background image

—23—

4. Ensure that the filters and return air grilles have

been installed and that the discharge louvers are

correctly positioned.

SERVICE AND MAINTENANCE

Remove unit grille, filter, and condensate pan for cleaning,

lubricating, or replacing parts.

I. MINIMUM MAINTENANCE

1. Check, clean, or replace air filter each month or as

required.

2. Check cooling coil, drain pan, condensate trap, and

condensate drain pan each cooling season for cleanli-

ness. Clean as necessary.

3. Check fan motor and wheel for cleanliness each heat-

ing and cooling season.

4. Check electrical connections for tightness and con-

trols for proper operation each heating and cooling

season. Service as necessary.

II. SERVICE

A. To Clean or Replace Air Filters

1. Place a plastic sheet on the floor to catch any water

that may spill from drain pan.

2. Slide filter out.
3. Vacuum clean or wash filter with soapy water. Rinse

and let air dry. If filter needs replacing, filters are

available from the local dealer.

B. To Clean or Replace Drain Pan

1. Place a plastic sheet on the floor to catch any water

that may spill from drain pan.

2. Remove the air intake and distribution assembly.

Remove the condensate water in the drain pan by

pulling out the rubber drain plug and letting water

drain into a 3-gallon bucket.

3. Remove screws holding the drain pan. Carefully hold

the drain pan to remove it from the assembly.

4. Reinstall the drain pan using the appropriate num-

ber of screws. Center and align the metal fan inlet

orifice with the fan. Ensure the fan spins freely.

TROUBLESHOOTING

See Table 9 and Fig. 35 for troubleshooting information.

I. FAULT CODE

Once a failure occurs with the indoor unit in operation, the

green LED on the indoor unit flashes at intervals of 0.5 sec-

onds. The fault code is deduced from the number of times the

green LED flashes, blocking unit operation. Between one

flash cycle and the next one, a pause of 5 seconds elapses.

See Fig. 35.

Table 9 — Fault Codes

*When code is enabled.

A. Using the Emergency Button

The Emergency button is for use by a qualified service tech-

nician only. The Emergency button is for use when the room

controller is inoperative. Use a screwdriver to press the

emergency button through the metal protection grille. See

Fig. 35.
Emergency Operation
When the unit is in the OFF mode and the Emergency but-

ton is pressed for 5 seconds, the unit will operate as follows:
• Automatic  mode

• temperature preset to 72 F

• automatic fan speed

• louvers set automatically according to the operating mode

• Timer function is cancelled

• buzzer beeps
When the unit is ON and the Emergency button is pressed

for 5 seconds, the unit will operate as follows:
• the unit is turned off

• buzzer beeps
When a signal is received by the remote control, the unit

operates accordingly.

CAUTION: 

 

Never operate unit without a filter or

with grille removed. Damage to the unit or personal

injury may result.

CAUTION: 

 

To avoid personal injury or damage to

unit, do not service until all power sources are shut

down, locked out, and tagged out. Failure to do so could

result in personal injury or unit damage.

CAUTION: 

 

If air filter is not replaced in the unit,

dust and dirt gather in air conditioner and operation

becomes impaired.

CAUTION: 

Do not use a screw driver to pry drain

pan out of assembly. It could damage the pan. 

CODE

DESCRIPTION

2

Condensate discharge pump

3

Room air sensor fault

4

Indoor unit coil sensor fault

6*

Filter dirty

7

Outdoor unit failure

10

EEPROM corrupt

11

Card serial number damaged

12

Address or zone incomplete

13

Gas flow distributor corrupt

14

Outdoor air thermistor fault

Fig. 34 — Inserting Water into Drain Pan

Summary of Contents for 619FNF

Page 1: ...llow all safety codes Wear safety glasses and work gloves Use quenching cloth for brazing operations Have fire extin guisher available Read these instructions thoroughly Con sult local building codes...

Page 2: ...charged or under charged from the factory NAME SPECIFICATIONS Connection Pipe 619FNF018 024 FNQ01824 5 8 in Mixed Phase 3 8 in Liquid 619FNF FNQ03036 3 4 in Mixed Phase 3 8 in Liquid Wall Sleeve Wall...

Page 3: ...4 8 7 3 15 16 100 5 29 32 150 1 10 5 8 575 0 2 1 4 3 4 0 8 2 1 1 5 2 2 4 6 5 5 8 2 0 1 4 3 5 1 6 3 4 6 1 1 1 1 2 13 64 56 2 52 1 10 5 8 575 8 5 1 2 3 7 7 0 3 8 9 0 5 1 2 3 9 2 5 2 3 14 70 8 9 2 4 3 1...

Page 4: ...18 18 18 Circuits 5 6 10 10 FILTERS Cleanable Quantity Size in 1 17 x 16 AIRSWEEP Horizontal Auto Preset OPERATING LIMITS Cooling Min Max 55 F 125 F CONTROLS Integrated Microprocessor Remote Controlle...

Page 5: ...4 6 4 6 No of Rows 2 2 3 3 Fins in 18 18 18 18 Circuits 6 6 10 10 FILTERS Cleanable Quantity Size in 1 24 x 235 16 AIRSWEEP Horizontal Auto Preset OPERATING LIMITS Heating Min Max 15 F 75 F Cooling M...

Page 6: ...ith the unit may be used as a guide Depending on the type of ceiling the hangers can be fixed as shown in Fig 5 Once the threaded hangers have been positioned do not tighten the nuts Insert the washer...

Page 7: ...the frame in to position See Fig 12 Ensure that the frame is not distorted by excessive tighten ing that it is aligned with the false ceiling and that there is a seal between the air inlet and outlet...

Page 8: ...e or other tem perature radiating object that may cause a false reading Do not locate close to or in direct airflow of a heating or cooling supply Do not locate in areas with poor circulation such as...

Page 9: ...extend through the hole in the mounting base Adjust the length and routing of each wire to reach the proper terminal in the connector block on the mounting base with 1 4 in of extra wire strip only 1...

Page 10: ...able 5 Refer to Fig 20 Table 5 Tightening Torque B Piping Connection to the Unit Use two wrenches to tighten all connections Once all connections have been completed check for leaks using soapy water...

Page 11: ...e unit shall be fuse or equipped with a breaker Table 6B 619FNQ Fan Coil Electrical Data LEGEND Permissible limits of the voltage range at which unit will operate satisfactorily NOTE In compliance wit...

Page 12: ...Room Controller Connections Ground Connection Outdoor Unit Connections Low Voltage High Voltage Power Connections Fig 21 619FNF Unit Matched to 538ENF Outdoor Unit Wiring Connection Cooling Only Syst...

Page 13: ...ltage High Voltage Room Controller Connections Outdoor Unit Connections Power Connections Ground Connection Fig 22 619FNQ Unit Matched to 538ENF Outdoor Unit Wiring Connection Cooling with Electric He...

Page 14: ...14 Low Voltage High Voltage Room Controller Connections Ground Connection Outdoor Unit Connections Power Connections Fig 23 619FNQ Unit Matched to 538QNF Outdoor Unit Wiring Connection Heat Pump Syste...

Page 15: ...ch OFM Outdoor Fan Motor OL Overload S Emergency TB Terminal Block TM Sensor TRAN Transformer Terminal Marked Terminal Unmarked Splice Terminal Block Factory Wiring Field Control Wiring Field Power Wi...

Page 16: ...Louver Motor LMS Louver Micro Switch OFM Outdoor Fan Motor OL Overload S Emergency ST Safety Thermostat TB Terminal Block TM Sensor TRAN Transformer Terminal Marked Terminal Unmarked Splice Terminal...

Page 17: ...est Point LLPS Liquid Low Pressure Switch LM Louver Motor LMS Louver Micro Switch OAS Outdoor Air Sensor OFM Outdoor Fan Motor OFR Outdoor Fan Relay OL Overload RVS Reversing Valve Solenoid S Emergenc...

Page 18: ...ctric heater Transformer Holes for fixing panel in position Emergency push button Fan connector LED RECEIVER connector Float connector Pump connector Louver connector CP CG CA CV CLR INTERNAL CONTROL...

Page 19: ...orrugated aluminum externally covered with anti condensate material fiberglass from 1 4 in to 1 in thickness 5 Use Fig 31 to determine the allowable static pres sure loss for the ductwork airflow The...

Page 20: ...m C 2 3 4 70 mm 3 15 16 100 mm 4 14 105 1 93 49 8 50 216 Note Dimensions in are in mm Fig 30 Installation Options NOTE Dimensions in are in mm Supply air duct to adjacent room Airflow cfm e r u s s e...

Page 21: ...C Temperatures will be displayed in degrees Celsius F Temperatures will be displayed in degrees Fahrenheit IV LOUVER MODE SELECTION To enter louver mode selection ensure the room controller is on and...

Page 22: ...unit is configured as a Heat Pump unit the louver will operate according to user selected position If user selected louver is Auto louver operates according to auto heat or cool louver based on operat...

Page 23: ...shes at intervals of 0 5 sec onds The fault code is deduced from the number of times the green LED flashes blocking unit operation Between one flash cycle and the next one a pause of 5 seconds elapses...

Page 24: ...right 2006 Bryant Heating Cooling Systems Printed in U S A CATALOG NO 02 619F0001 II Green LED Red LED Yellow LED Remote control signal receiver Emergency Button Fig 35 Warning Lamps and Emergency But...

Reviews: