ESTIMATING FLUE GAS FLOW RATE (ACFM)
Flue gas volumetric flow rate in SCFM (standard cubic
feet per minute) and ACFM (actual cubic feet per
minute) can be estimated by using the information in
1.8.1A. Divide the Total Input of appliances
connected to the chimney or vent by 1000. Then
multiply this result times the factor listed in the SCFM
and ACFM table. The ACFM data is required for
determining stack exit velocity and induced draft fan
requirements.
ESTIMATING STACK EXIT VELOCITY
First, determine the ACFM for the stack as described
above. Multiply the total ACFM times the Velocity
Factor from the Velocity Table in Table 1.8.1B for the
stack diameter used. The result is the Stack Exit
Velocity in feet per second.
ESTIMATING STACK EMISSIONS
Table 1.8.1C lists approximate emissions of NOx
(oxides of nitrogen) and CO (carbon monoxide). The
table lists both the concentration, in parts per million
(ppm), and the flow rate, in pounds per hour (PPH), of
each compound: Divide the total input of appliances
connected to the chimney or vent by 1,000,000. Then
multiply this result times the value listed in the table for
PPH emissions.
MANUAL REFERENCES
See Figure 1.8.1 for a graphics listing of applicable
sections of this manual for each section of the vent
system.
FIGURE 1.8.1: VENT DESIGN INSTRUCTIONS - REFERENCE
TABLE 1.8.1A: ESTIMATING FLUE GAS VOLUMETRIC FLOW RATE
Approximate Flue Gas VOLUMETRIC FLOW RATE (Per 1000 Btu/hr Input)
(Multiply factor listed times boiler input in MBH)
BOILER TYPE
SCFM Per
1000 Btu/hr INPUT
ACFM Per
1000 Btu/hr INPUT
APPROXIMATE FLUE GAS
TEMPERATURE AT FULL
INPUT
Water & 15# Steam
Boilers
Before Draft
Control
After Draft
Control
Before Draft
Control
After Draft
Control
Before Draft
Control
After Draft
Control
Atmospheric Gas
(Draft Diverter)
Atmospheric Gas
(Barometric D.R.)
0.250
0.250
0.364
0.280
0.462
0.462
0.546
0.474
480 F
480 F
350 F
430 F
150# Steam Boilers
Before Draft
Control
After Draft
Control
Before Draft
Control
After Draft
Control
Before Draft
Control
After Draft
Control
Atmospheric Gas
(Draft Diverter)
Atmospheric Gas
(Barometric D.R.)
0.250
0.250
0.364
0.280
0.486
0.486
0.602
0.517
550 F
550 F
400 F
500 F