02-2010
19
In case of emergency the
Emergency telephone number 0049 (0) 170 582 64 84
is
available
at all times
.
14
Information about Spare Parts
See enclosed list.
15
Details about Disposal and Recycling
Environment-related requirements for the recycling, re-using and disposal of operational
materials and the refrigeration aggregate according to DIN EN 378 and ROHS Guidelines
are to be strictly adhered to. The owner/operator is solely responsible.
16
Rules for the Owner/Operator
16.1 Rules referring to the refrigeration unit
The owner/operator of the cooling equipment is obliged:
•
to only allow suitably trained persons to work on the unit
•
to ensure that the operating instructions are read and observed iun case of a change of
the operating personnel (especially safety instructions)
•
to make sure the operating instructions are always at the workplace
•
to ensure that the care & maintenance instructions are followed
•
to make sure thaat the neccessary activities (e.g. maintenance) are only carried out by
suitable trained & qualified persons and groups of persons
•
to train & qualify such persons and groups of persons if it is so required
•
to ensure that the equipment is used only for the purpose it was designed and built for
The operators of refrigeration, air-conditioning & heating pump equipment are obliged by
law to carry out regular leakage inspections with certified personnel at certain regular
intervals. These persons have to present their qualifications to the satisafction of the
owner/operator. Test intervals are directly dependant on the cooling agent amount and
vary between yearly ( above 3kg i.e. 6kg in the case of Hermetic systems), half-yearly
(above 30kg) and quarter-yearly (above 300kg). Tests are to be documented in one of
the special manuals prepared for the unit. A suitable operating manual is available from
the manufacturer.
•
It is recommended to periodically inspect and list all elements in the prescribed process-
related safety program from the owner operator. Updated information is to be entered
into this documentation.
16.2 Planning for emergencies and assignment
It is recommended to include the equipment into the emergency measures & control plan in
order to minimize potential consequences.