Advanced operation
4.1
Reading and changing instrument parameters
4.1.1
Special parameters
All parameters described in this chapter affect the behavior of the IQ
+
FLOW®. Please be aware that wrong settings can
disorder the output. To avoid unintentional changes, some parameters are locked (shown by the
symbol). To unlock
parameters set parameter 'Init Reset' to 'Unlocked'.
Init Reset
Type
Access
Range
FlowDDE
FLOW-BUS
Modbus
Unsigned char
RW
82/64
7
0/10
0x000A/11
The 'Init Reset' parameter is used to unlock advanced parameters for writing. This parameter can be set to the following
values:
Value
Mode
Instrument action
82
Locked
Advanced parameters are read-only
64
Unlocked
Advanced parameters are writeable and readable
This parameter is always set to 'Locked' at power-up.
Control Mode
Type
Access
Range
FlowDDE
FLOW-BUS
Modbus
Unsigned int
RW
0…255
12
1/4
0x0024/37
The 'Control mode' is used to select different functions of the instrument. The following modes are available:
Value
Mode
Instrument action
Setpoint
source
Master
source
Slave
factor
0
BUS/RS232
Controlling
RS232/RS485
1
Analog input
Controlling
Analog input
2
FLOW-BUS slave
Controlling as slave of other instrument on
bus
FLOW-BUS *
slave factor /
100%
FLOW-
BUS
Slave
factor
3
Valve close
Close valve
4
Controller idle
Stand-by on BUS/RS232, Controlling is
stopped; Valve Out freezes in current position
5
Testing mode
Test mode enabled (factory only)
6
Tuning mode
Tuning mode enabled (factory only)
7
Setpoint 100%
Controlling at setpoint 100%
Fixed 100%
8
Valve fully open
Valve fully opened
9
Calibration
mode
Calibration mode enabled (factory only)
10
Analog slave
Controlling as slave of other instrument on
analog input
Analog input *
slave factor /
100%
Analog
input
Slave
factor
12
Setpoint 0%
Controlling at setpoint 0%
Fixed 0%
13
FLOW-BUS
analog slave
Controlling as slave of other instrument on
bus, slave factor is set with signal on analog
input
FLOW-BUS *
analog input *
slave factor /
100%
FLOW-
BUS *
analog
input
Analog
input