background image

3 | 

P a g e      

 

R e v 4 . 1

 

 

 
INSTALLATION – NOTES TO THE INSTALLER 

 
The LPG models & Natural models connected to a permanently fixed reticulated LP Gas supply, must be installed in 
accordance with AS/NZS 5601.1 by an authorised gas fitter / plumber

 

 

Where the LPG models are used in quasi-outdoor/indoor areas such as an alfresco or balcony situation the purchaser 
(consumer) may use an approved LP Gas regulator and hose assembly connected to a 4.5 or 9.0kg LP Gas cylinder. 
The use of 4.5 or 9.0kg LP Gas cylinders inside a building should be avoided

 

 
INSTALLATION 

Position of Wok Cooker outlet pipe at the rear of the unit: 

 

 

 

 
 

 

DC100-S Series 

 

DC200-S Series 

 

SAFETY PRECAUTIONS 

MAKE SURE YOU AND YOUR LICENSED GAS FITTER/PLUMBER CAREFULLY READ ALL OF THESE 
INSTRUCTIONS  BEFORE  INSTALLING  THE  APPLIANCE.  FOLLOW  ALL  WARNINGS  AND 
INSTRUCTIONS MARKED ON THE APPLIANCE. 
 

 

Do not install a damaged appliance. Contact Bromic if the appliance is damaged. 

 

Check the gas type of the appliance and make sure it is suited for the type of gas supplied. The data plate is 
located on the RH side panel of the appliance. Adhere the duplicate data plate to an accessible location near the 
appliance i.e. rear of a cupboard door. 

 

Make sure the gas inlet pipe is clean and not blocked before connecting the gas. 

 

Selecting a suitable position for the appliance is important to ensure maximum performance, economy and safety of 
operation.   

 

Always ensure that adequate fresh air is provided for ventilation. The minimum volume of the room where appliance 
is installed: 1.5 M2 per MJ. Refer to AS/NZS 5601.1 for details of the necessary ventilation requirements including 
the size of the openings. 

 

The appliance must only be operated on a level, firm non-combustible surface.  

 

This appliance shall not be installed in a position where it could create a fire hazard and the minimum clearances to 
combustible materials must be observed, as described below

CLEARANCES 

 

This appliance must be installed so that a vertical clearance of at least 600mm is maintained between its burners 
and any combustible material. Where it is not practical, the underside of any combustible material with a vertical 
clearance of less than 600mm above a burner should be protected by mill-board at least 6mm thick which is 
covered with sheet metal not less than 0.4mm thick, or protected by an equivalent material extending at least 
225mm beyond the sides of the cooker.  In either case, the vertical clearance above the cooker burner should not 
be less than 450mm.  
 

 

The minimum clearance from the appliance to rear or sides of combustible surfaces must be no less than 225mm. 
When the appliance is installed abutting a side or rear wall, the wall must be of non-combustible material, e.g. brick. 
If surrounding walls are constructed with a combustible material, contact your local Gas Authority for information on 
clearances required

.  

 

 

Combustible material 

Range hood 

Summary of Contents for DC100-S

Page 1: ...ory regulation s Refer to AS NZS 5601 1 for piping size details GAS PRESSURE REGULATOR DETAILS FOR NG MODELS The NG model they must be installed in accordance with AS NZS 5601 1 by an authorised gas fitter plumber A natural gas regulator Maxitrol RV20LM AGA Approval No 3088 with an outlet pressure of 1 0kPa is included with this appliance FOR LP MODELS Where the LPG models are connected to a perma...

Page 2: ...e and its effect on surrounding surfaces clothing and skin Children or the elderly should be supervised when near this appliance Do not hang clothing or other flammable material on or near this appliance Always keep flammable materials away from the appliance Make sure that you use cooking woks pots or pans that sit firmly on the trivet Do not use pots that are too small large for the burner size ...

Page 3: ...aximum performance economy and safety of operation Always ensure that adequate fresh air is provided for ventilation The minimum volume of the room where appliance is installed 1 5 M2 per MJ Refer to AS NZS 5601 1 for details of the necessary ventilation requirements including the size of the openings The appliance must only be operated on a level firm non combustible surface This appliance shall ...

Page 4: ... LP Gas Models Where the LPG models are connected to a permanently fixed reticulated LP Gas supply they must be installed in accordance with AS NZS 5601 1 by an authorised gas fitter plumber Where the LPG models are used in quasi outdoor indoor areas such as an alfresco or balcony situation the purchaser consumer may use an approved certified LP Gas regulator and hose assembly connected to a 4 5 o...

Page 5: ...e is off 7 The consumer fully understands the safety precautions operation and maintenance 8 The operation of the ignition system is satisfactory 9 The operation of the flame thermocouple safeguard is satisfactory 10 Flame abnormalities If any of the following are observed during operation of the appliance Carbon build up on the appliance or pans Excessive yellow tipping of the burner flame flames...

Page 6: ...s time press and hold the control knob for longer up to 10 seconds Warning Risk of deflagration 3 If after 10 seconds the flame does not ignite switch off the burner and open a nearby window or door Wait at least one minute before trying to switch the burner back again If the flame still does not ignite contact Bromic Pty Ltd or an authorized agent for assistance 4 Flame abnormalities If any of th...

Page 7: ...pan over the burner not to one side Otherwise it could tip over Place the pans on the pan supports never directly on the burner Make sure that the pan supports and burner caps are correctly positioned before using the appliance Pans should be placed on the hob carefully Do not strike the hob and do not place excessive weight on it CAUTION CORRECT PLACEMENT OF UTENSILS DO NOT SPRAY AEROSOLS IN THE ...

Page 8: ... clean these areas with a product that is suitable for stainless steel SERVICE INSTRUCTIONS FOR AUTHORISED PERSON such as LICENSED GAS FITTER OR PLUMBER DO NOT MODIFY THIS APPLAINCE Access to components under the hob Ensure the appliance is cool before attempting any service and the gas supply is turned off or disconnected Disconnect regulator or hose from gas supply Remove trivet s spillage bowls...

Page 9: ... 56 mm x 2 openings Primary air shutter in fully open position LP Gas Main burner inner primary aeration control 12 14 mm x 2 openings Primary air shutter in fully open position TROUBLESHOOTING Problem Possible Cause Solution No Ignition Main Gas Valve is not turned on Air trapped in the gas hose Electronic ignition is wet or dirty The safety valve is not open Turn off the gas valve once and then ...

Page 10: ...50 0 68 Dimensions mm H 145x W 300x D 382 H 145x W 720x D 382 Net Weight kg 3 7 6 6 Gas Type UNIVERSL LP GAS Gas Pressure kPa 2 75 Gas Fitting 5 8 18 UNF thread known as 3 8 SAE male fitting Ignition System Piezo electric Country of Origin China AGA Approval No 7092 G Bromic Pty Ltd and their appointed agents will not be liable in respect of any misuse which is not in accordance with the instructi...

Page 11: ...e the Purchaser for any investigation or service including parts and labour which is found not to be connected to a warranty issue Bromic is not liable for any incidental or consequential loss or damage arising from any cause whatsoever including but not limited to loss or damage arising from misuse of the Ring Burner neglect accident improper installation unauthorised modification unauthorised at...

Page 12: ...12 P a g e R e v 4 1 Call 1300 276 642 1300 BROMIC or 61 2 9426 5222 Email us plumbing bromic com au Visit www bromic com plumbing ...

Reviews: