background image

 

  

 

 

 
 

 
 
 
 
 

 

 

 

 
 

 

Broyce Control Ltd., Pool Street, Wolverhampton, West Midlands WV2 4HN. England 

Tel: +44 (0) 1902 773746 Fax: +44 (0) 1902 420639 Email: sales@broycecontrol.com Web: www.broycecontrol.com

 

The information provided in this literature is believed to be accurate (subject to change without prior notice); however, use of such information shall be entirely at the user’s own risk

P9680-3-A

  5

5

5

5    

012376 

 

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 
 
 
 
 
 
 
 
 
 

I

L1

 

 

20.70

A

    

I> 

I

L2

 

 

40.00

A    

 

I

L3

 

 

27.50

A  

 

I

O

 

  

0.00

A    

 

Phase with fault

 

I

L1

 

 

20.70

A

    

I>> 

I

L2

 

 

89.00

A    

R1    R2

 

I

L3

 

 

27.50

A  

 

I

O

  

   

0.00

A

 

I

L1

 

 

0.00

A

  

 

I

L2

 

 

0.00

A

      

 

I

L3

 

 

0.00

A    

Io>

 

I

O

 

  

1.00

   

 

I

L1

 

 

0.00

A

  

 

I

L2

 

 

0.00

A

    

 

I

L3

 

 

0.00

A    

Io>>

 

I

O

 

  

8.00

    R1 

 

Low-set  
triggered 
 

High-set 
triggered 

 

Relay(s) which 
energised on 
tripping

 

Low-set 
triggered

 

High-set 
triggered 
 
Relay(s) which 
energised on 
tripping

 

    

Earth fault 

current 

 

OVERCURRENT 

fault occurs 

Low-set I> 

triggered

 

Run IDMT or DT 

delay t> 

Run DT delay 

t>>

 

High-set 

I>> 

triggered? 

TRIP! 

Delay 

t> 

complete? 

Delay 

t>> 

complete? 

START 

EARTH FAULT 

occurs 

Low-set I

o

triggered

 

Run IDMT or DT 

delay t

o

Run DT delay 

t

o

>>

 

High-set 

I

o

>> 

triggered? 

TRIP! 

Delay 

t

o

complete? 

Delay 
t

o

>> 

complete? 

START 

 

TRIPPING MODES 

 

1. OVERCURRENT 

 

 

A fault which develops on a phase will be indicated by an increase in current 
reading on the LCD. When the level of current exceeds the Low-set setting, 
the phase at fault will be highlighted by the digits flashing.

 

 

The LCD backlight will flash.

 

 

Relay 2 will energise if assigned to Overcurrent and set to energise at the start 
of the time out period (See Section 3. RELAY 2 SETTING).

 

 

The characters 

“I>”

 will display to indicate the Low-set has been triggered. 

 

 
 
 
 

 
 
 
 
 
 
 
 
 
 
 

 

If the current continues to increase above the High-set setting, the

 

characters 

“I>”

 will change and display 

“I>>”

 to indicate the High-set has been 

triggered. 

 

 
 
 
 
 

 

When the unit finally trips, the digits of the phase at fault will stop flashing and 
remain highlighted. This allows the user to see which phase was at fault and 
caused the unit to trip.

 

 

The red “Tripped”

“Tripped”

“Tripped”

“Tripped” LED will also flash.

 

 

The relays which energised are also displayed on the screen after tripping.

 

 

Press 

to reset and return the unit back to normal operation (assuming 

the fault has been cleared). The LCD reverts back to displaying the normal 
system currents and the red “Tripp

“Tripp

“Tripp

“Tripped”

ed”

ed”

ed” LED stops flashing.

 

 

If either relay is set for Auto resetting, then they would have de-energised after the 

fault had cleared. The corresponding relay ident (i.e. R1 and/or R2) on the display 
would also disappear. Pressing the “RESET” 

“RESET” 

“RESET” 

“RESET” button will only clear the LCD. If either 

relay is set for Manual resetting, then pressing the “RESET”

“RESET”

“RESET”

“RESET” button will de-energise the 

relay(s) and clear the LCD.

 

 

In the event of an Overcurrent condition, the basic sequence of events is 
shown below. 

Assuming High-set trip is enabled.

 

 

2. EARTH FAULT 

 

 

When an Earth fault occurs causing a flow in current through the Neutral, an 
increase in current reading on the LCD will occur. When the level of current 
exceeds the Low-set setting, the reading will be highlighted by the digits 
flashing.

 

 

The LCD backlight will flash.

 

 

Relay 2 will energise if assigned to Earth fault and set to energise at the start of 
the time out period (See Section 3. RELAY 2 SETTING).

 

 

The characters 

“Io>”

 will display to indicate the Low-set has been triggered. 

 

 
 
 
 
 
 

 

If the current continues to increase above the High-set setting, the

 

characters 

“Io>”

 will change and display 

“Io>>”

 to indicate the High-set has been 

triggered. 

 

 
 
 
 
 
 
 
 

 

When the unit finally trips, the digits will stop flashing and remain highlighted. 
This allows the user to see what caused the unit to trip.

 

 

The red “Tripped”

“Tripped”

“Tripped”

“Tripped” LED will also flash.

 

 

The relays which energised are also displayed on the screen after tripping.

 

 

Press 

to reset and return the unit back to normal operation (assuming 

the fault has been cleared). The LCD reverts back to displaying the normal 
system currents and the red “Tripped”

“Tripped”

“Tripped”

“Tripped” LED stops flashing.

 

 

 If either relay is set for Auto resetting, then they would have de-energised after the 

fault had cleared. The corresponding relay ident (i.e. R1 and/or R2) on the display 
would also disappear.  Pressing the “RESET”

“RESET”

“RESET”

“RESET” button will only clear the LCD. If either 

relay is set for Manual resetting, then pressing the “RESET”

“RESET”

“RESET”

“RESET” button will de-energise the 

relay(s) and clear the LCD. 
 

In the event of an Earth fault condition, the basic sequence of events is shown 
below. 

Assuming High-set trip is enabled.

 

 

 

Summary of Contents for P9680

Page 1: ...or both Overcurrent and Earth fault detection The time current characteristic of the low set units are selectable between Normal Inverse curve 3 10 Normal Inverse curve 1 3 10 Long Time Inverse curve Very Inverse curve Extremely Inverse curve Extremely Inverse 0 65 curve and Definite Time High set units are the Definitive Time type Instantaneous tripping is possible by setting the time to minimum ...

Page 2: ...occurred continued on next page INSTALLATION BEFORE INSTALLATION ISOLATE THE SUPPLY THIS PRODUCT IS DESIGNED TO CONNECT TO SEVERAL TYPES OF CIRCUITS ENSURE ALL ARE ISOLATED Remove the P9680 P9680 P9680 P9680 from the packaging Lift the raised part of the side clip in order to withdraw from the housing Carry this out on each side Insert the P9680 P9680 P9680 P9680 into the panel cut out and fit the...

Page 3: ...TTING Default setting for Relay 2 is linked to O C E F and energising at the end of the time out period Resetting mode is Auto Setting of Relay 2 is carried out in a similar manner as Relay 1 however it is necessary to assign the relay to either energise at the start S or end E of the time out period Actual LCD presentation when adjustable parameters are displayed Press and hold the button to set ...

Page 4: ...further button presses are made If a trip condition occurs whilst in this mode the screen will automatically change to display the information relating to the current status As described in Section 8 use the to gain access to the Last Tripped Information screen The display will show the most recent trip information as follows If more than one trip event is stored use the and buttons to select the ...

Page 5: ...een cleared The LCD reverts back to displaying the normal system currents and the red Tripp Tripp Tripp Tripped ed ed ed LED stops flashing If either relay is set for Auto resetting then they would have de energised after the fault had cleared The corresponding relay ident i e R1 and or R2 on the display would also disappear Pressing the RESET RESET RESET RESET button will only clear the LCD If ei...

Page 6: ...0 05 t t t t s s s s 10 1 0 1 0 01 t t t t s s s s Normal Inverse 3 10 Normal Inverse 3 10 Normal Inverse 3 10 Normal Inverse 3 10 NI 3 10 NI 3 10 NI 3 10 NI 3 10 t t t t s s s s k k k k 1 0 0 9 0 8 0 7 0 6 0 5 0 4 0 3 0 2 0 1 0 05 10 1 0 1 1 10 20 I I I I I I I I Long Time Inverse Long Time Inverse Long Time Inverse Long Time Inverse LTI LTI LTI LTI 200 100 10 1 0 1 k k k k 1 0 0 9 0 8 0 7 0 6 0 ...

Page 7: ...e Un 1 2 85 265VAC 85 370VDC1 18 55VAC 18 72VDC Voltage range should be specified at time of ordering Rated frequency 50 60Hz AC Supplies Isolation Over voltage cat III Rated impulse withstand voltage 1 4kV 1 2 50µS IEC 60664 Power consumption 3W max If connecting a fuse externally a Time Delay type is recommended with a rating of 0 5A or higher Rated current input In 5A directly connected Rated f...

Reviews: