background image

16

1. On a new installation, air entrapped in oil line leading from

tank to nozzle must be thoroughly purged in order to

prevent excessive after drip. The oil pump is provided with
a special fitting which allows purging of any air between
tank and oil pump. The proper procedure for performing

this operation is as follows:

a. Place a piece of clear plastic 1/4--in. (6 mm) diameter

tubing over purge fitting on oil pump.

b. Start oil burner, then open purge fitting and allow burn-

er to run until purge tube is completely free of air

bubbles.

c. Tighten purge fitting. Allow oil to run to nozzle and

fire burner.

d. If purging takes longer than 15 sec. and no flame has

been established, burner stops. Push reset button on

front of primary control to restart burner.

e. For detailed information on operation of primary con-

trol, refer to burner instructions included with furnace.

2. The oil pressure regulator is factory set to give oil pressure

of 135 psig for the model having 105,000 BTUH input and
130 psig for the model having 119,000 BTUH input. The
firing rate noted on nameplate may be obtained using the

nozzles and pump pressures indicated in Table 6. The prop-
er oil burner turbulator setting for all the firing rates is 0

(zero).

3. A test kit to measure smoke, stack draft, over--fire draft,

CO2, oil--pump pressure, and stack temperatures MUST be

used in order to obtain proper air band setting.

4. The proper smoke number has been established by

engineering tests to be between 0 and 1. This degree of
smoke emission is commonly referred to as a “trace” of

smoke. It is recommended to use a Bacharach true--spot
smoke test set or equivalent.

a. Pierce a test hole in the flue pipe, approximately 18 in

(457 mm) from the furnace breech.

b. Insert the smoke test probe into the hole. For installation

using sidewall venting, use the orifice provided on the
breech plate.

c. From a cold start, let the unit operate for 5 minutes.

d. Adjust the burner air setting to achieve between 0 and 1

on the Bacharach Scale(or a trace);

e. Take a CO2 sample at the same test location where the

#1 smoke reading was taken and make note of it.
Example: 13.8% of CO2 or 2.5% of O2.

f. Adjust the burner air setting to obtain a: -- CO2 reading

1.5% lower or -- a O2 reading 2.0% higher than the

reading associated with the #1 smoke.
Example: 12.3% of CO2 or 4.5% of O2;

g. This method of adjusting the burner will result in clean

combustion (Smoke reading from the Bacharach scale
between 0 and a trace) and ensure the proper

functioning of the system.

5. In order to ensure proper draft through furnace, a barometric

draft regulator (supplied with furnace) must be installed.

In order for this device to function properly, barometric damper

must be mounted with hinge pins horizontal and face of damper
vertical. (See instructions included with damper.) The draft

regulator should be adjusted after furnace has been firing for at
least 5 min., and set between --0.025 and --0.035 in. wc. (See Table

5.)

Table 5 – Furnace Draft Conditions (in wc)

FURNACE

INPUT

(BTUH)

FLUE DRAFT

MINIMUM

OVER---FIRE DRAFT

MAXIMUM

TOTAL

RESTRICTION

THROUGH HEAT

EXCHANGER

70,000

---0.025

0.010

0.020 to 0.035

91,000

---0.025

0.020

0.030 to 0.045

105,000

---0.025

0.025

0.035 to 0.050

119,000

---0.025

0.025

0.035 to 0.050

140,000

---0.025

0.025

0.035 to 0.050

154,000

---0.025

0.025

0.035 to 0.050

6. The over--fire draft, which is taken through observation

door (located in center line above burner in front panel of
furnace), is a measurement necessary to determine if there is

a blockage between oil burner and flue outlet.
There should be a total pressure drop of between 0.020 and

0.05 in. wc. through furnace as shown in Table 5. The over--
fire draft must be set within the range shown in Table 5.
A reading outside the range shown in Table 5 (for example

+0.1 in. wc.) would indicate that furnace is in an extremely
high--pressure condition in primary section. This condition

may be caused by any of the following problems:

a. Excessive combustion air due to air band being too

wide open.

b. A lack of flue draft (chimney effect) or some other

blockage, such as soot, in secondary section of heat

exchanger.

c. Use of an oversized nozzle input.

d. Pump pressure over the values listed in Table 6.

7. After having adjusted the burner combustion, insert a ther-

mometer into the test hole in the breech pipe. The vent tem-

perature should be between 400 and 535

_

F (204 and 302

_

C). If not, check for improper air temperature rise, pump

pressure, nozzle size or a badly soiled heat exchanger.

Table 6 – Burner Input and Nozzle Size

FURNACE

INPUT

(BTUH)

FIRING RATE

GAL/HR (US)*

RIELLO OIL BURNER

PUMP

PRESSURE

(PSIG)

NO. 40

SERIES
MODEL

DELAVAN

NOZZLE

70,000

0.50

F3

0.40 -- 70A

160

91,000

0.65

F3

0.50 -- 70W

170

105,000

0.75

F3

0.65 -- 70W

135

119,000

0.85

F5

0.75 -- 70B

130

140,000

1.00

F5

0.85 -- 70W

140

154,000

1.10

F5

1.00 -- 70W

125

* For rating purposes only.

Additional information on the operation and adjustment of burner
can be found in the burner manual, included with the furnace.

After all the setup procedures mentioned above have been
completed, the burner should be allowed to operate and an

inspection mirror should be used to observe the flame pattern at tip

of nozzle. Any irregularities such as burning to 1 side or pulsating
flame patterns should be corrected by changing nozzle.

Step 4 — Fan Adjustment Check

This furnace is equipped with a variable--speed motor. The blower

is factory set to deliver the required airflow for 0.75GAL/HR(US)
INPUT and 3.0 tons air conditioning for the 374RAN105 (See

Tables 7, 8, and 9 and Fig. 19.). The blower is factory set to deliver
the required airflow for 0.85GAL/HR (US) INPUT and 5 tons air

conditioning for the 374RAN120. (See Tables 10, 11 and 12 and
Fig. 19.) The blower is field adjustable to deliver the required

airflow for other capacities.

374RAN

Summary of Contents for 374RAN

Page 1: ...Check 15 Step 4 Fan Adjustment Check 16 Step 5 Limit Control Check 17 Step 6 For Year Round Air Conditioning 17 CARE AND MAINTENANCE 17 Step 1 General 17 Step 2 Oil Burner 17 Step 3 Heat Exchanger an...

Page 2: ...g gasoline Never burn garbage or paper in the heating system and never leave rags paper or any flammable items around the unit WARNING All local and national code requirements governing installation o...

Page 3: ...the structure The furnace is controlled by a thermostat It may not be hot wired to provide heat continuously to the structure without thermostatic control Clean outside air is provided for combustion...

Page 4: ...st be avoided Such contamination would include the following ammonia chlorine hydrogen sulfide halogenated hydrocarbons carbon tetrachloride cleaning solvents hydrochloric acid water softening chemica...

Page 5: ...side of Structure If outside air is supplied to a confined space then the 2 openings must be equal and located as above 1 If combustion air is taken through a permanent opening directly communicating...

Page 6: ...each end of attic ends 1 ft 0 3m above floor Water heater A06463 Fig 4 Combustion Air Taken From Outdoors Through Vertical Ducts without louvers in foundation The Outlet air duct and Inlet air duct m...

Page 7: ...ter Outlet air duct Inlet air duct A06465 Fig 6 Combustion Air Taken From Outdoors Through Horizontal Ducts The top opening and the bottom opening must each be 8 in x 18 in when a 105 size furnace is...

Page 8: ...obstructions Any blockage must be cleared before installing furnace 3 Cleaning chimney or vent if previously used for venting a solid fuel burning appliance or fireplace 4 Confirming that all unused...

Page 9: ...installed in the flue between 2 in and 12 in from the furnace outlet and between the furnace outlet and draft regulator See Fig 9 Diagram B Riello A06403 Fig 8 Wiring Diagram for Riello Burner FIRE C...

Page 10: ...e and cleaning pipes The BVSO must be installed between 2 in and 12 in from the furnace outlet Limit Switches A06614 Fig 9 Blocked Vent Shut Off Device Wiring Installation shown Upflow with vertical e...

Page 11: ...n personal injury death or property damage Do not connect aluminum wire between disconnect switch and furnace Use only copper wire WARNING The control system depends on correct polarity of power suppl...

Page 12: ...12 BLOCKED VENT SHUT A06627 Fig 14 Wiring Diagram 374RAN...

Page 13: ...provided for air filter access Refer to Table 4 for filter rack flange dimensions for return air duct Table 4 Filter Size and Quantity UNIT SIZE AIR FILTER SIZE IN mm FLANGE OPENING SIZE IN mm 036105...

Page 14: ...ce Wiring with 1 Speed Air Conditioner A04184 Fig 16 24 VAC Oil Furnace Wiring with 2 Speed Air Conditioner A04185 Fig 17 24 VAC Oil Furnace with 1 Speed Heat Pump A04186 Fig 18 24 VAC Oil Furnace Wir...

Page 15: ...the BLWM keeps continuous blower speed until the end of Short run delay period After which the BLWM operates at the appropriate low cooling airflow When the thermostat is satisfied the BLWM switches t...

Page 16: ...ncluded with damper The draft regulator should be adjusted after furnace has been firing for at least 5 min and set between 0 025 and 0 035 in wc See Table 5 Table 5 Furnace Draft Conditions in wc FUR...

Page 17: ...ion for at least 15 minutes restrict return air supply by blocking filters or closing return registers and allow furnace to shut down on high limit The burner should shut off and main blower should co...

Page 18: ...required If cleaning is necessary the following steps should be performed BURN HAZARD Failure to follow this caution may result in personal injury If furnace has been in operation some surfaces may b...

Page 19: ...D13 R13 JW2 JW3 JW7 LED7 GRN R14 R12 D17 D18 D19 D21 D15 D16 LED4 LED3 LED5 LED7 LED8 LED1 GRN GRN GRN GRN GRN GRN P3 Y Y Y2 G DH O W R C HSC 1 1168 83 1 NOTES 1 The Red LED to the right of P 1 will i...

Page 20: ...SW2 COOL DIP SWITCH POSITION A C SIZE TON AIRFLOW CFM EXTERNAL STATIC PRESSURE IN WC 0 2 0 5 0 7 0 9 A 1 OFF 2 OFF 3 0 918 973 973 827 A 1 OFF 2 OFF 1010 1070 1070 910 A 1 OFF 2 OFF 826 876 876 744 B...

Page 21: ...OLING SW2 COOL DIP SWITCH POSITION A C SIZE TON AIRFLOW CFM EXTERNAL STATIC PRESSURE IN WC 0 2 0 5 0 7 0 9 A 1 OFF 2 OFF 5 0 1738 1738 1738 1725 A 1 OFF 2 OFF 1912 1912 1912 1898 A 1 OFF 2 OFF 1564 15...

Page 22: ...nge at any time specifications or designs without notice and without incurring obligations E2009 Bryant Heating Cooling Systems 7310 W Morris St Indianapolis IN 46231 Printed in U S A Edition Date 05...

Reviews: