56
APPENDIX III. FAN PERFORMANCE (cont.)
580J*05
1 Phase
4 Ton Horizontal Supply
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
0.2
0.4
0.6
0.8
1.0
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
Standard Static Option
Medium Static Option
1200
643
0.23
762
0.34
859
0.46
944
0.58
1020
0.71
1300
675
0.28
790
0.40
886
0.52
969
0.65
1044
0.78
1400
707
0.33
819
0.45
913
0.58
996
0.72
1070
0.86
1500
740
0.38
849
0.52
941
0.66
1023
0.80
1096
0.95
1600
773
0.45
879
0.59
970
0.73
1050
0.88
1123
1.04
1700
807
0.52
910
0.67
999
0.82
1078
0.98
1150
1.14
1800
841
0.59
942
0.75
1029
0.91
1106
1.08
1177
1.25
1900
875
0.68
974
0.85
1059
1.02
1135
1.19
1205
1.37
2000
910
0.77
1006
0.95
1090
1.13
1165
1.31
1234
1.49
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
1.2
1.4
1.6
1.8
2.0
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
Medium Static Option
Field---Supplied Drive
1
1200
1089
0.84
1153
0.98
1213
1.12
---
---
---
---
1300
1113
0.92
1177
1.06
---
---
---
---
---
---
1400
1138
1.01
1201
1.15
---
---
---
---
---
---
1500
1163
1.10
---
---
---
---
---
---
---
---
1600
1189
1.20
---
---
---
---
---
---
---
---
1700
---
---
---
---
---
---
---
---
---
---
1800
---
---
---
---
---
---
---
---
---
---
1900
---
---
---
---
---
---
---
---
---
---
2000
---
---
---
---
---
---
---
---
---
---
NOTE
: For more information, see General Fan Performance Notes on page 53.
Boldface
indicates field---supplied drive is required.
1. Recommend using field---supplied motor pulley (part number KR11HY161) and belt (part number KR30AE035).
580J*05
1 Phase
4 Ton Vertical Supply
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
0.2
0.4
0.6
0.8
1.0
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
Standard Static Option
Medium Static Option
1200
666
0.26
778
0.37
871
0.47
952
0.57
1025
0.67
1300
701
0.31
810
0.43
901
0.54
981
0.65
1053
0.76
1400
737
0.36
842
0.49
931
0.62
1010
0.74
1081
0.86
1500
773
0.42
875
0.57
963
0.70
1040
0.84
1110
0.96
1600
810
0.49
909
0.65
994
0.79
1070
0.94
1140
1.08
1700
847
0.57
943
0.73
1027
0.89
1101
1.05
1170
1.20
1800
885
0.66
978
0.83
1060
1.00
1133
1.16
1200
1.32
1900
923
0.75
1014
0.94
1093
1.11
1165
1.29
1231
1.46
2000
962
0.85
1049
1.05
1127
1.24
1198
1.42
1263
1.61
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)
1.2
1.4
1.6
1.8
2.0
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
Medium Static Option
Field---Supplied Drive
1
1200
1093
0.77
1155
0.87
1213
0.96
1268
1.05
1321
1.14
1300
1119
0.87
1181
0.98
1239
1.08
1294
1.18
---
---
1400
1147
0.98
1208
1.09
---
---
---
---
---
---
1500
1175
1.09
---
---
---
---
---
---
---
---
1600
---
---
---
---
---
---
---
---
---
---
1700
---
---
---
---
---
---
---
---
---
---
1800
---
---
---
---
---
---
---
---
---
---
1900
---
---
---
---
---
---
---
---
---
---
2000
---
---
---
---
---
---
---
---
---
---
NOTE
: For more information, see General Fan Performance Notes on page 53.
Boldface
indicates field---supplied drive is required.
1. Recommend using field---supplied motor pulley (part number KR11HY161) and belt (part number KR30AE035).
580J
Summary of Contents for 580J*04--12
Page 9: ...9 COOLING CHARGING CHARTS C08203 C08204 Fig 12 Cooling Charging Charts 580J ...
Page 10: ...10 COOLING CHARGING CHARTS cont C08228 C08229 Fig 12 Cooling Charging Charts cont 580J ...
Page 11: ...11 COOLING CHARGING CHARTS cont C08437 C08438 Fig 12 Cooling Charging Charts cont 580J ...
Page 12: ...12 COOLING CHARGING CHARTS cont C08439 Fig 12 Cooling Charging Charts cont 580J ...
Page 46: ...46 C08308 Fig 52 580J Typical Unit Wiring Diagram Power 06A B C 208 230 3 60 580J ...