background image

OPTIONS AND ACCESSORIES

FACTORY-INSTALLED OPTIONS

Louvered Grille provides hail and vandalism protection. See
model number nomenclature for louvered grille options.

Coil Options include copper/copper and vinyl-coated construc-
tion for refrigerant coils. Units are shipped standard with copper
tube/aluminum fin construction. See model number nomencla-
ture for coil options.

FIELD-INSTALLED ACCESSORIES

Economizer with Solid-State Controls and Barometric
Relief Dampers
Manual Air Damper (25% open)
Filter Rack
Flat Roof Curbs (8-in. and 14-in.)
Square-to-Round Duct Transition Kit
Thermostats
Controls Upgrade Kit
Crankcase Heater
Compressor Hard Start Kit (for use on single-phase units only)
LP Conversion Kit
High Altitude Kit
Low NO

x

Kit

Low Ambient Kit (Motormaster

T

II Control)

Solid-State Time Guard

T

II Device

Duct Conversion Kit (Horizontal to Vertical)

Economizer with Solid-State Controls and Barometric Re-
lief Dampers 
includes filter racks and provide outdoor air during
cooling and reduce compressor operation.

Manual Outside Air Damper includes hood and filter rack with
adjustable damper blade for up to 25% outdoor air.

Flat Roof Curbs in both 8 in. and 14 in. sizes are available for
roof mounted applications.

Square-to-Round Duct Transition Kit enables 024-048 size
units to be fitted to 14 in. round ductwork.

Compressor Hard Start Kit assists compressor start-up by
providing additional starting torque on single-phase units and
prolongs compressor motor life.

Duct Conversion Kit consists of 2 duct covers to be placed
over the horizontal supply and return duct openings when the
unit is converted for downshot applications.

Thermostats provide control for the system heating and cooling
functions. Thermostat models are available in both program-
mable and non-programmable versions.

Controls Upgrade Kit supplies high and low pressure safety
protection and protects the unit from operating in unsuitable
conditions.

Crankcase Heater provides anti-floodback protection for low-
load cooling applications.

LP (Liquid Propane) Conversion Kit allows for conversion
from natural gas to liquid propane fuel.

Low NO

x

Kit for use with units being installed in California Air

Quality Management Districts which require NO

x

emissions of

40 nanograms/joule or less.

Low-Ambient Kit (Motormaster II Control) allows the use
of mechanical cooling down to outdoor temperatures as low
as 0° F.

Solid-State Time Guard II Device provides short-cycling pro-
tection for the compressor. Not required with corporate elec-
tronic thermostats.

Filter Rack features easy installation, serviceability, and high-
filtering performance for vertical applications.

High Altitude Kit is for use at 2001 to 6000 ft above sea level.
Kit consists of natural gas orifices that compensate for gas heat
operation at high altitude.

6

Summary of Contents for 583A Series

Page 1: ...Heat Exchangers are constructed of alumi nized steel for corrosion resistance and optimum heat transfer for improved efficiency The tubular design permits hot gases to make multiple passes across the path of the supply air In addition dimples located on the heat exchanger walls force the hot gases to stay in close contact with the walls improving heat transfer Direct Drive Multi Speed PSC Permanen...

Page 2: ...steel capable of withstanding 500 hours in salt spray Interior surfaces of the evaporator heat exchanger compartment are insulated with cleanable semi rigid insulation board which keeps the conditioned air from being affected by the outdoor ambient temperature and provides improved indoor air quality Conforms to American Society of Heating Refrig eration and Air Conditioning Engineers No 62P The s...

Page 3: ...db 67 F wb indoor entering air temperature and 95 F db outdoor entering air temperature 2 Before purchasing this appliance read important energy cost and efficiency information available from your retailer Option Code A Base Unit Wire Grille H Base Unit Louvered Grille J Unit with Wire Grille and Vinyl Coated Condenser Coil K Unit with Louvered Grille and Vinyl Coated Condenser Coil L Unit with Wi...

Page 4: ...80 1 036060 47 220 25 55 78 7 042060 47 220 15 45 78 7 036090 88 000 71 910 45 75 79 9 042090 90 000 71 910 35 65 79 9 048090 90 000 70 740 25 55 78 6 060090 90 000 70 740 25 55 78 6 048115 115 000 93 265 35 65 81 1 060115 048130 130 000 104 390 40 70 80 3 060130 LEGEND AFUE Annual Fuel Utilization Efficiency NOTE Before purchasing this appliance read important energy cost and efficiency informati...

Page 5: ...24 20 x 24 24 x 30 24 x 30 UNIT SIZE 583A 048090 048115 048130 060090 060115 060130 NOMINAL CAPACITY ton 4 4 4 5 5 5 OPERATING WEIGHT lb 421 421 421 468 468 468 COMPRESSORS Scroll Quantity 1 REFRIGERANT R 22 Quantity lb 7 2 7 2 7 2 8 1 8 1 8 1 REFRIGERANT METERING DEVICE Acutrol Device Orifice ID in 034 034 034 032 032 032 CONDENSER COIL Rows Fins in 2 17 2 17 2 17 2 17 2 17 2 17 Face Area sq ft 1...

Page 6: ...14 in round ductwork Compressor Hard Start Kit assists compressor start up by providing additional starting torque on single phase units and prolongs compressor motor life Duct Conversion Kit consists of 2 duct covers to be placed over the horizontal supply and return duct openings when the unit is converted for downshot applications Thermostats provide control for the system heating and cooling f...

Page 7: ...OPTIONS AND ACCESSORIES cont Economizer Filter Rack Manual Outside Air Damper DAMPER BLADE MANUAL OUTSIDE AIR HOOD REPLACEMENT PANEL 7 ...

Page 8: ...4 4 NEC REQ D CLEARANCES in mm Between units power entry side 42 1066 8 Unit and ungrounded surfaces power entry side 36 914 Unit and block or concrete walls and other grounded surfaces control box side 42 1066 8 UNIT 583A ELECTRICAL CHARACTERISTICS UNIT WEIGHT UNIT HEIGHT in mm A CENTER OF GRAVITY in mm lb kg X Y Z 024040 060 208 230 1 60 290 0 639 3 35 02 889 5 22 0 558 8 14 5 368 3 16 0 406 4 0...

Page 9: ...RANCES in mm Between units power entry side 42 1066 8 Unit and ungrounded surfaces power entry side 36 914 Unit and block or concrete walls and other grounded surfaces control box side 42 1066 8 UNIT 583A ELECTRICAL CHARACTERISTICS UNIT WEIGHT UNIT HEIGHT in mm A CENTER OF GRAVITY in mm lb kg X Y Z 042060 090 208 230 1 60 208 230 3 60 460 3 60 382 842 2 38 98 990 2 23 0 584 2 16 3 412 8 16 6 421 6...

Page 10: ...Seal strip must be applied as required to unit being installed 3 Dimensions in are in millimeters 4 Roof curb is made of 16 gage steel 5 Table lists only the dimensions per part number that have changed 6 Attach ductwork to curb flanges of duct rest on curb 7 Insulated panels 1 in thick fiberglass 1 lb density 8 Dimensions are in inches 3 0 4 0 BASE PAN BOTTOM SUPPLY 0 75 SIDE PANEL SUPPORT RIB S ...

Page 11: ... UNIT TO PROVIDE DESIGN CONDITION REQUIREMENTS In the Heating Capacities and Efficiencies table on page 4 note that the unit 583A 036090 will provide 71 910 Btuh with an input of 88 000 Btuh IV DETERMINE FAN SPEED AND POWER REQUIRE MENTS AT DESIGN CONDITIONS Before entering the air delivery tables calculate the total static pressure required From the given example the Wet Coil Pressure Drop Table ...

Page 12: ... 23 3 SHC 18 3 15 2 11 9 19 2 16 3 12 5 19 7 17 2 13 0 kW 2 78 2 84 2 88 2 84 2 93 2 96 2 93 3 02 3 06 583A 030 Temp F Air Ent Condenser Evaporator Air Cfm BF 875 0 138 1000 0 149 1125 0 159 Evaporator Air Ewb F 62 67 72 62 67 72 62 67 72 85 TC 27 5 30 2 32 7 28 2 30 9 33 4 28 8 31 4 33 8 SHC 24 4 20 3 16 0 26 2 21 5 16 7 27 8 22 7 17 4 kW 2 58 2 60 2 62 2 59 2 61 2 62 2 59 2 61 2 63 95 TC 26 2 29...

Page 13: ... 97 3 93 4 06 4 15 4 09 95 TC 37 6 41 6 44 9 38 3 42 0 45 1 38 7 42 0 45 1 SHC 34 4 29 0 23 0 36 6 30 3 23 5 38 7 31 3 23 8 kW 3 80 3 82 3 80 3 91 4 04 3 94 4 03 4 16 4 11 105 TC 35 9 40 0 43 6 36 6 40 3 43 7 37 3 40 3 43 6 SHC 33 6 28 4 22 5 35 6 29 7 23 0 37 3 30 8 23 4 kW 3 79 3 83 3 80 3 89 3 98 3 95 3 99 4 17 4 12 115 TC 34 2 38 2 42 0 34 9 38 5 42 1 35 8 38 5 42 0 SHC 32 7 27 7 21 9 34 9 29 ...

Page 14: ... 23 5 28 5 41 5 55 5 59 95 TC 52 2 58 0 63 7 53 2 58 5 64 1 53 9 58 4 64 0 SHC 48 2 41 0 32 7 51 8 43 2 33 6 53 9 44 8 34 2 kW 5 39 5 57 5 50 5 64 5 75 5 77 5 90 6 03 6 09 105 TC 49 1 54 4 60 4 49 9 54 9 60 7 50 9 55 0 60 5 SHC 47 3 39 4 31 5 49 9 41 6 32 4 50 9 43 5 33 0 kW 5 87 5 98 6 02 6 13 6 22 6 30 6 34 6 57 6 62 115 TC 45 9 50 2 55 2 46 8 50 3 55 5 47 3 50 2 55 3 SHC 45 3 37 4 29 4 46 8 39 ...

Page 15: ...5 593 574 549 518 485 454 Cfm 1626 1614 1579 1532 1478 1421 1361 1295 1218 1120 Med Watts 726 695 661 625 591 561 540 Cfm 1731 1672 1610 1541 1456 1345 1193 High Watts 790 766 742 713 Cfm 1699 1602 1494 1367 048 Low Watts 614 588 577 572 566 556 539 517 491 Cfm 1591 1549 1581 1490 1460 1421 1372 1312 1242 Med Watts 778 756 738 719 699 676 650 623 596 572 555 Cfm 1854 1837 1804 1759 1705 1643 1577 ...

Page 16: ...0 0 132 ECONOMIZER 1 in FILTER PRESSURE DROP in wg UNIT 583A PRESSURE DROP 024 036 0 20 042 060 0 25 OUTDOOR SOUND ONE THIRD OCTAVE BAND DATA DECIBELS UNIT 583A Frequency Hz 024 030 036 042 048 060 63 43 6 52 6 49 5 56 8 54 7 55 5 125 54 1 47 3 56 4 56 9 64 0 64 1 250 57 1 58 2 61 0 64 0 69 9 66 6 500 64 9 63 2 67 4 68 0 73 3 70 6 1000 67 6 66 1 68 1 67 7 73 5 72 6 2000 64 1 64 0 65 8 64 6 70 4 69...

Page 17: ...r Therefore heat input rate should be reduced at higher altitudes Orifices available through your distributor LIQUID PROPANE ONLY ORIFICE CONVERSION 3 5 in wg MANIFOLD PRESSURE ALTITUDE ft INPUT Btuh OUTPUT Btuh ORIFICE NUMBER 0 2000 40 000 33 200 50 57 000 47 310 46 85 500 70 965 46 115 000 95 450 42 127 000 105 410 41 2001 4500 33 290 27 630 53 47 430 39 370 50 71 150 59 050 50 95 700 79 430 45 ...

Page 18: ...TYPICAL PIPING AND WIRING Vertical Discharge Horizontal Discharge NEC National Electrical Code 18 ...

Page 19: ...he hori zontal discharge openings in the unit Units installed in horizontal discharge orientation do not require duct covers 4 Airflow Units are draw thru in the Cooling mode and blow thru in the Heating mode 5 Maximum cooling airflow To minimize the possibility of condensate blow off from the evaporator airflow through the units should not exceed 450 cfm ton 6 Minimum cooling airflow The minimum ...

Page 20: ...s Fuse or HACR Breaker NOTES 1 In compliance with NEC National Electrical Code requirements for multimotor and combination load equipment refer to NEC Articles 430 and 440 the overcurrent protective device for the unit shall be fuse or HACR breaker The CGA Canadian Gas Association units may be fuse or circuit breaker 2 Minimum wire size is based on 60 C copper wire If other than 60 C wire is used ...

Page 21: ...sformer Field Splice Terminal Marked Terminal Unmarked Splice Splice Marked Factory Wiring Field Control Wiring Field Power Wiring Accessory or Optional Wiring To Indicate Common Potential Only Not to Represent Wiring NOTES 1 If any of the original wires furnished are replaced it must be replaced with type 90 degree C wire or its equivalent 2 See Trade Prices for thermostat and subbases 3 Use 75 d...

Page 22: ...Outdoor Fan Motor QT Quadruple Terminal RS Rollout Switch SEN Sensor SW Switch TRAN Transformer Field Splice Terminal Marked Terminal Unmarked Splice Splice Marked Factory Wiring Field Control Wiring Field Power Wiring Accessory or Optional Wiring To Indicate Common Potential Only Not to Represent Wiring NOTES 1 If any of the original wires furnished are replaced they must be replaced with type 90...

Page 23: ...tdoor Fan Motor QT Quadruple Terminal RS Rollout Switch SEN Sensor SW Switch TRAN Transformer Field Splice Terminal Marked Terminal Unmarked Splice Splice Marked Factory Wiring Field Control Wiring Field Power Wiring Accessory or Optional Wiring To Indicate Common Potential Only Not to Represent Wiring NOTES 1 If any of the original wires furnished are replaced they must be replaced with type 90 d...

Page 24: ... indoor evapo rator fan relay IFR The normally open contacts of C close and complete the circuit through compressor motor COMP to outdoor condenser fan motor OFM Both motors start in stantly The set of normally open contacts of IFR close and com plete the circuit through IFM The IFM starts instantly On the loss of the thermostat call for cooling 24 v is removed from both the Y and G terminals prov...

Page 25: ...or air cavity section 5 Unit shall have a field supplied condensate trap C Fans 1 The evaporator fan shall be 3 speed direct drive as shown on equipment drawings 2 Fan wheel shall be made from steel and shall be double inlet type with forward curved blades with cor rosion resistant finish Fan wheel shall be dynamically balanced 3 Condenser fan shall be direct drive propeller type with aluminum bla...

Page 26: ...cooling in addi tion manual or automatic changeover and indoor fan control 7 Natural to Propane Conversion Kit Shall be complete with all required hardware to con vert to liquid propane LP operation at 3 5 in wg manifold pressure 8 Low Ambient Package Shall consist of a solid state control and condenser coil temperature sensor for controlling condenser fan motor operation which shall allow unit to...

Page 27: ......

Page 28: ...Copyright 1999 Bryant Heating Cooling Systems SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE UNIT MUST BE INSTALLED IN ACCORDANCE WITH INSTALLATION INSTRUCTIONS Printed in U S A 4 99 5258 300 ...

Reviews: