background image

3

MAX 80  F / 27  C

MIN 55  F / 13  C

A06622

Fig. 3 -- Return Air Temperature

INTRODUCTION

The model 374RAN Furnace is available in two sizes. Each size
unit is capable of 3 heat/airflow combinations by a simple nozzle

change. Unit 036105 covers inputs of 70,000, 91,000, and 105,000

Btu, and unit 060120 covers inputs of 119,000, 140,000, and
154,000 Btuh.
This furnace is a multipoise unit. It may be installed in the upflow,
downflow, or horizontal configuration.

This furnace is

not

approved for installation in mobile homes, recreational vehicles, or

outdoors.
The furnace is shipped in the upflow configuration, complete with

burner and controls. It requires a line voltage (115 vac) connection
to control box, a thermostat hook--up as shown on wiring diagram,

oil line connection(s), adequate duct work, and connection to a
properly sized vent.
The air handling capacity of this furnace is designed for cooling

airflow. Refer to Table 13 for expected airflows at various external
duct static pressures.

LOCATION

Step 1 — General

ELECTRICAL SHOCK OR UNIT DAMAGE HAZARD

Failure to follow this warning could result in personal injury,

death and/or property damage.
This furnace is not watertight and is not designed for outdoor

installation. This furnace shall be installed in such a manner as

to protect electrical components from water.

Outdoor

installation would lead to a hazardous electrical condition and

to premature furnace damage.

!

WARNING

FIRE, EXPLOSION HAZARD

Failure to follow this warning could result in personal injury,

death and/or property damage.
For attic installation, it is important to keep insulation 12 in.

(305 mm) or more away from any furnace openings. Some

types of insulating materials may be combustibles.

!

WARNING

PERSONAL INJURY AND UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment damage

or improper operation.
This oil furnace may be used for construction heat provided

that:
--The furnace is permanently installed with all electrical

wiring, piping, venting and ducting installed according to

these installation instructions. A return air duct is provided,

sealed to the furnace casing, and terminated outside the space

containing the furnace. This prevents a negative pressure

condition as created by the circulating air blower, causing a

flame roll--out and/or drawing combustion products into the

structure.
--The furnace is controlled by a thermostat. It may not be “hot

wired” to provide heat continuously to the structure without

thermostatic control.
--Clean outside air is provided for combustion. This is to

minimize the corrosive effects of adhesives, sealers and other

construction materials. It also prevents the entrainment of

drywall dust into combustion air, which can cause fouling and

plugging of furnace components.
--The temperature of the return air to the furnace is maintained

between 55

_

F (13

_

C) and 80

_

F (27

_

C) with no evening

setback or shutdown. The use of the furnace while the

structure is under construction is deemed to be intermittent

operation per our installation instructions.
--The air temperature rise is within the rated rise range on the

furnace rating plate, and the firing rate has been set to the

nameplate value.
--The filters used to clean the circulating air during the

construction process must be either changed or thoroughly

cleaned prior to occupancy.
--The furnace, ductwork and filters are cleaned, as necessary, to

remove drywall dust and construction debris from all HVAC

system components after construction is completed.
--After construction is complete, verify furnace operating

conditions including ignition, input rate, temperature rise, and

venting, according to the manufacturer’s instructions.

CAUTION

!

This furnace is approved for reduced clearances to combustible

construction, therefore, it may be installed in a closet or similar

enclosure. Since this unit may be installed in an upflow, downflow,
or horizontal position, it may be located in a basement or on the

same level as area to be heated. In any case, unit should always be
installed level.
In a basement, or when installed on floor (as in a crawl space), it is

recommended that unit be installed on a concrete pad that is 1 in.
(25 mm) to 2 in. (51 mm) thick.
When installed in downflow position, furnace must not be installed
on combustible flooring unless approved subbase is used. Also,

since flue pipe is in a downflow position, Downflow
Conversion/Vent Guard Kit

MUST

be used.

When installed in a horizontal position, furnace may be suspended

by using an angle iron frame, as long as total weight of both
furnace and frame are allowed for in support calculations. (Other

methods of suspending are acceptable.) When installed in the
horizontal position, this furnace must not be installed on

combustible flooring unless the approved horizontal subbase is

used.
The required minimum clearances for furnace are specified in Table

1.

374RAN

Summary of Contents for 374RAN

Page 1: ...Check 15 Step 4 Fan Adjustment Check 16 Step 5 Limit Control Check 17 Step 6 For Year Round Air Conditioning 17 CARE AND MAINTENANCE 17 Step 1 General 17 Step 2 Oil Burner 17 Step 3 Heat Exchanger an...

Page 2: ...g gasoline Never burn garbage or paper in the heating system and never leave rags paper or any flammable items around the unit WARNING All local and national code requirements governing installation o...

Page 3: ...the structure The furnace is controlled by a thermostat It may not be hot wired to provide heat continuously to the structure without thermostatic control Clean outside air is provided for combustion...

Page 4: ...st be avoided Such contamination would include the following ammonia chlorine hydrogen sulfide halogenated hydrocarbons carbon tetrachloride cleaning solvents hydrochloric acid water softening chemica...

Page 5: ...side of Structure If outside air is supplied to a confined space then the 2 openings must be equal and located as above 1 If combustion air is taken through a permanent opening directly communicating...

Page 6: ...each end of attic ends 1 ft 0 3m above floor Water heater A06463 Fig 4 Combustion Air Taken From Outdoors Through Vertical Ducts without louvers in foundation The Outlet air duct and Inlet air duct m...

Page 7: ...ter Outlet air duct Inlet air duct A06465 Fig 6 Combustion Air Taken From Outdoors Through Horizontal Ducts The top opening and the bottom opening must each be 8 in x 18 in when a 105 size furnace is...

Page 8: ...obstructions Any blockage must be cleared before installing furnace 3 Cleaning chimney or vent if previously used for venting a solid fuel burning appliance or fireplace 4 Confirming that all unused...

Page 9: ...installed in the flue between 2 in and 12 in from the furnace outlet and between the furnace outlet and draft regulator See Fig 9 Diagram B Riello A06403 Fig 8 Wiring Diagram for Riello Burner FIRE C...

Page 10: ...e and cleaning pipes The BVSO must be installed between 2 in and 12 in from the furnace outlet Limit Switches A06614 Fig 9 Blocked Vent Shut Off Device Wiring Installation shown Upflow with vertical e...

Page 11: ...n personal injury death or property damage Do not connect aluminum wire between disconnect switch and furnace Use only copper wire WARNING The control system depends on correct polarity of power suppl...

Page 12: ...12 BLOCKED VENT SHUT A06627 Fig 14 Wiring Diagram 374RAN...

Page 13: ...provided for air filter access Refer to Table 4 for filter rack flange dimensions for return air duct Table 4 Filter Size and Quantity UNIT SIZE AIR FILTER SIZE IN mm FLANGE OPENING SIZE IN mm 036105...

Page 14: ...ce Wiring with 1 Speed Air Conditioner A04184 Fig 16 24 VAC Oil Furnace Wiring with 2 Speed Air Conditioner A04185 Fig 17 24 VAC Oil Furnace with 1 Speed Heat Pump A04186 Fig 18 24 VAC Oil Furnace Wir...

Page 15: ...the BLWM keeps continuous blower speed until the end of Short run delay period After which the BLWM operates at the appropriate low cooling airflow When the thermostat is satisfied the BLWM switches t...

Page 16: ...ncluded with damper The draft regulator should be adjusted after furnace has been firing for at least 5 min and set between 0 025 and 0 035 in wc See Table 5 Table 5 Furnace Draft Conditions in wc FUR...

Page 17: ...ion for at least 15 minutes restrict return air supply by blocking filters or closing return registers and allow furnace to shut down on high limit The burner should shut off and main blower should co...

Page 18: ...required If cleaning is necessary the following steps should be performed BURN HAZARD Failure to follow this caution may result in personal injury If furnace has been in operation some surfaces may b...

Page 19: ...D13 R13 JW2 JW3 JW7 LED7 GRN R14 R12 D17 D18 D19 D21 D15 D16 LED4 LED3 LED5 LED7 LED8 LED1 GRN GRN GRN GRN GRN GRN P3 Y Y Y2 G DH O W R C HSC 1 1168 83 1 NOTES 1 The Red LED to the right of P 1 will i...

Page 20: ...SW2 COOL DIP SWITCH POSITION A C SIZE TON AIRFLOW CFM EXTERNAL STATIC PRESSURE IN WC 0 2 0 5 0 7 0 9 A 1 OFF 2 OFF 3 0 918 973 973 827 A 1 OFF 2 OFF 1010 1070 1070 910 A 1 OFF 2 OFF 826 876 876 744 B...

Page 21: ...OLING SW2 COOL DIP SWITCH POSITION A C SIZE TON AIRFLOW CFM EXTERNAL STATIC PRESSURE IN WC 0 2 0 5 0 7 0 9 A 1 OFF 2 OFF 5 0 1738 1738 1738 1725 A 1 OFF 2 OFF 1912 1912 1912 1898 A 1 OFF 2 OFF 1564 15...

Page 22: ...nge at any time specifications or designs without notice and without incurring obligations E2009 Bryant Heating Cooling Systems 7310 W Morris St Indianapolis IN 46231 Printed in U S A Edition Date 05...

Reviews: