background image

WARNING:

Never operate unit without a filter(s) or

with filter access door removed. A failure to follow this
warning could result in fire, personal injury, or death.

1. Downflow

Each furnace requires 2 filters which are installed in the
return-air duct. (See Fig. 4.) To remove filters for cleaning
or replacement, proceed as follows:

a. Turn off electrical supply before removing blower access

door.

b. Remove blower access door.

c. Reach up behind top plate, tilt filters toward center of

return-air plenum, remove filters. Replace filters if torn
or damaged.

d. Furnaces are equipped with permanent, washable filters.

e. Clean filters by spraying tap water through filter from

opposite direction of airflow.

f. Rinse and let dry. Oiling or coating of filters is not

recommended or required.

g. Reinstall filters.

h. Replace blower access door and turn on electrical supply

to furnace.

2. Upflow/Horizontal.

Each furnace requires 1 or 2 filters which are installed in the
blower compartment. (See Fig. 5.) To remove filters for
cleaning or replacement, proceed as follows:
a. Turn off electrical supply before removing blower and

control access doors.

b. Release filter retainer from clip at front of furnace

casing. (See Fig. 5.) For side return, clips may be used
on either or both sides of the furnace.

c. Slide filter out.

d. Clean filters by spraying tap water through filter from

opposite direction of airflow.

e. Rinse and let dry. Oiling or coating of filter is not

recommended or required.

f. Place filter in furnace.

g. Replace blower and control access doors and turn on

electrical supply to furnace.

B.

Blower Motor and Wheel

For long life, economy, and high efficiency, clean accumulated dirt
and grease from blower wheel and motor annually.

The following steps should be performed by a qualified service
technician:

The motors have prelubricated sealed bearings and require no
lubrication.

Remember to disconnect the electrical supply before removing
access doors.

Clean as follows:

1. Remove blower access door.

2. Disconnect vent pipe on downflow furnace only.

a. Remove vent pipe enclosure.

b. Disconnect vent pipe and remove short piece of pipe

from furnace.

c. Disconnect wires from auxiliary limit on blower housing

(if present).

3. Disconnect blower electrical leads from control. (See Fig. 5

and 6.) Note location of wires for reassembly.

4. Remove control and bracket assembly.

5. Remove screws holding blower assembly to blower deck

and slide blower assembly out of furnace.

6. Loosen a screw in strap holding motor capacitor to blower

housing and slide capacitor out from under strap.

Fig. 4—Downflow Filter Arrangement

A88486

RETURN-AIR

PLENUM

AIRFLOW

ACCESS DOOR

INSTALLATION

POSITION

OF FILTERS

Fig. 5—Model 330JAV Upflow

A95386

MOUNTING

SCREWS

RELIEF

BOX

MAIN

LIMIT

SWITCH

MANUAL

RESET

LIMIT

SWITCHES

CONTROL

FILTER
RETAINER

WASHABLE
FILTER

PRESSURE
SWITCHES

DRAFT
SAFEGUARD
SWITCH

—3—

Summary of Contents for 330JAV

Page 1: ...ted States follow all safety codes including the National Fuel Gas Code NFPA No 54 1996 ANSI Z223 1 1996 In Canada refer to the current edition of the National Standard of Canada CAN CGA B149 1 and 2...

Page 2: ...commercial sources may also be used to prevent ESD damage CARE AND MAINTENANCE For continuing high performance and to minimize possible equip ment failure it is essential that periodic maintenance be...

Page 3: ...ter through filter from opposite direction of airflow e Rinse and let dry Oiling or coating of filter is not recommended or required f Place filter in furnace g Replace blower and control access doors...

Page 4: ...alified service technician NOTE Deposits of soot and carbon indicate the existence of a problem which needs to be corrected Take action to correct the problem If it becomes necessary to clean heat exc...

Page 5: ...ctors leading to control 13 Reconnect vent pipe to relief box When applicable replace vent pipe enclosure 14 Replace blower door only 15 Turn power and gas to ON 16 Set thermostat and check furnace fo...

Page 6: ...connect and reconnect of red wire Fig 9 Heating and Cooling Application Wiring Diagram for Single Stage Thermostats and Single Speed Condensing Units A97443 115 V FUSED DISCONNECT SWITCH WHEN REQUIRED...

Page 7: ...condition E Troubleshooting Refer to service label See Fig 12 Page 10 contains a trouble shooting guide This guide can be a useful tool in isolating furnace operation problems Beginning with the word...

Page 8: ...itches ALS1 2 used on some horizontal and some downflow models 7 This wire must be connected to furnace sheet metal for control to prove flame 8 Factory connected when LGPS not used RED LS FRS2 RED RE...

Page 9: ...DOWNFLOW ONLY SWITCH DID NOT CLOSE OR REOPENED Check for Proper vent sizing and condensate pitch with side wall vent Low inducer voltage 115v Blower motor and capacitor Defective inducer motor Defect...

Page 10: ...eck for proper orifice size Control will attempt to light burners 4 times approximately 1 minute between attempts Code 34 Voltage is present at the gas valve for 7 sec during each ignition trial Syste...

Page 11: ...11...

Page 12: ...video based formats and materials All include video and or slides plus companion book Classroom Service Training plus hands on the products in our labs can mean increased confidence that really pays d...

Reviews: