P9660-2-A

  6

6

6

6    

012378 

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Electrical life:                    

 150,000 ops at rated load 

Dielectric voltage:               2kV AC (rms) IEC 60947-1 
Rated impulse 
 withstand voltage:              4kV (1.2 / 50

µ

S) IEC 60664 

 
 
 
 
 
 
 
 
 
 

                 Max. DC Load Breaking Capacity                    Electrical Endurance 

 
Housing:                       Flame retardant Lexan 
Protection:                     IP55 / IP20 (rear) 
Weight:                       

 410g 

Mounting:                     Panel mounting. Cut-out = 91 x 91mm (

±

 0.5mm) 

Max. panel thickness:          12mm 
 
Terminal type: 

UL94 V-0 rated pluggable and re-wireable female 
connectors comprising: 

                                2-way (Power supply 

1, 2

                                6-way (Relay contacts 

3….8

                                8-way

 

(CT input 

15, 16

Note that terminals 

9 to 14

 are not used on this 

model and should be left unconnected.  

Terminal conductor size:      0.05 - 2.5mm

2

 (30 - 12AWG) 

Recommended tightening 
 torque:                        4.4in lb (0.5Nm) 
Wire stripping length:         0.24 – 0.30in (6 – 7.5mm) 
 
Approvals:                     Conforms to IEC. CE and       and RoHS Compliant. 

 EMC: Immunity: EN/IEC 61000-6-2 

       Emissions: EN/IEC 61000-6-4 

Generic: IEC 60255-26 (EMC), IEC 255-3, IEC 

60255-151 

 

( ) Bold digits in brackets refer to terminal numbers on the rear of the unit. 

 

Options: 
 

 

The P9600 range also includes combined Overcurrent or Earth fault relays 

available with either IDMT or DT characteristics. Additionally, a voltage, power 
and frequency monitoring only product is also available. Please refer to separate 
data sheets. 

 

 

 
 
 
 
 
 
 
 
 

 

 

 

 

TECHNICAL SPECIFICATION 

 
Aux. Supply voltage Un (

1, 2

):  85 – 265VAC/85 - 370VDC

1

 

                                  18 – 55VAC/18 – 72VDC* 
                               

  (Voltage range should be specified at time of        

                                   ordering) 

Rated frequency:                50/60Hz (AC Supplies) 
Isolation:                         Over voltage cat. III 
Rated impulse  
 withstand voltage:             

1

4kV (1.2 / 50

µ

S) IEC 60664 

Power consumption:            3W max. 

* If connecting a fuse externally, a Time Delay type is recommended with a rating of 0.5A or 
higher. 

 
Rated current input In:          5A (directly connected) 
Rated frequency:                50/60Hz 
Burden:                          <0.4VA @ In 
Overload:                       4 x In (continuous) 
 
External CT (

15,16

):              Class P recommended. (with 5A secondary) 

Maximum CT primary 
 current rating:                   6000A  
 
Earth fault settings: 
 Low-set trip (I

o

>):              0.10 – 5.00A (2 – 100%) 

 Low-set time multiplier (k

o

>): 0.05 – 1.00 

 Low-set definite time (t

o

>):    0.05 – 100s 

 High-set trip (I

o

>>):           0.10 – 50.0A (2 – 1000%) or disable 

 High-set definite time (t

o

>>): 0.05 – 2.5s 

 
Pick up value:                    +2% of trip setting 
Accuracy: 
 Protection threshold:          

±

 5% 

 Time delay (DT):              

±

 5% (with a minimum of 50mS) 

 Time delay (IDMT): 

±

 5% (with a minimum of 50mS and I > 1.2 x 

set-trip) 

Actual Earth fault current:      

±

 1% of rated current In 

Display update time:            <1 sec. 
Repeat accuracy:               

±

 0.5% @ constant conditions 

 

Ambient temperature:          -10 to +60

°

Relative humidity:               +95% 
 
Output: 
 (RL1 - 

3, 4, 5

):                  1 x SPDT relay 

 (RL2 - 

6, 7, 8

):                  1 x SPDT relay 

Output rating:                   AC1  250V 8A (2000VA) 
                                  AC15  250V 5A (1250VA) 
                                  DC1 25V 8A (200W) 

 
 

 

 
 
 
 
 

 

CONNECTION DIAGRAM

 

 

L1

L2

L3

N

A1

A2

RL1

RL2

Aux.

1 2

3

4

5 6

7

9

8

10 11 12 13 14

16

15

I

N

 

 

DIMENSIONS

 

 

 

 

96

96

   

MADE IN U.K.

10

100

89.5

96

 

           Front view                                                          Side view 

   

  All dimensions are in mm.

 

 

 

 