-9-
AIR DELIVERY - POWER DRAW (WATTS)**
Unit
Operating Mode
CFM Airflow
External Static
External Static Pressure (ESP)
Size
Setting
Pressure Range*
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
036070
POWER DRAW (WATTS)**
†† Low Heat
735†
0-0.50
84
100
119
133
148
High Heat
1180
0-1.0
227
256
287
318
347
381
407
435
462
485
†† 1-1/2-Ton Cooling
525
0-0.50‡
48
63
74
86
98
†† 2-Ton A/C Cooling
700
0-0.50‡
75
90
108
121
135
2-1/2-Ton A/C Cooling
875
0-1.0‡
123
145
163
183
202
221
238
257
275
297
3-Ton A/C Cooling
1050
0-1.0‡
181
205
226
253
278
302
326
350
371
392
3-1/2-Ton A/C Cooling
1225
0-1.0
254
289
320
355
384
416
444
472
495
515
Maximum
1400
0-1.0
381
413
462
490
527
556
586
607
616
608
048090
Low Heat
985†
0-1.0
115
144
170
197
224
251
279
306
334
359
High Heat
1210
0-1.0
187
216
245
280
314
343
375
407
435
463
†† 1-1/2-Ton A/C Cooling
525
0-0.50‡
45
61
77
93
107
†† 2-Ton A/C Cooling
700
0-0.50‡
61
78
96
118
138
2-1/2-Ton A/C Cooling
875
0-1.0‡
87
110
136
159
183
207
229
254
283
304
3-Ton A/C Cooling
1050
0-1.0‡
127
159
185
214
242
271
301
329
356
384
3-1/2-Ton A/C Cooling
1225
0-1.0‡
191
223
246
283
312
349
378
412
441
469
4-Ton A/C Cooling
1400
0-1.0
267
304
342
382
424
463
495
531
558
587
Maximum
1600
0-1.0
390
434
483
526
568
608
617
623
630
625
060110***
Low Heat
1440†
0-1.0
209
250
287
334
371
411
440
485
528
566
High Heat
2005
0-1.0
499
554
601
656
707
761
810
856
898
937
†† 2-Ton A/C Cooling
700
0-0.50‡
63
81
102
120
140
†† 2-1/2-Ton A/C Cooling
875
0-0.50‡
78
106
125
148
168
†† 3-Ton A/C Cooling
1050
0-0.50‡
107
136
163
195
226
3-1/2-Ton A/C Cooling
1225
0-1.0‡
143
181
215
253
287
318
347
384
408
451
4-Ton A/C Cooling
1400
0-1.0‡
191
230
264
318
354
399
429
474
521
557
5-Ton A/C Cooling
1750
0-1.0‡
356
394
436
487
524
571
616
664
706
753
6-Ton A/C Cooling
2100
0-1.0
563
626
671
731
784
837
895
934
978 1010
Maximum
2200
0-1.0
631
692
761
814
878
922
967 1023 1059 1091
066135
Low Heat
1700†
0-1.0
321
371
430
469
509
562
608
666
706
757
High Heat
1915
0-1.0
429
476
542
601
658
730
778
832
902
944
†† 2-Ton A/C Cooling
700
0-0.50‡
61
83
107
128
149
†† 2-1/2-Ton A/C Cooling
875
0-0.50‡
76
107
134
160
187
†† 3-Ton A/C Cooling
1050
0-0.50‡
103
135
174
208
240
3-1/2-Ton A/C Cooling
1225
0-1.0‡
131
174
210
253
289
336
374
423
459
511
4-Ton A/C Cooling
1400
0-1.0‡
201
250
283
330
376
410
453
491
533
565
5-Ton A/C Cooling
1750
0-1.0‡
343
400
450
491
535
584
630
681
730
779
6-Ton A/C Cooling
2100
0-1.0
573
631
705
762
827
890
943
998 1044 1091
Maximum
2200
0-1.0
656
725
803
863
928
984 1047 1087 1126 1142
066155
Low Heat
1715†
0-1.0
310
366
402
443
486
525
580
621
668
719
High Heat
1970
0-1.0
442
493
547
604
655
720
770
826
879
932
†† 2-Ton A/C Cooling
700
0-0.50‡
60
79
105
126
147
†† 2-1/2-Ton A/C Cooling
875
0-0.50‡
73
97
128
154
178
†† 3-Ton A/C Cooling
1050
0-0.50‡
96
122
153
196
226
3-1/2-Ton A/C Cooling
1225
0-1.0‡
121
166
201
244
277
314
358
400
441
491
4-Ton A/C Cooling
1400
0-1.0‡
188
225
266
299
345
389
423
462
498
540
5-Ton A/C Cooling
1750
0-1.0‡
322
367
422
466
498
546
598
653
693
740
6-Ton A/C Cooling
2100
0-1.0
500
557
620
691
743
814
864
936
985 1027
Maximum
2200
0-1.0
592
673
746
811
885
935
994 1026 1102 1129
*
Actual external static pressure (ESP) can be determined by using the fan laws (CFM
2
proportional to ESP); such as,
a system with 1180 CFM at 0.5 ESP would operate at cooling airflow of 1050 CFM at 0.4 ESP and low-heating airflow
of 735 CFM at 0.19 ESP.
†
Low heat CFM when low-heat rise adjustment switch (SW1-3) and comfort/efficiency adjustment switch (SW1-4) on
control center are OFF.
‡
Ductwork must be sized for high-heating CFM within the operational range of ESP.
**
Wattage data provided is for the circulating blower with bottom return and does not include draft inducer, accessories,
or gas controls.
††
Operation within the blank areas of the chart is not recommended because high-heat operation will be above 1.0 ESP.
***
All airflows on 110 size furnace are 5% less on side return only installations.