6
—
– Not applicable.
NOTE: Units meet California’s South Coast Air Quality Management District
(SCQAQMD) Low - NO
X
emissions requirement of 40 nanograms per joule or
less.
LEGEND
dB
– Decibel
NOTES:
1. Outdoor sound data is measured in accordance with AHRI standard 270.
2. Measurements are expressed in terms of sound power. Do not compare these
values to sound pressure values because sound pressure depends on specific
environmental factors which normally do match individual applications. Sound
power values are independent of the environment and therefore more accurate.
3. A-weighted sound ratings filter out very high and very low frequencies, to
better approximate the response of the “average” human ear. A-weighted mea-
surement for Bryant units are taken in accordance with AHRI standard 270.
HEATING RATING TABLE – LOW NO
X
(see note)
582J UNIT
GAS HEAT
LOW NO
X
HEAT EXCHANGER
TEMP RISE
(DEG F)
THERMAL
EFFICIENCY (%)
AFUE (%)
INPUT/OUTPUT
STAGE 1 (MBH)
INPUT/OUTPUT
STAGE 2 (MBH)
SINGLE/THREE PHASE
04
LOW
—
60/49
20–50
82.0%
81.3%
MED
—
90/73.5
30–60
82.0%
81.5%
HIGH
—
—
—
—
—
05
LOW
—
60/49
20–50
82.0%
81.3%
MED
—
90/73.5
30–60
82.0%
81.5%
HIGH
—
120/98
40–70
82.0%
81.3%
06
LOW
—
60/49
15–50
82.0%
81.3%
MED
—
90/73.5
25–60
82.0%
81.5%
HIGH
—
120/98
35–70
82.0%
81.3%
SOUND PERFORMANCE TABLE
582J UNIT
COOLING
STAGES
OUTDOOR SOUND (dB) AT 60 Hz
A–WEIGHTED
63
125
250
500
1000
2000
4000
8000
04 A
1
76
78.2
78.0
74.2
73.3
70.6
66.0
62.4
56.9
05 A
1
81
90.9
84.6
79.5
77.9
76.5
71.1
66.9
62.5
06 A
1
77
87.5
82.5
76.1
73.6
71.3
67.1
64.1
60.0
MINIMUM - MAXIMUM AIRFLOW RATINGS–NATURAL GAS AND PROPANE
VOLTAGE
UNIT
HEAT LEVEL
COOLING
AL HX HEATING
SS HX HEATING
MINIMUM
MAXIMUM
MINIMUM
MAXIMUM
MINIMUM
MAXIMUM
SINGLE
PHASE
582J*04
LOW
900
1500
900
1970
900
1970
MED
800
1520
800
1520
HIGH
—
—
—
—
582J*05
LOW
1200
2000
900
2470
900
2470
MED
1050
2280
1050
2280
HIGH
1230
2190
1230
2190
582J*06
LOW
1500
2500
900
3290
900
3290
MED
1050
2730
1050
2730
HIGH
1230
2820
1230
2820
THREE
PHASE
582J*04
LOW
900
1500
990
2190
990
2190
MED
1010
1570
1010
1570
HIGH
—
—
—
—
582J*05
LOW
1200
2000
990
2190
990
2190
MED
1330
2460
1330
2460
HIGH
1390
2220
1390
2220
582J*06
LOW
1500
2500
990
2730
990
2730
MED
1330
2880
1330
2880
HIGH
1390
2780
1390
2780
AHRI CAPACITY RATINGS (cont)