background image

5

5. INSTALLATION IN BRICK WALLS

1  Before commencing installation, check the condition of the damper, the correct position of the shutter, in a closed 

position, and that the command works properly.

2  Make a hole in the wall which is 120 mm large in H and L than the nominal damper measurements (fig.1).

3  Position the damper inside the hole centring it horizontally, making sure the shutter axis corresponds to the wall 

axis. Maintain the axis of rotation of the blade horizontal as from tests carried out (is not allowed to be installed 

with vertical axis). Respect the dimensions shown (fig.2 - table 1).

4  Fill in the space between the wall and the damper using fireproof cement material (M10 cat. or higher) to reinstate 

resistance and insulation (fig.3).

On completing installation, it is recommended to run a test to check the blade rotates correctly and the commands 

work properly (in both manual and motorised mode). It can be conducted in manual mode by using the lever to reset 

the damper and pressing the test button to simulate operating functions. In motorised mode, use the thermoelectric 

fuse lever.In motorised mode, use the thermoelectric fuse lever.

fig. 1

fig. 2

fig. 3

TABLE 1

P (mm)

S1 (mm)

S2 (mm)

120

190

90

150

175

75

> 150

175

= 400 - (P+S1)

Summary of Contents for MDF30EURO

Page 1: ...making air better MDF30EURO INSTALLATION AND OPERATION MANUAL FIRE PROTECTION EN...

Page 2: ...RK 3 3 HANDLING AND INSTALLATION WARNINGS 4 4 MAINTENANCE 4 5 INSTALLATION IN BRICK WALLS 5 6 INSTALLATION IN CONCRETE FLOORS 6 7 INSTALLATION IN LIGHTWEIGHT WALLS 7 8 CONTROL FUNCTIONS 8 9 REPLACING...

Page 3: ...has been installed the control unit will remain outside the masonry to make post installation interventions easier When installed following the instructions provided in this manual it can be used in H...

Page 4: ...ch could prevent the correct operations of the commands outside the duct itself Keep as much access clearance as possible on the control unit side so as to ensure the user and maintenance operators ha...

Page 5: ...d to be installed with vertical axis Respect the dimensions shown fig 2 table 1 4 Fill in the space between the wall and the damper using fireproof cement material M10 cat or higher to reinstate resis...

Page 6: ...inst the damper casing so that it is blocked in the correct position fig 2 5 The metal brackets are designed to be fastened to the floor fig 3 6 Fill in the space between the floor and the damper usin...

Page 7: ...he side of the bracket supporting the damper does not protrude over the outer edge of the flange Use the threaded bolts supplied with the brackets to fix them in place fig 3 5 Position the damper insi...

Page 8: ...lectromagnetic circuit breaker Reset Power up the electromagnet electrical wiring diagram on page 8 Raise the metal lever on the control unit casing fig 1 Remove the reset lever from the housing compa...

Page 9: ...he key supplied with the delivery into the housing on the servomotor and turn it counter clockwise by half a turn to enable the spring return that will automatically move the servomotor into the close...

Page 10: ...Switch technical data Casing Fibre glass reinforced thermoplastic Protection rating EN 60526 Standard IP65 Cable cross section diameter rigid 2 5mm flexible with ferrule 1 5 mm Operating temperature...

Page 11: ...device consists of three fuses these make the fire damper shutters sensitive to the temperature inside the duct with Tf 2 and Tf 3 fuses which can be replaced and to ambi ent temperatures using the Tf...

Page 12: ...rofer it INSTALLER 19 143 43 211 70 55 500 210 21 30 051 Fax 210 22 23 283 BROFER SRL Via Roma 66 31023 Resana TV Italy Tel 39 0423 716611 Fax 39 0423 716612 info brofer it www brofer it making air be...

Reviews: