Broyce Control Ltd., Pool Street, Wolverhampton, West Midlands WV2 4HN. England
Tel: +44 (0) 1902 773746 Fax: +44 (0) 1902 420639 Email: sales@broycecontrol.com Web: www.broycecontrol.com
The Information provided in this literature is believed to be accurate (subject to change without prior notice); however, use of such information shall be entirely at the user’s own risk.
ELR01PN_30PN-1-A.DOCX
Page
1
of
3
1811
Dims: to DIN
43880
W. 44mm
•
FUNCTION DIAGRAMS
The following operational modes are either enabled using the app or by adding external links
Latching mode (factory default)
Auto-reset mode (enabled via app)
Terminal
Protection
to IP20
Programmable user settings/adjustments
Built-in NFC (Near Field Communication) allows user to access and change settings via
compatible Smartphone/Device with installed app^ as well as retrieve historical data
Two models available 6mA – 1A (ELR01PN) and 30mA – 30A (ELR30PN) – True R.M.S.
measurements
Option to select alternative toroid ratio, tripping method (latch or auto-reclosure modes),
Output relay logic (pre-alarm, energise or de-energise on trip) and filter cut-off points
Connection facility for remote “Test” and “Reset” push buttons or N.O. contacts
Toroid open and short-circuit detection forces unit to trip (Red LED flashes during this condition)
2 Relay outputs – Relay 1 (SPDT) and Relay 2 (SPNO) - User configurable
Wide auxiliary operating supply voltage - 24 – 230V AC/DC
Compliant with IEC 60947-2 / Annex M
Type: ELR01PN/30PN
Earth Leakage Relay – Type A (with NFC Technology)
^ App available from:
Continued…..
Auto-reclosure mode (enabled via app)
Pre-Alarm mode (enabled via app)
Note: relays are shown operating in their factory default states i.e. RLY1 = Standard Output
and RLY2 = Positive Safety Output (Pre-Alarm default states are RLY1 and RLY2 = Standard
Output)
Aux. Supply
5, 7
13
12
14
Pre-alarm trip
level (50% x I n)*
∆
∆
t
Fault Current
10
11
Test/Reset button
∆
t
25%
50%
75%
ELR_PA0216
RLY1
RLY2
Trip level (I n)
∆
Reset level
Reset
Test
Reset
•
OVERVIEW
The ELR…PN is a fully featured, Earth Leakage Relay that can either be easily configured using the built-in pre-defined “Profiles” or tailored specifically to suit the
application. The app^ allows the user to define how the unit should operate (see Function diagrams below) as well as configure and set parameters such as the toroid
ratio, relay logic (i.e. energise or de-energise on trip) and define how the Auto-Reclosure mode should operate. Additionally, the option to set a filter cut-off point can
also be defined therefore allowing the unit to ignore signals above a certain frequency.
Utilising NFC technology allows the unit to be used in a “Passive” mode whereby settings can be made in the app and written to the unit without the need for the unit
to be powered. This feature is useful where a panel needs to be shut down and power removed (for safety reasons) before any work or alterations need to be made.
The user also has the ability to read back the configuration of a unit using the app in order to establish/check the settings. Additionally, it is possible to measure (and
display) the actual leakage current present in the system.
An option to recall previous tripping information (accessed via the Logs option in the app) provides the user with historical data allowing the user to establish a pattern
in the tripping occurrence’s and hence make any necessary adjustments.