Bronkhorst®
Instruction Manual mini CORI-FLOW ML120
9.17.097G
48
Normal Step Response
Type
Access
Range
FlowDDE
FLOW-BUS
Modbus
Unsigned char
RW
0…255
72
114/5
0x0E45/3654
Response factor, applied to proportional action during normal control (at setpoint step).
·
Default value: 128 (no correction)
·
Other values adjust the controller gain (correction signal) as follows: Controller gain =
Controller Speed
*
PID-Kp
*
1.05
(response factor - 128)
Stable Situation Response
Type
Access
Range
FlowDDE
FLOW-BUS
Modbus
Unsigned char
RW
0…255
141
114/17
0x0E51/3666
Stable situation response, applied when the controller is stable (within a 2% band around the setpoint).
·
Default value: 128 (no correction)
·
Other values adjust the controller gain (correction signal) as follows: Controller gain =
Controller Speed
*
PID-Kp
*
1.05
(response factor - 128)