UNIT SIZE
580G
OPERATING
WEIGHT
A
B
CORNER WEIGHT
(lb)
lb
ft-in.
ft-in.
1
2
3
4
240 350
4176
6- 0
3
⁄
8
3-6
3
⁄
8
879
954
1220
1124
240 525
4256
6- 1
5
⁄
16
3-6
11
⁄
16
917
973
1218
1148
300 350
4262
5- 9
5
⁄
8
3-8
899
899
1232
1232
300 525
4342
5-10
1
⁄
8
3-8
5
⁄
16
929
916
1240
1257
324 350
4262
5- 9
5
⁄
8
3-8
899
899
1232
1232
324 525
4342
5-10
1
⁄
8
3-8
5
⁄
16
929
916
1240
1257
360 350
4262
5- 9
5
⁄
8
3-8
899
899
1232
1232
360 525
4342
5-10
1
⁄
8
3-8
5
⁄
16
929
916
1240
1257
Fig. 2 — Base Unit Dimensions, 580G240-360
NOTES:
1. Weights include economizer (STD).
2.
Center of gravity.
3. Do not locate adjacent units with flue discharge
facing economizer inlet. Min. clearances to be:
Adjacent Units: 15
8
-0
9
Top of Units: No Overhang
Condenser Coil: 4
8
-0
9
Economizer Side: 6
8
-0
9
Heat Side: 4
8
-0
9
Filter Access Side: 10
8
-0
9
(For Removal of Evapo-
rator Coil)
4. For smaller service and operational clearances, con-
tact Carrier Application Engineering department.
5. Bottom ducts designed to be attached to acces-
sory roof curb. If unit is mounted on dunnage, it is
recommended the ducts be supported by braces
as done on accessory roof curb.
—3—