77
580J**14
3 PHASE
12.5 TON HORIZONTAL SUPPLY
CFM
Available External Static Pressure (in. wg)
0.2
0.4
0.6
0.8
1.0
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
Standard Static Option
Medium Static Option
3438
639
0.98
713
1.20
781
1.43
843
1.65
901
1.88
3750
683
1.23
753
1.47
817
1.71
877
1.96
933
2.21
4063
728
1.52
794
1.78
855
2.04
912
2.31
966
2.57
4375
774
1.85
836
2.13
894
2.41
949
2.70
1001
2.98
4688
820
2.23
879
2.53
935
2.83
987
3.14
1037
3.44
5000
867
2.66
923
2.98
976
3.30
1026
3.63
1074
3.95
5313
914
3.15
967
3.49
1018
3.83
1066
4.17
1112
4.52
5625
962
3.69
1012
4.05
1061
4.42
--
--
--
--
5938
1009
4.30
1058
4.68
--
--
--
--
--
--
6250
--
--
--
--
--
--
--
--
--
--
CFM
Available External Static Pressure (in. wg)
1.2
1.4
1.6
1.8
2.0
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
Medium Static Option
High Static Option
3438
955
2.12
1007
2.35
1056
2.59
1103
2.83
1148
3.08
3750
985
2.46
1035
2.71
1083
2.97
1129
3.23
1173
3.49
4063
1017
2.84
1066
3.12
1112
3.39
1157
3.67
1200
3.95
4375
1050
3.27
1097
3.56
1142
3.86
1186
4.15
1228
4.45
4688
1084
3.75
1130
4.06
1174
4.37
1216
4.68
1257
5.00
5000
1120
4.28
1164
4.61
--
--
1248
5.27
1288
5.60
5313
--
--
--
--
--
--
--
--
--
--
5625
--
--
--
--
--
--
--
--
--
--
5938
--
--
--
--
--
--
--
--
--
--
6250
--
--
--
--
--
--
--
--
--
--
NOTE
: For more information, see General Fan Performance Notes.
Boldface
indicates field--supplied drive is required.
580J
Summary of Contents for 580J*08--14D
Page 10: ...10 COOLING CHARGING CHARTS C09221 Fig 10 Cooling Charging Charts 08D F Both Circuits 580J ...
Page 11: ...11 COOLING CHARGING CHARTS C09222 Fig 11 Cooling Charging Charts 12D F Both Circuits 580J ...
Page 36: ...36 C07129 Fig 42 RTU MP Multi Protocol Control Board 580J ...
Page 37: ...37 C09163 Fig 43 Typical RTU MP System Control Wiring Diagram 580J ...
Page 60: ...60 C09156 Fig 73 580J Typical Unit Wiring Diagram Power 08D F 208 230 3 60 580J ...
Page 61: ...61 C09157 Fig 74 580J Typical Unit Wiring Diagram Control 08 12D F 208 230 3 60 580J ...
Page 84: ...84 580J ...