background image

 

 
 

Broyce Control Ltd., Pool Street, Wolverhampton, West Midlands WV2 4HN. England 

Tel: +44 (0) 1902 773746 Fax: +44 (0) 1902 420639 Email: sales@broycecontrol.com Web: www.broycecontrol.com 

                   The Information provided in this literature is believed to be accurate (subject to change without prior notice); however, use of such information shall be entirely at the user’s own risk.

 

 

P50EFR-4-A.DOCX 

Page 

2

 of 

1806 

 

 

  

 

 

DIMENSIONS 

 

 

 

CONNECTION DIAGRAM 

  

 

 

 

TECHNICAL SPECIFICATION (continued) 

 

Output (continued) 

Electrical life:

 

DC load capacity:

 

 
 

  

  

 

Switching current (A) 

 

 
 

 

 

DC current (A) 

 

 

 

 

 

 

 

Dielectric voltage: 

1kV AC (rms) IEC 60947-1 

Rated impulse withstand voltage: 

4kV (1.2/50

µ

S) IEC 60664-1 

 

 

Housing 

 

Material: 

Grey flame retardant Lexan UL94 V0 

Weight: 

≈ 225g 

Protection: 

IP40 (front face) / IP20 (rear) 

Mounting: 

Panel mount. Cut-out (see information below) 

Max. panel thickness: 

10mm 

 

Rear Terminals 

Conductor size: 

 

0.3 – 2mm

2

 (22 – 14AWG) 

Wire stripping length: 

≈ 6mm 

Recommended tightening torque: 

1.3Nm (12lb-in) 

 

 

Standards 

Product: 

 

IEC 255-3, IEC 60255-151 

EMC: 

IEC 60255-26, IEC 61000-4 Series 

 

CE and RoHS Compliant. C-tick 

 

 

Ordering: 

Please specify product part number and voltage when ordering.  

For example: 

P50EFR/2 230V AC 

 

 

Type: P50EFR & P50EFR/2 

Earth Fault Relay (Definite Time – DT)

 
 

 

TECHNICAL SPECIFICATION 

 

Auxiliary Power Supply (1, 8) 

Supply voltage (Un): 

115V or 230V AC (To be specified when ordering) 

Frequency range: 

50/60Hz 

Supply variation: 

85 – 115% of Un 

Auxiliary supply is galvanically isolated from the CT input 

Overvoltage category: 

III 

Rated impulse withstand voltage: 

4kV (1.2/50

µ

S) IEC 60664-1 

Power consumption (max.): 

3VA 

 

 

Monitored input (via external Current Transformer connected to terminals 2 and 7) 

Rated current input (In): 

5A (directly connected) 

Rated frequency: 

50Hz 

Burden: 

<0.4VA @ In 

Overload: 

4 x In (continuous) 

CT recommendation: 

Class P (with 5A secondary) 

 

 

Device Characteristics 

Measurement principle: 

True R.M.S. 

Trip current [Current setting] 
(Io>): 

0.10 – 2.0A (2 – 40%) 

Time delay [Operating time] (t): 

0.05 – 1.0s 

Pick up value: 

+2% of trip value 

Accuracy: 

 

 Trip current:  

±

 5% 

 Time delay: 

±

 5% (with a minimum of 50ms) 

Repeat accuracy: 

±

 0.5% @ constant conditions 

 

 

LED indication 

 

Power Supply: 

 

Green x1 

 

Tripped:  

Red x 1 

 

 

 

Test and Reset 

“Test” method 
(assuming unit is in the non-
tripped state): 

Press once to trip the unit 

“Reset” method 
(assuming unit is in the tripped 
state and fault current cleared): 

Press once to reset the unit 

 

 

Temperature rating

 

 

Operating: 

P50EFR

 

P50EFR/2

 

 

-10 to +60

°

-10 to +55

°

Storage: 

-30 to +70

°

Relative humidity: 

+95% max. 

 

 

Output - Model No./Type 

P50EFR 

P50EFR/2 

Rear Terminal No. 

(3, 4, 5) 

(3, 4 / 5, 6) 

Contact arrangement: 

1 x SPDT 

2 x SPNO 

 

AC1 (250V) 

8A (2000VA) 

3A (750VA) 

 

AC15 (250V) 

2.5A 

1.5A 

 

DC1 (25V) 

8A (200W) 

3A (75W) 

 

 

 

 

 

 
 
 
 

 

C

y

cl

e

D

C

 V

o

lt

a

g

e

 (

V

Resistive 
load 

250V AC 

AC1 

Resistive load 

 

CUT-OUT 

 

Key:  

      P50EFR         

             P50EFR/2 

Reviews: