Operating the VIBROCONTROL 1500
VIBROCONTROL 1500
VC1500EN / C103845.002 / V 09 / 14.04.2015
- 33 -
In the setup menu the reference value can be reset by a return to zero in the
channel setup, which e.g. becomes necessary after a bearing exchange, and
the entire procedure repeats itself as described above.
VIBROCONTROL 1500 monitors the BC value with the help of two
adjustable limit values designated as L1BC and L2BC. Beyond that it stores
and visualizes the BC trend as averaging of Avg-Values and provides the
frequencies and amplitudes of the three dominant vibration components
within the range of 500 to 5,000 cycles per second for damage identification.
With the help of the visualization software
VIBROCONTROL 1500 Control-
Center
-
Software
the trend and frequency analysis of rolling-element bearing
condition can be displayed with a higher resolution and in a greater extent.
Course of the measurement of the rolling-element bearing condition.
Fig.17: Menu for rolling-element bearing condition
After confirming the button
ENTER/MENU,
the display for selection of the
channel appears, with the calculation/analysis is to done. The channel is
selected using the pushbuttons
and
.
Fig.18: Channel selection
The calculation / analysis is started by pushing the button
ENTER
.
Fig.19: Display during the analysis
After the bearing condition analysis is completed the result is displayed.
During the first 8 hours after a reset of the trend measurement, the following
value will be displayed: Bearing condition reference value
Ref
(displays the
value 0 because only after at least 8 hours can the first reference value be
calculated).