background image

The control in this furnace is equipped with an LED status light to
aid in installation, servicing, and troubleshooting. It can be viewed
through the sight glass or window on blower access door. The
control indicates status with the LED on continuously, rapid
flashing, or a code composed of 2 digits. (The first digit is the
number of short flashes, the second is the number of longs flashes.)
Refer to service label on blower compartment door for code
explanations and useful troubleshooting suggestions. (See Fig. 12.)
It is important to note that power to furnace must not be interrupted
and furnace blower door must not be removed until the LED status
code(es) is recorded. When power to control is interrupted, status
memory is erased.

The control will store up to 5 previous codes but will not store
non-current codes longer than 48 hr. To retrieve previous codes, if
present, no thermostat inputs to control must be present and all
time delays must expire. Remove 1 of the red main limit wires 1
to 4 sec until the LED light goes out, then reconnect it. (See Fig.
5 and 6.) (Do not leave red wire disconnected for longer than 4 sec
as control will assume an overtemperature condition exists and
will respond with indoor blower operation.) This places control in
status recall mode and displays first code stored in memory.
Record code and repeat the disconnect and reconnect of red wire,

Fig. 9—Heating and Cooling Application Wiring Diagram for Single-Stage Thermostats

and Single-Speed Condensing Units

A97443

115-V FUSED

DISCONNECT

SWITCH

(WHEN REQUIRED)   

JUNCTION
BOX   

CONTROL

BOX

24-V

TERMINAL

BLOCK  

TWO-WIRE

HEATING-

ONLY   

FIVE

WIRE

   

1-STAGE THERMOSTAT TERMINALS

FIELD-SUPPLIED

FUSED DISCONNECT

CONDENSING

UNIT   

FURNACE

COM

R

W

Y

R

G

C

GND   

GND   

FIELD 24-V WIRING
FIELD 115-, 208/230-, 460-V WIRING
FACTORY 24-V WIRING
FACTORY 115-V WIRING   

208/230- OR
460-V
THREE
PHASE   

208/230-V
SINGLE
PHASE   

WHT   

BLK   

WHT   

BLK   

W/W1

W2

Y/Y2

G

NOTES: 

  

1.  Connect Y-terminal as shown for proper operation.

                2.  Some thermostats require a "C" terminal connection as shown.

3.  If any of the original wire, as supplied, must be replaced,
     use same type or equivalent wire.

Fig. 10—Heating and Cooling Application Wiring Diagram for 2-Stage Thermostats

and/or 2-Speed Condensing Units

A97444

115-V FUSED

DISCONNECT

SWITCH

(WHEN REQUIRED)   

JUNCTION
BOX   

CONTROL

BOX

24-V

TERMINAL

BLOCK  

THREE-WIRE

HEATING-

ONLY   

SEVEN

WIRE

2-STAGE THERMOSTAT TERMINALS
   

FIELD-SUPPLIED

FUSED DISCONNECT   

2-SPEED
CONDENSING
UNIT   

FURNACE

G

R

W2

Y2

G

Y1

C

GND   

GND   

FIELD 24-V WIRING
FIELD 115-, 208/230-, 460-V WIRING
FACTORY 24-V WIRING
FACTORY 115-V WIRING   

208/230- OR
460-V
THREE
PHASE   

208/230-V
SINGLE
PHASE   

Y2   

Y1   

C   

WHT   

BLK   

WHT   

BLK   

W1

R

W2

COM

W/W1

Y/Y2

NOTES: 

  

1.  Connect Y-terminal as shown for proper operation.

                2.  Some thermostats require a "C" terminal connection as shown.

3.  If any of the original wire, as supplied, must be replaced,
     use same type or equivalent wire.

—6—

Summary of Contents for 330JAV

Page 1: ...ted States follow all safety codes including the National Fuel Gas Code NFPA No 54 1996 ANSI Z223 1 1996 In Canada refer to the current edition of the National Standard of Canada CAN CGA B149 1 and 2...

Page 2: ...commercial sources may also be used to prevent ESD damage CARE AND MAINTENANCE For continuing high performance and to minimize possible equip ment failure it is essential that periodic maintenance be...

Page 3: ...ter through filter from opposite direction of airflow e Rinse and let dry Oiling or coating of filter is not recommended or required f Place filter in furnace g Replace blower and control access doors...

Page 4: ...alified service technician NOTE Deposits of soot and carbon indicate the existence of a problem which needs to be corrected Take action to correct the problem If it becomes necessary to clean heat exc...

Page 5: ...ctors leading to control 13 Reconnect vent pipe to relief box When applicable replace vent pipe enclosure 14 Replace blower door only 15 Turn power and gas to ON 16 Set thermostat and check furnace fo...

Page 6: ...connect and reconnect of red wire Fig 9 Heating and Cooling Application Wiring Diagram for Single Stage Thermostats and Single Speed Condensing Units A97443 115 V FUSED DISCONNECT SWITCH WHEN REQUIRED...

Page 7: ...condition E Troubleshooting Refer to service label See Fig 12 Page 10 contains a trouble shooting guide This guide can be a useful tool in isolating furnace operation problems Beginning with the word...

Page 8: ...itches ALS1 2 used on some horizontal and some downflow models 7 This wire must be connected to furnace sheet metal for control to prove flame 8 Factory connected when LGPS not used RED LS FRS2 RED RE...

Page 9: ...DOWNFLOW ONLY SWITCH DID NOT CLOSE OR REOPENED Check for Proper vent sizing and condensate pitch with side wall vent Low inducer voltage 115v Blower motor and capacitor Defective inducer motor Defect...

Page 10: ...eck for proper orifice size Control will attempt to light burners 4 times approximately 1 minute between attempts Code 34 Voltage is present at the gas valve for 7 sec during each ignition trial Syste...

Page 11: ...11...

Page 12: ...video based formats and materials All include video and or slides plus companion book Classroom Service Training plus hands on the products in our labs can mean increased confidence that really pays d...

Reviews: