7. Commissioning
7.1 Commissioning RGT/RGTK
Following the correct installation of the RGT/RGTK room controller, the parame-
ters of the system controller are transferred to the room controller, which is then
ready for operation.
Note
: If only one room controller is installed, that will automatically be configured
as room controller 1. If a further room controller is installed, that must be configu-
red as room controller 2 under prog. no. 40 (see
Tab. 2
).
Tab. 2: Programming unit parameter
Prog. no.
Setting level
Function
Standard value
Programming unit
40
I
Use as
Room controller 1 | Room controller 2 | Programming
unit | Service unit
Room controller 1
42
I
Room controller 1 assignment
Heating circuit 1 | Heating circuit 1 and 2
Heating circuit 1
For detailed information on programming the integrated system controllers LMS,
LMU or RVS and setting tables with the programmable parameters, see the appli-
ance installation manual.
7.2 RGTF/RGTKF commissioning
with FEK receiver
Set up wireless connection
In order to set up the wireless connection between the FEK receiver and the RGTF/
RGTKF room controller, the following conditions must be met:
- the FEK receiver must be correctly connected at the boiler
- the batteries of the RGTF/RGTKF room controller must be inserted correctly
Note
: Ensure that the insulating strip has been removed from the battery com-
partment.
To set up the wireless connection proceed as follows:
1. Hold down the key on FEK receiver for at least 8 s until the LED on the FEK fla-
shes quickly
2. On the RGTF/RGTKF room controller call up the setting level "Wireless"
3. Select menu option "Binding" (prog no. 120), see
tab. 3
)
4. Select option
"Yes"
to start building the connection
Note
: The status of the connection process will be shown in the display of the
room controller. Connection has been made when the LED on the receiver extin-
guishes. This can take up to 2 min.
For information on changing parameters, see the boiler installation manual.
Commissioning
34
RGT B/RGTK B and RGTF B/RGTKF B room controller
136 231 03.11
GB