background image

13

Accessory Installation

1. General

When installing optional accessories to this appliance,

follow manufacturer’s Installation Instructions included
with accessory. Other than wiring for thermostat, wire with

a minimum of type ’T’ insulation (63

_

F/35

_

C rise) must be

used for accessories.

2. Auxiliary Terminals

The HUM 120 VAC terminals on the electronic control
board are tied directly to the #8 pin of the 9 pin connector

and provide a 120 VAC signal whenever the burner is
energized. (See Fig. 14.)

Supplementary 120 VAC and

neutral terminals can be used for accessory wiring. See
Electronic Air Cleaner and Humidifier sections for further
information.

3. Electronic Air Cleaner Connections

When using an electronic air cleaner with variable--speed

oil--fired furnaces, use an Airflow Sensor kit. As the air
cleaner is connected to constant 120 VAC power, the
airflow sensor turns on the electronic air cleaner when the

furnace blower is operating.

4. Humidifier/Humidistat Connections

To ensure humidifier will operate properly, use HUM
output of Humidistat Control to control humidifier

operation. A 24--VAC signal can be connected from the W
and C on terminal block connections on the electronic board
or a 120 VAC signal from the “HUM 120 VAC” terminal

when primary heating source is used. (See Fig. 15--18.)

5. Dehumidify

Capability

with

Standard

Humidistat

Connection
Latent capabilities for systems using the variable--speed
oil--fired furnaces are better than average systems. If

increased latent capacity is an application requirement, the
field wiring terminal block provides connection terminals

for use of a standard humidistat.
The variable--speed oil--fired unit will detect the humidistat
contacts opening on increasing humidity and reduce its

airflow to approximately 85% of nominal cooling mode
airflow. This reduction will increase the system latent

capacity until the humidity falls to a level which causes the
humidistat contacts to close. When the contacts close, the

airflow will return to 100% of the selected cooling airflow.
To activate this mode, remove the Jumper between DH and
R of the electronic board and wire in a standard humidistat.

Filters

FIRE, CARBON MONOXIDE POISONING HAZARD

Failure to follow this warning could result in personal

injury, death and/or property damage.
Never operate unit without a filter or with filter access door

removed.

!

WARNING

An internal filter rack is provided as standard equipment with
furnace and is located in blower compartment. A sufficient

clearance should be provided for air filter access. Refer to Table 4

for filter rack flange dimensions for return air duct.

Table 4 – Filter Size and Quantity

UNIT

SIZE

AIR FILTER SIZE

IN (mm)

FLANGE OPENING SIZE

IN (mm)

036105

16 x 24 x 1

(406 x 609 x 25)

or

16 x 25 x 1

(406 x 635 x 25)

15 x 23

(381 x 584)

060120

20 x 30 x 1

(508 x 762 x 25)

19 x 29

(483 x 737)

Step 11 — Horizontal or Downflow Installation

For horizontal installation, determine which “side” will become the
“top” when the unit is laid down. Remove the flue pipe clearance

knock--out from the top of that side panel. Install the flue elbow so

that it exits the cabinet of the furnace through that opening.
For counterflow installation, the flue pipe must exit the cabinet

through 1 of the side panel openings (as above), then extended up
the side of the furnace. Insure that adequate clearances to

combustibles are observed. Downflow Conversion/Vent Guard Kit
MUST be used.
Remove burner by loosening mounting nuts and turn oil burner

slightly counter--clockwise to unlock the keyhole burner flange.
Prevent putting undue strain on burner wiring. (It may be

necessary to disconnect burner wiring in some cases.)
To reinstall burner, insert on the four burner studs on keyhole

burner flange and turn it clockwise to lock it and tighten nuts.

IMPORTANT

: Burner must always be installed in the upright

position with ignition control on top.

START--UP, ADJUSTMENT, AND SAFETY

CHECKOUT

Step 1 — Operational Checkout

Installation of furnace is now complete. Perform the following

checkout procedures.

1. Correct nozzle size has been selected for desired input rate.
2. Electrical wiring is completed according to Fig. 14.
3. Blower wheel support is removed.
4. Blower access door is secured in place.
5. Valve on oil supply line is open.
6. RESET BUTTON on primary control is pushed down.
7. Flame observation door is closed.
8. Thermostat is set for heating mode and set above room

temperature.

If all of the above items have been performed, set main electrical

switch to ON position and burner should start. When burner starts,
proceed to Combustion Check section.

Step 2 — Sequence of Operation

Using schematic diagram in Fig. 14 follow the sequence of

operation through the different modes. Read and follow diagram
very carefully.

NOTE

: The GE ICM2+ blower motor speeds are infinitely--

variable control--airflow rate (CFM). The ICM2+ motor ramps to
speed at a controlled rate to reduce start--up noise perception. The
ICM2+ motor ramps down slowly to a stop in the same time as
ramp--up time. ICM2+ ramp--up and ramp--down times are additive
to blower--on and --off delays, respectively. The ICM2+ is 115--v
energized whenever power is available at furnace control, but
operates only when 24--v motor control input(s) are on.

374RAN

Summary of Contents for 374RAN

Page 1: ...Check 15 Step 4 Fan Adjustment Check 16 Step 5 Limit Control Check 17 Step 6 For Year Round Air Conditioning 17 CARE AND MAINTENANCE 17 Step 1 General 17 Step 2 Oil Burner 17 Step 3 Heat Exchanger an...

Page 2: ...g gasoline Never burn garbage or paper in the heating system and never leave rags paper or any flammable items around the unit WARNING All local and national code requirements governing installation o...

Page 3: ...the structure The furnace is controlled by a thermostat It may not be hot wired to provide heat continuously to the structure without thermostatic control Clean outside air is provided for combustion...

Page 4: ...st be avoided Such contamination would include the following ammonia chlorine hydrogen sulfide halogenated hydrocarbons carbon tetrachloride cleaning solvents hydrochloric acid water softening chemica...

Page 5: ...side of Structure If outside air is supplied to a confined space then the 2 openings must be equal and located as above 1 If combustion air is taken through a permanent opening directly communicating...

Page 6: ...each end of attic ends 1 ft 0 3m above floor Water heater A06463 Fig 4 Combustion Air Taken From Outdoors Through Vertical Ducts without louvers in foundation The Outlet air duct and Inlet air duct m...

Page 7: ...ter Outlet air duct Inlet air duct A06465 Fig 6 Combustion Air Taken From Outdoors Through Horizontal Ducts The top opening and the bottom opening must each be 8 in x 18 in when a 105 size furnace is...

Page 8: ...obstructions Any blockage must be cleared before installing furnace 3 Cleaning chimney or vent if previously used for venting a solid fuel burning appliance or fireplace 4 Confirming that all unused...

Page 9: ...installed in the flue between 2 in and 12 in from the furnace outlet and between the furnace outlet and draft regulator See Fig 9 Diagram B Riello A06403 Fig 8 Wiring Diagram for Riello Burner FIRE C...

Page 10: ...e and cleaning pipes The BVSO must be installed between 2 in and 12 in from the furnace outlet Limit Switches A06614 Fig 9 Blocked Vent Shut Off Device Wiring Installation shown Upflow with vertical e...

Page 11: ...n personal injury death or property damage Do not connect aluminum wire between disconnect switch and furnace Use only copper wire WARNING The control system depends on correct polarity of power suppl...

Page 12: ...12 BLOCKED VENT SHUT A06627 Fig 14 Wiring Diagram 374RAN...

Page 13: ...provided for air filter access Refer to Table 4 for filter rack flange dimensions for return air duct Table 4 Filter Size and Quantity UNIT SIZE AIR FILTER SIZE IN mm FLANGE OPENING SIZE IN mm 036105...

Page 14: ...ce Wiring with 1 Speed Air Conditioner A04184 Fig 16 24 VAC Oil Furnace Wiring with 2 Speed Air Conditioner A04185 Fig 17 24 VAC Oil Furnace with 1 Speed Heat Pump A04186 Fig 18 24 VAC Oil Furnace Wir...

Page 15: ...the BLWM keeps continuous blower speed until the end of Short run delay period After which the BLWM operates at the appropriate low cooling airflow When the thermostat is satisfied the BLWM switches t...

Page 16: ...ncluded with damper The draft regulator should be adjusted after furnace has been firing for at least 5 min and set between 0 025 and 0 035 in wc See Table 5 Table 5 Furnace Draft Conditions in wc FUR...

Page 17: ...ion for at least 15 minutes restrict return air supply by blocking filters or closing return registers and allow furnace to shut down on high limit The burner should shut off and main blower should co...

Page 18: ...required If cleaning is necessary the following steps should be performed BURN HAZARD Failure to follow this caution may result in personal injury If furnace has been in operation some surfaces may b...

Page 19: ...D13 R13 JW2 JW3 JW7 LED7 GRN R14 R12 D17 D18 D19 D21 D15 D16 LED4 LED3 LED5 LED7 LED8 LED1 GRN GRN GRN GRN GRN GRN P3 Y Y Y2 G DH O W R C HSC 1 1168 83 1 NOTES 1 The Red LED to the right of P 1 will i...

Page 20: ...SW2 COOL DIP SWITCH POSITION A C SIZE TON AIRFLOW CFM EXTERNAL STATIC PRESSURE IN WC 0 2 0 5 0 7 0 9 A 1 OFF 2 OFF 3 0 918 973 973 827 A 1 OFF 2 OFF 1010 1070 1070 910 A 1 OFF 2 OFF 826 876 876 744 B...

Page 21: ...OLING SW2 COOL DIP SWITCH POSITION A C SIZE TON AIRFLOW CFM EXTERNAL STATIC PRESSURE IN WC 0 2 0 5 0 7 0 9 A 1 OFF 2 OFF 5 0 1738 1738 1738 1725 A 1 OFF 2 OFF 1912 1912 1912 1898 A 1 OFF 2 OFF 1564 15...

Page 22: ...nge at any time specifications or designs without notice and without incurring obligations E2009 Bryant Heating Cooling Systems 7310 W Morris St Indianapolis IN 46231 Printed in U S A Edition Date 05...

Reviews: