31
V. 1.3-24-04-19
brookvent.co.uk
T: +44 (0) 28 9061 6505
7.4 Fan Replacement
The aircycle 1.3 heat recovery system has a very straight forward fan replacement process
should the unlikely event of a fan failure occur.
Step 1.
Isolate the unit from the mains and ensure all supply
circuits are disconnected.
Step 2.
Unscrew the Fan cover (4 No. screws) and remove the cover.
Step 3
. Unplug the two leads from the fan.
Step 4.
Unscrew the locking screw on the fan mount.
Step 5.
Turn the fan mount anti-clockwise to the line marked on the fan case and then
pull straight out.
Step 6.
Place the new fan assembly in the fan case, lining it up with the line marked in
the fan case. Push inward until flush with the fan case and then turn clockwise to
tighten.
Step 7.
Refit the locking screw and connect the cables
Step 8.
Re-fit the fan cover and secure with the screws.
Step 9
. Power the unit on at the isolator and ensure any supply circuits are
reconnected. The unit will not need to be re-commissioned as the controller will hold
the settings.
Turn Fan mount until the edge
shown in green lines up with
the line on the fan case
(shown in red)