background image

 

 

 

 
 

 
 
 
 
 

 

 

 

 
 

 

Broyce Control Ltd., Pool Street, Wolverhampton, West Midlands WV2 4HN. England 

Tel: +44 (0) 1902 773746 Fax: +44 (0) 1902 420639 Email: sales@broycecontrol.com Web: www.broycecontrol.com

 

The information provided in this literature is believed to be accurate (subject to change without prior notice); however, use of such information shall be entirely at the user’s own risk

P9680[C]-5-A.DOCX

  3

3

3

3    

2006 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

6. MODBUS SETTING (P9680C only) 
 

 

 

Here there is the option to set the Address, Baud rate and Parity. Use the e 

 button to select the different parameters.

 

 
 
 
 
 

 

Actual LCD presentation when adjustable parameters are displayed. 

 

 

Press either 

 or 

to change the parameter values.

 

 

Press and hold the 

 button to see a summary of the “OVERCURRENT”

“OVERCURRENT”

“OVERCURRENT”

“OVERCURRENT” 

then “EARTH FAULT”

“EARTH FAULT”

“EARTH FAULT”

“EARTH FAULT” settings as described in the next section. 

 
7. OVERCURRENT & EARTH FAULT SUMMARY  

It is not possible to edit settings when these screens are displayed. 

 

 

Following the setting of “Earth Fault”, the LCD displays the “Overcurrent 
Summary” screen showing a summary of the settings made during 
programming. All settings are displayed. The selected CT ratio, Network 
Frequency and Relay operation (following a Reset) information is also 
displayed.

 

 
 
 
 
 

 
 

 

Press and hold the 

 button to display the 

 

       “Earth Fault Summary” screen.

 

 

 

 
 
 

 

 

8. SAVING OF SETTINGS

 

 

If after viewing the Summary screens the settings are correct, press and hold 

the 

 button until the word “Saved.”

“Saved.”

“Saved.”

“Saved.” appears. Any new settings are now 

stored.

 

 

The screen will revert back to Normal operation.

 

 

8. QUICK VIEW OF USER SETTINGS

 

It is not possible to edit settings when these screens are displayed. 
This feature can also be activated with the front window closed! 

 

Press and hold the 

 button to display the initial power up screen. 

 

Press the same button again to display the “Last Tripped Information” screen 
(

refer to the next page for further information on this feature).

 

 

Press again to display the “Overcurrent Summary” screen. 

 

Press again to display the “Earth Fault Summary” screen. 

 

Press again to display the contact details for Broyce Control. 

 

Press again to revert back to Normal operation. 

 

9. LAST TRIPPED INFORMATION

 

Refer to next page for detailed information of this feature 

 

Notes during programming 

If during programming it is necessary to abort, press the  

 

button briefly.

    

Pressing and holding either

 

 

or

 

for >1sec. will increment or decrement 

the new value at a quicker rate. 

Stepping through each User Setting screen is performed by pressing and holding 

the 

button until the desired screen is displayed.  

Short presses of the 

button will allow further editable settings to be changed 

within a specific screen. 

If the user remains in a setting or summary screen where no adjustments or button 

presses are made within a certain period, the screen will revert back to Normal 
operation. Additionally, any settings that have been made but not stored will not be 
saved. 

”O/C” refers to Overcurrent and “E/F” refers to Earth fault.

 

 

PROGRAMMING (continued) 

 

 

Press and hold the 

 button to set the options for “Relay 2” 

Relay 2” 

Relay 2” 

Relay 2” as described 

in the next section. 

 
3. RELAY 2 SETTING 

Default setting for Relay 2 is linked to “O/C & E/F” and energising at the end of the 

time out period. Resetting mode is Auto. 

 

 

Setting of “Relay 2” is carried out in a similar manner as “Relay 1”, however it 
is necessary to assign the relay to either energise at the start (S) or end (E) of 
the time out period.

 

 
 
 
 
 

 

Actual LCD presentation when adjustable parameters are displayed. 

 

 

Press and hold the 

 button to set the options for “OVERCURRENT” 

“OVERCURRENT” 

“OVERCURRENT” 

“OVERCURRENT” as 

described in the next section. 

 

4. OVERCURRENT SETTING 

The description for the Curves is abbreviated when displayed on the screen. Refer 

to “IDMT Characteristic Curves” for further explanation. 

Default settings for Overcurrent are shown in the last LCD screen example in this 

section. 

 

 

Settings for Overcurrent are displayed in turn following subsequent presses of 

the 

 button.  The Low-set trip current (I>) is displayed first.

 

 
 
 
 

 

 

 

Press either 

 or 

to change the current.

 

 

Press the 

 button to select the remaining settings and use the 

 and 

buttons to change them.

 

 
 
 
 
 

 

Actual LCD presentation when adjustable parameters are displayed.  

Screen example above also shows the default settings for OVERCURRENT. 

 

Press and hold the 

 button to set the options for “EARTH FAULT” 

“EARTH FAULT” 

“EARTH FAULT” 

“EARTH FAULT” as 

described in the next section. 

 

If the Curve in selection “2:” is set to Definite Time, then selection “3:” will display 

“3: t>” and the required delay can then be set. 

If High-set is set to Disable in selection “4:”, then I>> or t>> cannot be 

adjusted.

 

 

5. EARTH FAULT SETTING 

Default settings for Earth Fault are shown in the LCD screen example in this 

section. 

 

 

Settings for Earth Fault are carried out the same as described for Overcurrent. 

 

 
 
 
 
 

 

Screen example showing the default settings for EARTH FAULT. 

 

 

Press and hold the 

 button for either: 

 

Summary of the “OVERCURRENT”

“OVERCURRENT”

“OVERCURRENT”

“OVERCURRENT” then “EARTH FAULT”

“EARTH FAULT”

“EARTH FAULT”

“EARTH FAULT” settings 

(Model: P9680) 

 

Option to change the MODBUS settings (Model: P9680C) 

 

If the Curve in selection “2:” is set to Definite Time, then selection “3:” will display 

“3: to>” and the required delay can then be set. 

If High-set is set to Disable in selection “4:”, then Io>> or to>> cannot be 

adjusted.

 

 

O/C SETTING 

Low set 

    1: I>  5.00A 

    

 

RELAY 

2

 CONFIGURATION 

 

  1:           2:          

  O/C         

AUTO (E)

 

  E/F          MAN (E)

 

 

O/C & E/F       

AUTO (S) 

              MAN (S) 

 

O/C SETTING 

Low Set: 

    1: I>  5.00A 

    2: Curve NI 3/10 

    3: k> 0.1 

High Set: 

    4: I>> 50.00A 

    5: t>> 0.05s 

E/F SETTING 

Low Set: 

    1: Io> 2.00A 

    2: Curve NI 3/10 

    3: k> 0.1 

High Set: 

    4: Io>> 10.00A 

    5: to>> 0.05s 

O/C  SUMMARY   

  I>  5.00A 

  NI   3/10 

  k>  0.1 

  I>>50.00A 

  t>>0.05s 

  R1 = MAN  R2 = AUTO (E) 

  CT=5:5, FREQ=50Hz 

E/F  SUMMARY                   

  Io>   2.00A 

  NI   3/10 

  ko>   0.1 

  Io>>10.00A 

  to>>0.05s 

  R1 = MAN  R2 = AUTO (E) 

  CT=5:5, FREQ=50Hz 

The letter in brackets refers to 
whether Relay 2 has been set 
to trigger at the start or end of 
the time out period. 
(E) = E

EE

End of time out 

(S) = S

SS

Start of time out 

Either abbreviation can appear 
after the word MAN or AUTO 

See Section 3. RELAY 2 
SETTING 

MODBUS 

 

            ADDR   1 

            BAUD   9600 

           PARITY    None 

 

 

   

 

 

Summary of Contents for P9680C

Page 1: ...iving early warning before a system actually shuts down Low set and High set thresholds can be programmed for both Overcurrent and Earth fault detection The time current characteristic of the low set...

Page 2: ...occurred continued on next page INSTALLATION BEFORE INSTALLATION ISOLATE THE SUPPLY THIS PRODUCT IS DESIGNED TO CONNECT TO SEVERAL TYPES OF CIRCUITS ENSURE ALL ARE ISOLATED Remove the P9680 P9680 P96...

Page 3: ...fers to Overcurrent and E F refers to Earth fault PROGRAMMING continued Press and hold the button to set the options for Relay 2 Relay 2 Relay 2 Relay 2 as described in the next section 3 RELAY 2 SETT...

Page 4: ...further button presses are made If a trip condition occurs whilst in this mode the screen will automatically change to display the information relating to the current status As described in Section 8...

Page 5: ...been cleared The LCD reverts back to displaying the normal system currents and the red Tripped Tripped Tripped Tripped LED stops flashing If either relay is set for Auto resetting then they would hav...

Page 6: ...0 05 t t t t s s s s 10 1 0 1 0 01 t t t t s s s s Normal Inverse 3 10 Normal Inverse 3 10 Normal Inverse 3 10 Normal Inverse 3 10 NI 3 10 NI 3 10 NI 3 10 NI 3 10 t t t t s s s s k k k k 1 0 0 9 0 8...

Page 7: ...tch female connector supplied with unit Recommended wiring type 2 core shield twisted pair 24AWG i e Belden type 9841NH TECHNICAL SPECIFICATION Aux Supply voltage Un 1 2 85 265VAC 85 370VDC1 18 55VAC...

Page 8: ...is as follows Address 1 Address 2 Address n Modbus Master The P9680C is provided with a Modbus termination switch It is recommended that for the last unit connected in the system the switch is set to...

Reviews: