background image

b. A lack of flue draft (chimney effect) or some other

blockage, such as soot, in secondary section of heat
exchanger.

c. Use of an oversized nozzle input.

d. Pump pressure over the values listed in Table 10.

5. The CO

2

and stack temperature instruments enable you to

obtain data required to determine thermal efficiency of
furnace.

6. An oil filter should be installed as close to burner as

possible with ALL oil burners and is essential on lower
firing rate burners. We recommend the use of a low
pressure drop oil filter such as the General Filter, Inc. model
#1A-25A or equivalent.

7. The oil pressure regulator is factory set to give oil pressure

of 135 psig for the model having 105,000 BTUH input and
135 psig for the model having 119,000 BTUH input. The
firing rate noted on nameplate may be obtained using the
nozzles and pump pressures indicated in Table 10. The
proper oil burner turbulator setting for all the firing rates is
0 (zero).

8. On a new installation, air entrapped in oil line leading from

tank to nozzle must be thoroughly purged in order to
prevent excessive after drip. The oil pump is provided with
a special fitting which allows purging of any air between
tank and oil pump. The proper procedure for performing
this operation is as follows:

a. Place a piece of clear plastic 1/4-in. diameter tubing over

purge fitting on oil pump.

b. Start oil burner, then open purge fitting and allow burner

to run until purge tube is completely free of air bubbles.

c. Tighten purge fitting. Allow oil to run to nozzle and fire

burner.

d. If purging takes longer than 15 sec and no flame has

been established, burner stops. Push reset button on front
of primary control to restart burner.

e. For detailed information on operation of primary control,

refer to instructions included with furnace.

After all the setup procedures mentioned above have been com-
pleted, the burner should be allowed to operate and an inspection
mirror should be used to observe the flame pattern at tip of nozzle.
Any irregularities such as burning to 1 side or pulsating flame
patterns should be corrected by changing nozzle.

III.

FAN ADJUSTMENT CHECK

This furnace is equipped with a variable speed motor to deliver a
constant airflow. Adjust DIP switches on the electronic board
ACCORDING TO OIL INPUT SELECTED AND A/C SIZE. (See
Tables 11A, 11B, and 11C or Tables 12A, 12B, and 12C.)

WARNING:

FIRE HAZARD AND UNIT

RELIABILITY
Failure to follow this warning could result in property
damage, personal injury or death.
When operating furnace in heating mode, static pressure
and temperature rise (supply-air temperature minus
return-air temperature) must be within those limits speci-
fied on rating label.

IV.

LIMIT CONTROL CHECK

After furnace has been in operation for at least 15 minutes, restrict
return-air supply by blocking filters or closing return registers and
allow furnace to shut down on high limit. The burner should shut
off, and main blower should continue to run.

V.

FOR YEAR-ROUND AIR CONDITIONING

This furnace is designed for use in conjunction with cooling
equipment to provide year-round air conditioning. The blower has
been sized for both heating and cooling, however, fan motor speed
may need to be changed to obtain necessary cooling airflow.

VI.

HEATING

The blower speed is factory set to deliver required airflow at
normal duct static pressure for 0.75 GAL/HR (US) INPUT for the
368RAN 105 size (See Tables 11A, 11B, and 11C) and 0.85
GAL/HR (US) INPUT for the 368RAN 120 size. (See Tables 12A,
12B, and 12C.) The blower motor may be field adjusted to deliver
required airflow for other capacity.

VII.

COOLING

The blower speed may be field adjusted to deliver required airflow
for cooling application. (See Table 13 or 14.)

TABLE 10—BURNER INPUT AND NOZZLE SIZE

FURNACE

INPUT

(BTUH)

FIRING

RATE

GAL/HR (US)*

RIELLO OIL BURNER

PUMP

PRESSURE

(PSIG)

No. 40 Series

Model

Nozzle

70,000

0.50

F3

0.40 - 70A

160

91,000

0.65

F3

0.50 - 70W

170

105,000

0.75

F3

0.65 - 70W

135

119,000

0.85

F5

0.75 - 70B

130

140,000

1.00

F5

0.85 - 70W

140

154,000

1.10

F5

1.00 - 70W

125

*For rating purposes only

TABLE 11A— 368RAN 105 SIZE DIP SWITCH

ADJUSTMENT FOR OIL HEATING MODE

SW1-HEAT

DIP SWITCH

POSITION

INPUT

USGPH

SW4-DELAY
DIP SWITCH

POSITION

INPUT

USGPH

1

2

1

2

OFF

OFF

0.75

OFF

OFF

0.75

ON

OFF

0.65

ON

OFF

0.65

OFF

ON

0.5

OFF

ON

0.5

ON

ON

N/A

ON

ON

N/A

TABLE 11B— 368RAN 105 SIZE DIP SWITCH

ADJUSTMENT FOR HEAT PUMP AND COOLING MODE

SW2-COOL

DIP SWITCH POSITION

A/C SIZE

(TONS)

1

2

OFF

OFF

3.0

ON

OFF

2.5

OFF

ON

2.0

ON

ON

1.5

TABLE 11C— 368RAN 105 SIZE DIP SWITCH

CFM ADJUSTMENTS IN ALL MODES

SW2-ADJUST

DIP SWITCH POSITION

HEATING CFM %

INCREASE OR

DECREASE

COOLING CFM %

INCREASE OR

DECREASE

1

2

OFF

OFF

0

0

ON

OFF

+ 13

+ 10

OFF

ON

- 15

- 10

ON

ON

N/A

0

—10—

Summary of Contents for 368RAN Series A

Page 1: ...INITY OF THIS OR ANY OTHER APPLIANCE DO NOT ATTEMPT TO START THE BURNER WHEN EXCESS OIL HAS ACCUMULATED WHEN THE FURNACE IS FULL OF VAPOR OR WHEN THE COMBUSTION CHAMBER IS VERY HOT WARNING CARBON MONO...

Page 2: ...esult in severe personal injury or death WARNING signifies a hazard which could result in personal injury or death CAUTION is used to identify unsafe practices which may result in minor personal injur...

Page 3: ...tion debris from all HVAC system components after construction is completed This furnace is approved for reduced clearances to combustible construction therefore it may be installed in a closet or sim...

Page 4: ...n and dilution of flue gases This determi nation must be made on an individual installation basis and must take into consideration the overall volume of unconfined space the number of windows and vent...

Page 5: ...and Air Conditioning Systems or Canadian equivalent The supply duct work should be attached to flanged front opening provided at discharge end of furnace The return air duct work should be attached to...

Page 6: ...tion length of 3 3 4 in The oil pump is set to operate on a single line system To operate on a two line system the by pass plug must be installed F Oil Connections CAUTION UNIT DAMAGE HAZARD Failure t...

Page 7: ...ply line is open 6 RESET BUTTON on primary control is pushed down 7 Flame observation door is closed 8 Thermostat is set for heating mode and set above room temperature If all of the above items have...

Page 8: ...Fig 3 Wiring Diagram A04182 8...

Page 9: ...Wiring with 1 Speed Air Conditioner Fig 5 24 VAC Oil Furnace Wiring with 2 Speed Air Conditioner A04184 A04185 Fig 6 24 VAC Oil Furnace Wiring with 1 Speed Heat Pump A04186 Fig 7 24 VAC Oil Furnace W...

Page 10: ...ic board ACCORDING TO OIL INPUT SELECTED AND A C SIZE See Tables 11A 11B and 11C or Tables 12A 12B and 12C WARNING FIRE HAZARD AND UNIT RELIABILITY Failure to follow this warning could result in prope...

Page 11: ...R1 JW6 R3 D20 D1 D3 D04 D02 D13 R13 JW2 JW3 JW7 LED7 GRN R14 R12 D17 D18 D19 D21 D15 D16 LED4 LED3 LED5 LED7 LED8 LED1 GRN GRN GRN GRN GRN GRN P3 Y Y Y2 G DH O W R C HSC 1 1168 83 1 NOTES 1 The Red LE...

Page 12: ...TURNED OFF IF BURNER IS SHUT DOWN FOR AN EXTENDED PERIOD OF TIME II OIL BURNER For optimum performance oil burner nozzle should be replaced once a year Contact your service technician if you are unsur...

Page 13: ...de with no 24 VAC input to DH the CFM STD is reduced by 15 COOLING MODE OR HEAT PUMP HEATING MODE 2 SPEED LOW 24 VAC INPUT R TO G Y1 AND O FOR COOLING SW2 COOL Dip Switch Position A C Size TON CFM STD...

Page 14: ...COOLING SW2 COOL Dip Switch Position A C Size TON CFM STD with SW3 ADJ Dip Switch A Position CFM HIGH with SW3 ADJ Dip Switch B Position CFM LOW with SW3 ADJ Dip Switch C Position A 1 OFF 2 OFF 5 0 9...

Page 15: ...oduct theory and skills programs is available using popular video based formats and materials All include video and or slides plus companion book Classroom ServiceTraining plus hands on the products i...

Page 16: ...2004 Bryant Heating Cooling Systems 7310 W Morris St Indianapolis IN 46231 16 Printed in U S A ii368r361 Catalog No 5336 800...

Reviews: