX 1000
Page 6: ...vi Brocade ServerIron ADX Installation Guide 53 1002405 01...
Page 10: ...x Brocade ServerIron ADX Installation Guide 53 1002405 01...
Page 72: ...62 Brocade ServerIron ADX Installation Guide 53 1002405 01 Port specifications A...
Page 75: ...Brocade ServerIron ADX Installation Guide 65 53 1002405 01 ServerIron ADX 8000 B...
Page 76: ...66 Brocade ServerIron ADX Installation Guide 53 1002405 01 ServerIron ADX 8000 B...
Page 80: ...70 Brocade ServerIron ADX Installation Guide 53 1002405 01 BMSI STATEMENT TAIWAN C...