26
Table 7—CO
2
Sensor Standard Settings
SETTING
EQUIPMENT
OUTPUT
VENTILATION
RATE
(cfm/Person)
ANALOG
OUTPUT
CO
2
CONTROL RANGE
(ppm)
OPTIONAL
RELAY SETPOINT
(ppm)
RELAY
HYSTERESIS
(ppm)
1
Proportional
Any
0-10V
4-20 mA
0-2000
1000
50
2
Interface w/Standard
Building Control System
Proportional
Any
2-10V
7-20 mA
0-2000
1000
50
3
Building Control System
Exponential
Any
0-10V
4-20 mA
0-2000
1100
50
4
Proportional
15
0-10V
4-20 mA
0-1100
1100
50
5
Economizer
Proportional
20
0-10V
4-20 mA
0- 900
900
50
6
Economizer
Exponential
15
0-10V
4-20 mA
0-1100
1100
50
7
Exponential
20
0-10V
4-20 mA
0- 900
900
50
8
Health & Safety
Proportional
—
0-10V
4-20 mA
0-9999
5000
500
9
Parking/Air Intakes/
Loading Docks
Proportional
—
0-10V
4-20 mA
0-2000
700
50
LEGEND
ppm —
Parts Per Million
6000
5000
4000
3000
2000
1000
0
0
0.05
0.1
0.15
0.2
0.25
0.3
0.35
DEL
TA
P
IN.
WG
4 & 5 ton
6 ton
3 ton
C06133
Fig. 41
---
Perfect Humidity
t
Adaptive Dehumidification System Static Pressure Drop (in. wg)
C06134
Fig. 42
---
Belt Drive Motor Mounting
C06041
Fig. 43
---
Indoor--Fan Pulley Adjustment