10
TABLE 5 – HEATING RATING TABLE -- LOW NO
X
1
UNIT
GAS HEAT
LOW NOx HEAT EXCHANGER
TEMP RISE
(DEG F)
THERMAL
EFFICIENCY
(%)
AFUE
(%)
INPUT / OUTPUT
STAGE 1 (MBH)
INPUT / OUTPUT
STAGE 2 (MBH)
Sin
gle
Pha
se
04
LOW
---
60 / 50
20 --- 50
81%
80%
MED
---
90 / 74
30 --- 60
81%
81%
HIGH
---
---
---
---
---
05
LOW
---
60 / 50
20 --- 50
81%
80%
MED
---
90 / 74
30 --- 60
81%
81%
HIGH
---
120 / 101
40 --- 70
81%
80%
06
LOW
---
60 / 50
15 --- 50
81%
80%
MED
---
90 / 74
25 --- 60
80%
81%
HIGH
---
120 / 101
35 --- 70
80%
81%
Th
re
e
P
ha
se
04
LOW
---
60 / 50
20 --- 50
81%
80%
MED
---
90 / 74
30 --- 60
81%
81%
HIGH
---
---
---
---
---
05
LOW
---
60 / 50
20 --- 50
81%
80%
MED
---
90 / 74
30 --- 60
81%
81%
HIGH
---
120 / 101
40 --- 70
81%
80%
06
LOW
---
60 / 50
15 --- 50
81%
80%
MED
---
90 / 74
25 --- 60
80%
81%
HIGH
---
120 / 101
35 --- 70
80%
81%
NOTE
:
1. Units meet California’s South Coast Air Quality Management District (SCAQMD) Low---NO
x
emissions requirement of 40
nanograms per joule or less.
TABLE 6 – SOUND PERFORMANCE TABLE
UNIT
COOLING
STAGES
OUTDOOR SOUND (dB) AT 60
A---WEIGHTED
63
125
250
500
1000
2000
4000
8000
04A
1
76
78.2
78.0
74.2
73.3
70.6
66.0
62.4
56.9
05A
1
78
84.7
83.6
77.1
74.6
72.3
68.3
64.7
60.9
06A
1
77
87.5
82.5
76.1
73.6
71.3
67.1
64.1
60.0
07A
1
82
90.1
82.6
81.0
79.4
77.0
73.0
70.4
66.7
08D
2
82
90.6
84.3
80.2
79.3
77.1
72.2
67.4
63.7
09D
2
82
88.6
85.0
81.6
79.5
77.4
74.1
71.0
66.3
LEGEND
dB --- Decibel
Use of the AHRI Certified
TM Mark indicates a
manufacturer’s
participation in the
program For verification
of certification for individual
products, go to
www.ahridirectory.org.
NOTES:
1. Outdoor sound data is measure in accordance with
AHRI.
2. Measurements are expressed in terms of sound power.
Do not compare these values to sound pressure values
because sound pressure depends on specific environ-
mental factors which normally do not match individual
applications. Sound power values are independent of
the environment and therefore more accurate.
3. A---weighted sound ratings filter out very high and very
low frequencies, to better approximate the response of
“average” human ear. A---weighted measurements for
Bryant units are taken in accordance with AHRI.
581J
Summary of Contents for 581J
Page 51: ...51 TYPICAL WIRING DIAGRAMS C08518 Fig 15 1 Stage Cooling Typical Power Diagram 581J ...
Page 52: ...52 TYPICAL WIRING DIAGRAMS cont C08577 Fig 16 2 Stage Cooling Typical Power Diagram 581J ...
Page 53: ...53 C08524 Fig 17 1 Stage Typical Wiring Diagram 581J ...
Page 54: ...54 C08578 Fig 18 2 Stage Typical Wiring Diagram 581J ...