Boiler Control Instruction & Operation Manual
Page 6
6
of
68
Specifications
Parameter Summary
USB
Parameter
Range
Security
Page
X
Boost Time
0 to 30 minutes
Basic
39
X
Central Heat ODR Max Off Point
50 to 190
°
F
Basic
39
X
Lead Lag CH ODR Max Off Point
50 to 190
°
F
Basic
39
Sequence Master Menu
Master Enable/Disable
Disable / Enabled
Supervisor
40
Base Load Common Rate
25 to 100 %
Supervisor
40
Indirect Water Heater
Boiler Piped / Primary Piped
Supervisor
40
Boiler Start Delay
0.5 to 20 minutes
Supervisor
40
DHW Two Boiler Start
Enable / Disable
Supervisor
40
Stop All Boilers
50 to 195
°
F
Basic
40
Boiler Stop Delay
0.5 to 5 minutes
Supervisor
40
Lead Rotation Time
8 to 48 hours
Basic
40
LL Response Speed
0 to 5
Supervisor
40
Slave Sequencer Menu
Slave Selection Order
First / Normal / Last
Supervisor
41
Boiler Address
1 to 8
Supervisor
41
Limits Menu
X
Stepped Modulation Start Offset
(Stepped Modulation Recycle 6) - 30
Factory
41
X
Stepped Modulation Recycle Offset
10 - (Stepped Modulation Start Offset - 6)
Factory
41
X
Preferred Stack Limit Setpoint
150
°
F to Stack Default Limit
Factory
41
X
Preferred Outlet Limit Setpoint
60
°
F to Outlet Default Limit
Factory
41
EMS Remote Demand Menu
Modulation Source
Local / 4 - 20mAdc / Modbus
Supervisor
20
CH Demand Switch
Local / Modbus
Supervisor
20
LL Demand Switch
Local / Modbus
Supervisor
20
4mA Water Temp
50 to 185
°
F
Supervisor
20
Lead Lag Setpoint Source
Local / 4 - 20mAdc / Modbus
Supervisor
20
Central Heat Setpoint Source
Local / 4 - 20mAdc / Modbus
Supervisor
20
20mA Water Temp
50 to 185
°
F
Supervisor
20
Analog Input Hysteresis
0 to 10
Supervisor
20
Analog output hysteresis
0 to 40
Supervisor
20
Analog Rate Tracking
Disable / PW M to 4 - 20mA / PWM to 0 - 10V / LL
Rate to 4 - 20mA / LL Rate to 0 - 10V
Supervisor
20
Fan Tune Menu
X
Fan speed - up ramp
0 to 12000
Supervisor
44
X
Fan slow - down ramp
0 to 12000
Supervisor
44
X
Fan gain up
1 to 100
Factory
44
X
Fan gain down
1 to 100
Factory
44
X
CH slow start enable/disable
Enable - Disable
Supervisor
44
X
DHW slow start enable/disable
Enable - Disable
Supervisor
44
X
Slow start ramp
0 to 1000 rpm
Supervisor
44
X
Slow start degrees
0
°
F to 180
Supervisor
44
NOTES
“Load Parameters” loads the current saved parameter settings off a USB Drive. This allows for easy transfer of
boiler parameters and contact information from one boiler to another.