Table 9 — Fan Performance — Power Exhaust
580G,H240-360
Airflow
(Cfm)
Low Speed
Medium Speed
High Speed
208 v
230, 460, 575 v
208 v
230, 460, 575 v
208 v
230, 460, 575 v
ESP
Bhp
Watts
ESP
Bhp
Watts
ESP
Bhp
Watts
ESP
Bhp
Watts
ESP
Bhp
Watts
ESP
Bhp
Watts
6,500
0.32
2.82
3160
0.70
2.98
3340
—
—
—
—
—
—
—
—
—
—
—
—
6,700
0.23
2.87
3220
0.63
3.03
3400
0.60
3.01
3380
0.82
3.23
3620
—
—
—
—
—
—
6,900
0.17
2.92
3270
0.59
3.09
3460
0.55
3.07
3440
0.78
3.28
3680
—
—
—
—
—
—
7,100
0.13
2.93
3290
0.56
3.11
3490
0.49
3.12
3500
0.73
3.34
3740
—
—
—
—
—
—
7,300
0.09
2.97
3330
0.53
3.15
3530
0.43
3.18
3560
0.68
3.39
3800
—
—
—
—
—
—
7,500
—
—
—
0.51
3.19
3580
0.39
3.24
3630
0.64
3.44
3860
—
—
—
—
—
—
7,700
—
—
—
0.48
3.23
3620
0.33
3.27
3670
0.59
3.48
3900
0.60
3.69
4140
0.73
3.98
4460
7,900
—
—
—
0.45
3.27
3670
0.27
3.32
3720
0.54
3.52
3950
0.56
3.74
4190
0.69
4.02
4510
8,100
—
—
—
0.40
3.33
3730
0.22
3.36
3770
0.49
3.57
4000
0.51
3.78
4240
0.65
4.07
4560
8,500
—
—
—
—
—
—
0.17
3.47
3890
0.40
3.67
4120
0.41
3.83
4290
0.56
4.12
4620
8,900
—
—
—
—
—
—
0.00
3.58
4010
0.30
3.77
4230
0.31
3.93
4410
0.47
4.23
4740
9,300
—
—
—
—
—
—
—
—
—
0.22
3.87
4340
0.20
4.07
4560
0.37
4.37
4900
9,700
—
—
—
—
—
—
—
—
—
0.16
3.95
4430
0.11
4.17
4670
0.30
4.47
5010
10,100
—
—
—
—
—
—
—
—
—
0.12
4.03
4520
0.04
4.25
4770
0.23
4.56
5110
10,500
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
0.17
4.66
5220
10,900
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
0.12
4.75
5330
11,300
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
0.07
4.80
5380
11,700
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
0.04
4.83
5420
LEGEND
Bhp
— Brake Horsepower
ESP
— External Static Pressure (in. wg)
Watts — Input Watts to Motor
Table 10 — Motor Limitations
STANDARD EFFICIENCY MOTORS
Nominal
Hp
Maximum
Bhp
Maximum Amps
Maximum
Watts
Motor
Efficiency
230
460
575
5
5.9
14.6
—
—
5,030
87.5
5.9
—
7.9
6.0
5,030
87.5
7.5
8.7
22.0
—
—
7,334
88.5
9.5
—
12.0
10.0
8,008
88.5
10
10.2
28.0
—
—
8,502
89.5
11.8
—
14.6
12.0
9,836
89.5
15
15.3
43.8
—
—
12,543
91.0
18.0
—
21.9
19.0
14,756
91.0
20
22.4
62.0
—
—
18,363
91.0
23.4
—
28.7
23.0
19,183
91.0
HIGH EFFICIENCY MOTORS
Nominal
Hp
Maximum
Bhp
Maximum Amps
Maximum
Watts
Motor
Efficiency
230
460
5
5.9
15.8
—
4,918
89.5
5.9
—
7.9
4,918
89.5
7.5
8.7
22.0
—
7,078
91.7
9.5
—
12.0
7,728
91.7
10
10.2
28.0
—
8,298
91.7
11.8
—
15.0
9,600
91.7
15
15.3
43.8
—
12,273
93.0
18.0
—
21.9
14,439
93.0
20
22.4
58.2
—
17,853
93.6
23.4
—
28.7
18,650
93.6
LEGEND
BHP — Brake Horsepower
NOTE: Extensive motor and electrical testing on the these units has en-
sured that the full horsepower range of the motor can be utilized with
confidence. Using your fan motors up to the horsepower ratings shown
on the Motor Limitations table will not result in nuisance tripping or pre-
mature motor failure. Unit warranty will not be affected.
Table 11 — Air Quantity Limits
UNIT 580G,H
MINIMUM HEATING
CFM
MINIMUM COOLING
CFM
MAXIMUM
CFM
240
6,000
6,000
10,000
300
7,500
7,500
12,500
324
8,250
8,250
13,750
360
9,000
9,000
15,000
—27—