background image

9

Manual command with input electromagnet

Reset:

• Raise the metal lever on the control unit casing (fig.1).

• Remove the reset lever from the housing compartment (fig.2).

• Insert the reset lever inside the control pin as far as possible, turning the lever clockwise by 90 degrees, making sure 

that the control pin is blocked in the open position (fig.3).

• Now remove the lever from the control pin and replace it in its housing compartment.

Manual closing:

• Press the button highlighted in fig.4.

Electromagnetic closing:

• Power up the electromagnet.

Servomotor mode

Reset:

• Insert the key supplied with the delivery into the housing on the servomotor and turn it clockwise to a 90 degree 

position.

• Quickly rotate it counter clockwise to block the servomotor in the open position.

• Manual closing:

• Insert the key supplied with the delivery into the housing on the servomotor and turn it counter clockwise by half a 

turn to enable the spring return that will automatically move the servomotor into the closed position and the relative 

indicator in a 0 degree position.  

Motorised closinga:

• Move the thermoelectric fuse lever located to the side of the servomotor or disconnect the power supply.

fig. 1

fig. 1

fig. 2

fig. 2

fig. 3

fig. 3

fig. 4

fig. 4

9. REPLACING THE MECHANICAL FUSE

Warning !

All connection and maintenance operations must be carried out with the damper closed and the power supply discon-

nected.

• Check that the indicator on the control unit is set to CLOSE. If this is not the case, press the test button to close the 

damper manually.

• Remove the plastic cover by loosening the central fastener screw (fig.2).

• Unscrew the 3 cross-head screws and remove the release mechanism from the plate (fig.3).

• Replace the fuse by squeezing the spring and hooking it onto the two protruding pins (fig.4).

Summary of Contents for MDF30EURO

Page 1: ...making air better MDF30EURO INSTALLATION AND OPERATION MANUAL FIRE PROTECTION EN...

Page 2: ...RK 3 3 HANDLING AND INSTALLATION WARNINGS 4 4 MAINTENANCE 4 5 INSTALLATION IN BRICK WALLS 5 6 INSTALLATION IN CONCRETE FLOORS 6 7 INSTALLATION IN LIGHTWEIGHT WALLS 7 8 CONTROL FUNCTIONS 8 9 REPLACING...

Page 3: ...has been installed the control unit will remain outside the masonry to make post installation interventions easier When installed following the instructions provided in this manual it can be used in H...

Page 4: ...ch could prevent the correct operations of the commands outside the duct itself Keep as much access clearance as possible on the control unit side so as to ensure the user and maintenance operators ha...

Page 5: ...d to be installed with vertical axis Respect the dimensions shown fig 2 table 1 4 Fill in the space between the wall and the damper using fireproof cement material M10 cat or higher to reinstate resis...

Page 6: ...inst the damper casing so that it is blocked in the correct position fig 2 5 The metal brackets are designed to be fastened to the floor fig 3 6 Fill in the space between the floor and the damper usin...

Page 7: ...he side of the bracket supporting the damper does not protrude over the outer edge of the flange Use the threaded bolts supplied with the brackets to fix them in place fig 3 5 Position the damper insi...

Page 8: ...lectromagnetic circuit breaker Reset Power up the electromagnet electrical wiring diagram on page 8 Raise the metal lever on the control unit casing fig 1 Remove the reset lever from the housing compa...

Page 9: ...he key supplied with the delivery into the housing on the servomotor and turn it counter clockwise by half a turn to enable the spring return that will automatically move the servomotor into the close...

Page 10: ...Switch technical data Casing Fibre glass reinforced thermoplastic Protection rating EN 60526 Standard IP65 Cable cross section diameter rigid 2 5mm flexible with ferrule 1 5 mm Operating temperature...

Page 11: ...device consists of three fuses these make the fire damper shutters sensitive to the temperature inside the duct with Tf 2 and Tf 3 fuses which can be replaced and to ambi ent temperatures using the Tf...

Page 12: ...rofer it INSTALLER 19 143 43 211 70 55 500 210 21 30 051 Fax 210 22 23 283 BROFER SRL Via Roma 66 31023 Resana TV Italy Tel 39 0423 716611 Fax 39 0423 716612 info brofer it www brofer it making air be...

Reviews: