Housing:                       Flame retardant Lexan 
Protection:                     IP55 / IP20 (rear) 
Weight:                       

 450g 

Mounting:                     Panel mounting. Cut-out = 91 x 91mm (

±

 0.5mm) 

Max. panel thickness:          12mm 

 

Terminal conductor size:      0.05 - 2.5mm

2

 (30 - 12AWG) 

Recommended tightening 
 torque:                        10in lb (1Nm) 
Wire stripping length:         0.24 – 0.30in (6 – 7.5mm) 

 

Approvals:                     Conforms to IEC. CE and       and RoHS Compliant. 

 EMC: Immunity: EN/IEC 61000-6-2 

       Emissions: EN/IEC 61000-6-4 

Generic: IEC 60255-26 (EMC), IEC 255-3, IEC 

60255-151 

 

( ) Bold digits in brackets refer to terminal numbers on the rear of the unit. 

 
Options: 
 

 

The P9600 range also includes individual Overcurrent or Earth fault relays 

available with either IDT or IDMT tripping characteristics. Please refer to separate 
data sheets. 

 

 

 
 
 
 
 
 
 
 
 
    

 

 

 

TECHNICAL SPECIFICATION 

 
Supply voltage Un (

1, 2

):        115VAC 

±

15% 

                                  230VAC 

±

15% 

                               

  (Voltage should be specified at time of   ordering) 

Rated frequency:                50/60Hz 
Isolation:                         Over voltage cat. III 
Rated impulse  
 withstand voltage:              4kV (1.2 / 50

µ

S) IEC 60664 

Power consumption:            3W max. 

 

Rated current input In:          5A (directly connected) 
Rated frequency:                50Hz 
Burden:                          <0.4VA @ In 
Overload:                       4 x In (continuous) 

 

External CT’s (

15, 16

):          Class P recommended. (with 5A secondary) 

 

Earth fault settings: 
 Low-set trip (I

o

>):              0.10 – 2.0A (2 – 40%) 

 Low-set definite time (t>):     0.05 – 1.0s 
 High-set trip (I

o

>>):           x1 – x10 or disable (

 High-set definite time:          Instantaneous (<50mS) 

 

Pick up value:                    +2% of trip setting 
Accuracy: 
 Protection thresholds:         

±

 5% 

 Time delay (DT):              

±

 5% (with a minimum of 50mS) 

Repeat accuracy:               

±

 0.5% @ constant conditions 

 

Ambient temperature:          -10 to +60

°

Relative humidity:               +95% (non-condensing) 

 

Output: 
 (RL1 - 

3, 4, 5

):                  1 x SPDT relay 

Output rating:                   AC1  250V 8A (2000VA) 
                                  AC15  250V 5A (1250VA) 
                                  DC1 25V 8A (200W) 
Electrical life:                    

 150,000 ops at rated load 

Dielectric voltage:               2kV AC (rms) IEC 60947-1 
Rated impulse 
 withstand voltage:              4kV (1.2 / 50

µ

S) IEC 60664 

 

         

 

 

                 Max. DC Load Breaking Capacity                          Electrical Endurance 

 

 

CONNECTION DIAGRAM

 

 
 

L1

L2

L3

N

A1 A2

RL1

Aux.

9

I

o

11

10

12

13

14

15

16

1

3

2

4

5

6

7

8

 

 

DIMENSIONS

 

 

 

 

96

96

   

10

95

89.5

96

12

80

 

              Front view                                             Side view 

   

  All dimensions are in mm.

 

 

 

 

   

 

Reviews: