background image

Cancels: New

II 619F-18-1

4/1/06

installation, start-up and
service instructions

IN-CEILING CASSETTE
FAN COIL UNITS

619FNF

619FNQ

Sizes 018-03036

CONTENTS

Page

SAFETY CONSIDERATIONS

. . . . . . . . . . . . . . . . . . . . . . . . .  1

GENERAL

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  1

INSTALLATION

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-19

I.  Step 1 — Complete Pre-Installation Checks

. . . . . .  2

II.  Step 2 — Locating and Mounting the Unit

. . . . . . . .  6

III.  Step 3 — Locating and Mounting the Room 

Controller

 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  8

IV.  Step 4 — Complete Refrigerant Piping 

Connections

. . . . . . . . . . . . . . . . . . . . . . . . . . . . .  10

V.  Step 5 — Make Electrical Connections

 . . . . . . . . .  11

INSTALLATION OPTIONS

 . . . . . . . . . . . . . . . . . . . . . . . .19-22

I. Fresh Air Intake

 . . . . . . . . . . . . . . . . . . . . . . . . . . . .  19

II.  Conditioned Air Supply to Adjacent Room

. . . . . .  19

III.  Room Controller Configuration Setup

. . . . . . . . . .  21

IV.  Louver Mode Selection

 . . . . . . . . . . . . . . . . . . . . . .  21

V.  Main Board Configuration

. . . . . . . . . . . . . . . . . . . .  21

START-UP

 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22,23

SERVICE AND MAINTENANCE

. . . . . . . . . . . . . . . . . . . . . .  23

TROUBLESHOOTING

. . . . . . . . . . . . . . . . . . . . . . . . . . . . 23,24

SAFETY CONSIDERATIONS

Installing and servicing air-conditioning equipment can be

hazardous due to system pressure and electrical components.

Only trained and qualified service personnel should install or

service air-conditioning equipment.
Untrained personnel can perform basic maintenance, such as

cleaning and replacing filters. All other operations should be

performed by trained service personnel. When working on air

conditioning equipment, observe safety precautions in litera-

ture, tags, and labels attached to unit.
Follow all safety codes. Wear safety glasses and work gloves.

Use quenching cloth for brazing operations. Have fire extin-

guisher available. Read these instructions 

thoroughly

. Con-

sult local building codes and the National Electrical Code

(NEC) for special installation requirements.

GENERAL 

These instructions cover the installation, start-up and service

of in-ceiling cassette fan coil units. See Fig. 1.
The following accessories can be used with 619FNF, FNQ

units. See the price pages for part numbers and additional

information for the following accessories:
• photocatalytic and electrostatic filter with mount

• air supply outlet obstruction kit

• wired room controller

• room controller wiring kit for multiple units

• zone manager kit for multiple units

• zone manager

• infrared remote kit

WARNING: 

 

Before installing or servicing system,

always turn off main power to system. There may be

more than one disconnect switch. Turn off accessory

heater power if applicable. Electrical shock can cause

serious personal injury.

CAUTION: 

 

This system uses Puron® refrigerant

(R-410A), which has higher pressures than R-22 and

other refrigerants. No other refrigerant may be used in

this system. All equipment must be designed to handle

R-410A refrigerant. If unsure about equipment, consult

the equipment manufacturer.

CAUTION: 

 

Do not operate the unit without a filter

or with the grille removed. Damage to the unit or per-

sonal injury may result.

Fig. 1 — 619FNF, FNQ Unit

Summary of Contents for 619FNF

Page 1: ...llow all safety codes Wear safety glasses and work gloves Use quenching cloth for brazing operations Have fire extin guisher available Read these instructions thoroughly Con sult local building codes...

Page 2: ...charged or under charged from the factory NAME SPECIFICATIONS Connection Pipe 619FNF018 024 FNQ01824 5 8 in Mixed Phase 3 8 in Liquid 619FNF FNQ03036 3 4 in Mixed Phase 3 8 in Liquid Wall Sleeve Wall...

Page 3: ...4 8 7 3 15 16 100 5 29 32 150 1 10 5 8 575 0 2 1 4 3 4 0 8 2 1 1 5 2 2 4 6 5 5 8 2 0 1 4 3 5 1 6 3 4 6 1 1 1 1 2 13 64 56 2 52 1 10 5 8 575 8 5 1 2 3 7 7 0 3 8 9 0 5 1 2 3 9 2 5 2 3 14 70 8 9 2 4 3 1...

Page 4: ...18 18 18 Circuits 5 6 10 10 FILTERS Cleanable Quantity Size in 1 17 x 16 AIRSWEEP Horizontal Auto Preset OPERATING LIMITS Cooling Min Max 55 F 125 F CONTROLS Integrated Microprocessor Remote Controlle...

Page 5: ...4 6 4 6 No of Rows 2 2 3 3 Fins in 18 18 18 18 Circuits 6 6 10 10 FILTERS Cleanable Quantity Size in 1 24 x 235 16 AIRSWEEP Horizontal Auto Preset OPERATING LIMITS Heating Min Max 15 F 75 F Cooling M...

Page 6: ...ith the unit may be used as a guide Depending on the type of ceiling the hangers can be fixed as shown in Fig 5 Once the threaded hangers have been positioned do not tighten the nuts Insert the washer...

Page 7: ...the frame in to position See Fig 12 Ensure that the frame is not distorted by excessive tighten ing that it is aligned with the false ceiling and that there is a seal between the air inlet and outlet...

Page 8: ...e or other tem perature radiating object that may cause a false reading Do not locate close to or in direct airflow of a heating or cooling supply Do not locate in areas with poor circulation such as...

Page 9: ...extend through the hole in the mounting base Adjust the length and routing of each wire to reach the proper terminal in the connector block on the mounting base with 1 4 in of extra wire strip only 1...

Page 10: ...able 5 Refer to Fig 20 Table 5 Tightening Torque B Piping Connection to the Unit Use two wrenches to tighten all connections Once all connections have been completed check for leaks using soapy water...

Page 11: ...e unit shall be fuse or equipped with a breaker Table 6B 619FNQ Fan Coil Electrical Data LEGEND Permissible limits of the voltage range at which unit will operate satisfactorily NOTE In compliance wit...

Page 12: ...Room Controller Connections Ground Connection Outdoor Unit Connections Low Voltage High Voltage Power Connections Fig 21 619FNF Unit Matched to 538ENF Outdoor Unit Wiring Connection Cooling Only Syst...

Page 13: ...ltage High Voltage Room Controller Connections Outdoor Unit Connections Power Connections Ground Connection Fig 22 619FNQ Unit Matched to 538ENF Outdoor Unit Wiring Connection Cooling with Electric He...

Page 14: ...14 Low Voltage High Voltage Room Controller Connections Ground Connection Outdoor Unit Connections Power Connections Fig 23 619FNQ Unit Matched to 538QNF Outdoor Unit Wiring Connection Heat Pump Syste...

Page 15: ...ch OFM Outdoor Fan Motor OL Overload S Emergency TB Terminal Block TM Sensor TRAN Transformer Terminal Marked Terminal Unmarked Splice Terminal Block Factory Wiring Field Control Wiring Field Power Wi...

Page 16: ...Louver Motor LMS Louver Micro Switch OFM Outdoor Fan Motor OL Overload S Emergency ST Safety Thermostat TB Terminal Block TM Sensor TRAN Transformer Terminal Marked Terminal Unmarked Splice Terminal...

Page 17: ...est Point LLPS Liquid Low Pressure Switch LM Louver Motor LMS Louver Micro Switch OAS Outdoor Air Sensor OFM Outdoor Fan Motor OFR Outdoor Fan Relay OL Overload RVS Reversing Valve Solenoid S Emergenc...

Page 18: ...ctric heater Transformer Holes for fixing panel in position Emergency push button Fan connector LED RECEIVER connector Float connector Pump connector Louver connector CP CG CA CV CLR INTERNAL CONTROL...

Page 19: ...orrugated aluminum externally covered with anti condensate material fiberglass from 1 4 in to 1 in thickness 5 Use Fig 31 to determine the allowable static pres sure loss for the ductwork airflow The...

Page 20: ...m C 2 3 4 70 mm 3 15 16 100 mm 4 14 105 1 93 49 8 50 216 Note Dimensions in are in mm Fig 30 Installation Options NOTE Dimensions in are in mm Supply air duct to adjacent room Airflow cfm e r u s s e...

Page 21: ...C Temperatures will be displayed in degrees Celsius F Temperatures will be displayed in degrees Fahrenheit IV LOUVER MODE SELECTION To enter louver mode selection ensure the room controller is on and...

Page 22: ...unit is configured as a Heat Pump unit the louver will operate according to user selected position If user selected louver is Auto louver operates according to auto heat or cool louver based on operat...

Page 23: ...shes at intervals of 0 5 sec onds The fault code is deduced from the number of times the green LED flashes blocking unit operation Between one flash cycle and the next one a pause of 5 seconds elapses...

Page 24: ...right 2006 Bryant Heating Cooling Systems Printed in U S A CATALOG NO 02 619F0001 II Green LED Red LED Yellow LED Remote control signal receiver Emergency Button Fig 35 Warning Lamps and Emergency But...

Reviews: