background image

For Example:

If the unconfined space is of unusually tight construction, air for
combustion and ventilation MUST come from either the outdoors
or spaces freely communicating with the outdoors. Combustion
and ventilation openings must be sized the same as for a confined
space as defined below. Return air must not be taken from the
room unless an equal or greater amount of air is supplied to the
room.

V.

CONFINED SPACE

A confined space is defined as a space whose volume is less than
50 cu ft per 1000 Btuh of total input ratings of all appliances
installed in that space. A confined space MUST have provisions
for supplying air for combustion, ventilation, and dilution of flue
gases using 1 of the following methods. (See Figs. 3, 4, and Table
2.)

NOTE:

In determining free area of an opening, the blocking

effect of louvers, grilles, and screens must be considered. If free
area of louver or grille design is unknown, assume that wood
louvers have a 20 percent free area and metal louvers or grilles
have a 60 percent free area. Screens, when used, must not be
smaller than 1/4-in. mesh. Louvers and grilles must be constructed
so they cannot be closed.

The size of the openings depends upon whether air comes from
outside of the structure or an unconfined space inside the structure.

1. All air from inside the structure requires 2 openings (for

structures not usually tight):

a. Each opening MUST have at least 1 sq in. of free area

per 1000 Btuh of total input for all equipment within the
confined space, but not less than 100 sq in. per opening.
(See Fig. 3 and Table 2.) The minimum dimension of air
openings shall not be less than 3 in.

b. If building is constructed unusually tight, a permanent

opening directly communicating with the outdoors shall
be provided. See item 2 below.

c. If furnace is installed on a raised platform to provide a

return-air plenum, and return air is taken directly from
hallway or space adjacent to furnace, all air for combus-
tion must come from outdoors.

2. Air from outside the structure requires 1 of the following

methods:

a. If combustion air is taken from outdoors through 2

vertical ducts, the openings and ducts MUST have at
least 1 sq in. of free area per 4000 Btuh of total input for
all equipment within the confined space. (See Figs. 3, 4,
and Table 2.)

b. If combustion air is taken from outdoors through 2

horizontal ducts, the openings and ducts MUST have at
least 1 sq in. of free area per 2000 Btuh of total input for
all equipment within the confined space. (See Fig. 4 and
Table 2.)

c. If combustion air is taken from outdoors through a single

opening or duct (horizontal or vertical) commencing
within 12 in. of the top of the confined space, opening
and duct MUST have at least 1 sq in. of free area per

3000 Btuh of the total input for all equipment within the
confined space and not less than the sum of the areas of
all vent connectors in the confined space. (See Fig. 4 and
Table 2.) Equipment clearances to the structure shall be
at least 1 in. from the sides and back and 6 in. from the
front of the appliances.

When ducts are used, they must be of the same cross-sectional area
as the free area of the openings to which they connect. The
minimum dimension of ducts must not be less than 3 in. (See Fig.
4.)

AIR DUCTS

This section covers installation of the 376CAV Series H and J
furnace.

I.

GENERAL REQUIREMENTS

The duct system should be designed and sized according to
accepted national standards such as those published by: Air
Conditioning Contractors Association (ACCA), Sheet Metal and
Air Conditioning Contractors National Association (SMACNA) or
American Society of Heating, Refrigerating and Air Conditioning
Engineers (ASHRAE). Or consult factory The Air Systems Design
Guidelines
reference tables available from your local distributor.
The duct system should be sized to handle the required system
design airflow CFM at the design external static pressure.

When a furnace is installed so that the supply ducts carry air to
areas outside the space containing the furnace, the return air must
also be handled by a duct(s) sealed to the furnace casing and
terminating outside the space containing the furnace.

Secure ductwork with proper fasteners for type of ductwork used.
Seal supply- and return-duct connections to furnace with code
approved tape or duct sealer.

Flexible connections should be used between ductwork and
furnace to prevent transmission of vibration. Ductwork passing
through unconditioned space should be insulated to enhance
system performance. When air conditioning is used, a vapor
barrier is recommended.

Maintain a 1-in. clearance from combustible materials to supply air
ductwork for a distance of 36 in. horizontally from the furnace. See
NFPA 90B or local code for further requirements.

II.

DUCTWORK ACOUSTICAL TREATMENT

Metal duct systems that do not have a 90 degree elbow and 10 ft
of main duct to the first branch take-off may require internal
acoustical lining. As an alternative, fibrous ductwork may be used
if constructed and installed in accordance with the latest edition of
SMACNA construction standard on fibrous glass ducts. Both
acoustical lining and fibrous ductwork shall comply with NFPA
90B as tested by UL Standard 181 for Class 1 Rigid air ducts.

III.

SUPPLY AIR CONNECTIONS

A.

Downflow Furnaces

Connect supply-air duct to supply-air opening on furnace. The
supply-air ducts attachment must ONLY be connected to furnace
supply/outlet or air conditioning coil casing (when used), when
installed on non-combustible material. When installed on combus-
tible material, supply-air duct attachment must ONLY be con-
nected to an accessory subbase or factory approved air condition-
ing coil casing. DO NOT cut main furnace casing to attach supply
side air duct, humidifier, or other accessories. All accessories
MUST be connected external to the furnace main casing.

B.

Horizontal Furnaces

Connect supply-air duct to supply-air opening on furnace. The
supply-air ducts attachment must ONLY be connected to furnace
supply/outlet or air conditioning coil casing (when used). DO NOT
cut main furnace casing to attach supply side air duct, humidifier,
or other accessories. All accessories MUST be connected external
to the furnace main casing.

376CAV FURNACE

INPUT BTUH

MINIMUM SQ FT WITH

7–1/2 FT CEILING

46,000

307

69,000

460

92,000

613

115,000

767

135,000

920

—5—

Summary of Contents for 376CAV

Page 1: ...words DANGER WARNING and CAUTION and NOTE These words are used with the safety alert symbol DANGER identifies the most serious hazards which will result in severe personal injury or death WARNING sig...

Page 2: ...D E VENT CONN SHIP WT LB 024050 14 3 16 12 9 16 12 11 16 4 123 036050 14 3 16 12 9 16 12 11 16 4 128 024070 14 3 16 12 9 16 12 11 16 4 130 036070 14 3 16 12 9 16 12 11 16 4 139 036096 17 1 2 15 7 8 1...

Page 3: ...nace the control and the person at the same electro static potential 1 Disconnect all power to the furnace DO NOT TOUCH THE CONTROL OR ANY WIRE CONNECTED TO THE CONTROL PRIOR TO DISCHARGING YOUR BODY...

Page 4: ...y downflow subbase which is available from your distributor or branch when required II LOCATION RELATIVE TO COOLING EQUIPMENT The cooling coil must be installed parallel with or on the downstream side...

Page 5: ...d they must be of the same cross sectional area as the free area of the openings to which they connect The minimum dimension of ducts must not be less than 3 in See Fig 4 AIR DUCTS This section covers...

Page 6: ...SQ IN PER 1000 BTUH IN DOOR OR WALL 12 MAX 1 SQ IN PER 1000 BTUH IN DOOR OR WALL 12 MAX INTERIOR HEATED SPACE Minimum opening size is 100 sq in with minimum dimensions of 3 in Minimum of 3 in when typ...

Page 7: ...APPLICATION PLENUM OPENING FLOOR OPENING A B C D 14 3 16 Non Combustible Flooring 12 11 16 19 13 3 8 19 5 8 Combustible Flooring Using KGASB Subbase 11 13 16 19 13 7 16 20 3 8 Combustible Flooring wit...

Page 8: ...VIII FILTER ARRANGEMENT WARNING Never operate unit without filter access door removed Failure to follow this warning could result in fire personal injury or death Fig 8 Typical Attic Installation A97...

Page 9: ...If a flexible connector is required or al lowed by the authority having jurisdiction black iron pipe shall be installed at the gas valve and extend a minimum of 2 in outside the furnace casing WARNIN...

Page 10: ...pple into the lower end of the tee The capped nipple should extend below the level of the gas controls See Fig 13 Piping should be pressure tested in accordance with local and national plumbing and ga...

Page 11: ...vided for 24 v humidifier connection See Fig 16 HUM terminal is energized with 24 v 0 5 amp maximum after inducer pressure switch closes WARNING DO NOT connect furnace control HUM terminal to HUM humi...

Page 12: ...motor comes up to speed the pressure switch contacts close to begin a 15 sec prepurge period b Igniter warm up At the end of the prepurge period the igniter is energized for a 17 sec igniter warm up...

Page 13: ...pump the furnace control automatically changes the timing sequence to avoid long blower off time during demand defrost cycles When the W Y or W Y G thermostat inputs are received at the same time the...

Page 14: ...C CONDUCTOR ON PCB FIELD WIRING TERMINAL FIELD GROUND EQUIPMENT GROUND FIELD SPLICE PLUG RECEPTACLE L1 L2 L1 BLWR HI LO TO 115VAC FIELD DISCONNECT NOTE 4 EQUIPMENT GROUND SPARE 2 HEAT SPARE 1 COOL NOT...

Page 15: ...Obtain average yearly gas specific gravity from local gas supplier 3 Verify furnace model Table 7 can only be used for model 376CAV Furnaces 4 Find installation altitude in Table 7 NOTE For Canada al...

Page 16: ...3 2 7 43 2 8 43 2 9 43 3 0 43 3 1 1025 43 2 6 43 2 6 43 2 7 43 2 8 43 2 9 ALTITUDE RANGE FT AVG GAS HEAT VALUE BTU CU FT SPECIFIC GRAVITY OF NATURAL GAS 0 58 0 60 0 62 0 64 0 66 Orifice no Manifold Pr...

Page 17: ...43 2 4 43 2 5 43 2 5 43 2 6 850 43 2 2 43 2 2 43 2 3 43 2 4 43 2 5 875 43 2 0 43 2 1 43 2 2 43 2 3 43 2 3 ALTITUDE RANGE FT AVG GAS HEAT VALUE AT ALTITUDE BTU CU FT SPECIFIC GRAVITY OF NATURAL GAS 0 5...

Page 18: ...re Orifice No Manifold Pressure Orifice No Manifold Pressure Orifice No Manifold Pressure U S A Only 9001 to 10 000 575 43 3 0 43 3 1 43 3 2 43 3 3 43 3 4 600 43 2 7 43 2 8 43 2 9 43 3 0 43 3 1 625 43...

Page 19: ...or varying the heating cycle length NOTE When using an electronic thermostat set cycle rate for 3 cycles per hr V CHECK SAFETY CONTROLS The flame sensor gas valve and pressure switch were all checked...

Page 20: ...ts when used a Turn off 115 v power to furnace b Remove blower access door c Disconnect red motor lead at blower speed selector Mark terminal for proper re connection d Replace blower access door e Tu...

Page 21: ...pward Slope _________________ Joints Secure _________________ See Vent Table Instructions CHECKLIST START UP _________________ Gas Input Rate Set Within 2 percent of Rating Plate _________________ Tem...

Page 22: ...22...

Page 23: ...23...

Page 24: ...o based formats and materials All include video and or slides plus companion book Classroom Service Training plus hands on the products in our labs can mean increased confidence that really pays divid...

Reviews: