background image

9

Step 6 — Oil Burner

This furnace is supplied with a high--pressure atomizing retention

head--type burner (for use with grade 1 or 2 Fuel Oil). The
mounting flange is fixed to burner air tube and no adjustment is

required for insertion length. The oil pump is set to operate on a
single line system. To operate on a two--line system the by--pass

plug must be installed.

Step 7 — Oil Connections

Complete instructions for installing fuel oil piping can be found in
oil burner Installation Instructions included with furnace.
Oil line entry holes are provided in side panels. Two holes are
provided in each location so that a 2--pipe system may be used if

desired.
An oil filter should be installed as close to burner as possible with
ALL oil burners and is essential on lower firing rate burners. We

recommend the use of a low--pressure--drop oil filter such as the
General Filter, Inc. model #1A--25A or equivalent.

Step 8 — Barometric Draft Control

The barometric draft control shipped with furnace MUST be used

with furnace to ensure proper operation. Instructions for installing
control are packed with control.

Step 9 — Blocked Vent Shut--Off (BVSO) For Chimney

Venting

All oil furnaces installed in Canada must have a Blocked Vent

Shut--Off.
Refer to Fig. 8--13 and the installation instructions supplied with

the Blocked Vent Shut--Off for installation and wiring procedures.
The Blocked Vent Shut--Off must be installed in the flue between 2
in and 12 in from the furnace outlet and between the furnace outlet

and draft regulator. (See Fig. 9.)

Diagram B 

Riello

 

A06403

Fig. 8 -- Wiring Diagram for Riello Burner

FIRE, CARBON MONOXIDE POISONING HAZARD

Failure to follow this warning could result in personal injury

or death.
Do not dent or scratch the surface of the thermal switch. The

thermal switch MUST be replaced if it is damaged.

!

WARNING

FIRE, CARBON MONOXIDE POISONING HAZARD

Failure to follow this warning could result in personal injury,

death, and/or property damage.
DO NOT reset the device or restart the furnace unless the

cause of the interruption has been identified and corrected by

a qualified agency. Ensure that the Blocked Vent Shut--Off

has been cleaned by a qualified agency before placing into

service. Annual inspection and cleaning of the Blocked Vent

Shut--Off by a qualified agency is required.

!

WARNING

FIRE, CARBON MONOXIDE POISONING HAZARD

Failure to follow this warning could result in personal injury,

death, and/or property damage.
The Blocked Vent Shut--Off

MUST

be inspected and

maintained annually by a qualified agency.

!

WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury

or death.
Disconnect electrical power supply to the furnace before

wiring the Blocked Vent Shut--Off.

!

WARNING

CUT HAZARD

Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care

and wear appropriate protective clothing, safety glasses, and

gloves when handling parts and servicing furnaces.

CAUTION

!

374RAN

Summary of Contents for 374RAN

Page 1: ...Check 15 Step 4 Fan Adjustment Check 16 Step 5 Limit Control Check 17 Step 6 For Year Round Air Conditioning 17 CARE AND MAINTENANCE 17 Step 1 General 17 Step 2 Oil Burner 17 Step 3 Heat Exchanger an...

Page 2: ...g gasoline Never burn garbage or paper in the heating system and never leave rags paper or any flammable items around the unit WARNING All local and national code requirements governing installation o...

Page 3: ...the structure The furnace is controlled by a thermostat It may not be hot wired to provide heat continuously to the structure without thermostatic control Clean outside air is provided for combustion...

Page 4: ...st be avoided Such contamination would include the following ammonia chlorine hydrogen sulfide halogenated hydrocarbons carbon tetrachloride cleaning solvents hydrochloric acid water softening chemica...

Page 5: ...side of Structure If outside air is supplied to a confined space then the 2 openings must be equal and located as above 1 If combustion air is taken through a permanent opening directly communicating...

Page 6: ...each end of attic ends 1 ft 0 3m above floor Water heater A06463 Fig 4 Combustion Air Taken From Outdoors Through Vertical Ducts without louvers in foundation The Outlet air duct and Inlet air duct m...

Page 7: ...ter Outlet air duct Inlet air duct A06465 Fig 6 Combustion Air Taken From Outdoors Through Horizontal Ducts The top opening and the bottom opening must each be 8 in x 18 in when a 105 size furnace is...

Page 8: ...obstructions Any blockage must be cleared before installing furnace 3 Cleaning chimney or vent if previously used for venting a solid fuel burning appliance or fireplace 4 Confirming that all unused...

Page 9: ...installed in the flue between 2 in and 12 in from the furnace outlet and between the furnace outlet and draft regulator See Fig 9 Diagram B Riello A06403 Fig 8 Wiring Diagram for Riello Burner FIRE C...

Page 10: ...e and cleaning pipes The BVSO must be installed between 2 in and 12 in from the furnace outlet Limit Switches A06614 Fig 9 Blocked Vent Shut Off Device Wiring Installation shown Upflow with vertical e...

Page 11: ...n personal injury death or property damage Do not connect aluminum wire between disconnect switch and furnace Use only copper wire WARNING The control system depends on correct polarity of power suppl...

Page 12: ...12 BLOCKED VENT SHUT A06627 Fig 14 Wiring Diagram 374RAN...

Page 13: ...provided for air filter access Refer to Table 4 for filter rack flange dimensions for return air duct Table 4 Filter Size and Quantity UNIT SIZE AIR FILTER SIZE IN mm FLANGE OPENING SIZE IN mm 036105...

Page 14: ...ce Wiring with 1 Speed Air Conditioner A04184 Fig 16 24 VAC Oil Furnace Wiring with 2 Speed Air Conditioner A04185 Fig 17 24 VAC Oil Furnace with 1 Speed Heat Pump A04186 Fig 18 24 VAC Oil Furnace Wir...

Page 15: ...the BLWM keeps continuous blower speed until the end of Short run delay period After which the BLWM operates at the appropriate low cooling airflow When the thermostat is satisfied the BLWM switches t...

Page 16: ...ncluded with damper The draft regulator should be adjusted after furnace has been firing for at least 5 min and set between 0 025 and 0 035 in wc See Table 5 Table 5 Furnace Draft Conditions in wc FUR...

Page 17: ...ion for at least 15 minutes restrict return air supply by blocking filters or closing return registers and allow furnace to shut down on high limit The burner should shut off and main blower should co...

Page 18: ...required If cleaning is necessary the following steps should be performed BURN HAZARD Failure to follow this caution may result in personal injury If furnace has been in operation some surfaces may b...

Page 19: ...D13 R13 JW2 JW3 JW7 LED7 GRN R14 R12 D17 D18 D19 D21 D15 D16 LED4 LED3 LED5 LED7 LED8 LED1 GRN GRN GRN GRN GRN GRN P3 Y Y Y2 G DH O W R C HSC 1 1168 83 1 NOTES 1 The Red LED to the right of P 1 will i...

Page 20: ...SW2 COOL DIP SWITCH POSITION A C SIZE TON AIRFLOW CFM EXTERNAL STATIC PRESSURE IN WC 0 2 0 5 0 7 0 9 A 1 OFF 2 OFF 3 0 918 973 973 827 A 1 OFF 2 OFF 1010 1070 1070 910 A 1 OFF 2 OFF 826 876 876 744 B...

Page 21: ...OLING SW2 COOL DIP SWITCH POSITION A C SIZE TON AIRFLOW CFM EXTERNAL STATIC PRESSURE IN WC 0 2 0 5 0 7 0 9 A 1 OFF 2 OFF 5 0 1738 1738 1738 1725 A 1 OFF 2 OFF 1912 1912 1912 1898 A 1 OFF 2 OFF 1564 15...

Page 22: ...nge at any time specifications or designs without notice and without incurring obligations E2009 Bryant Heating Cooling Systems 7310 W Morris St Indianapolis IN 46231 Printed in U S A Edition Date 05...

Reviews: