background image

800SA/801SA: Installation, Start–Up, Operating and Service and Maintenance Instructions

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

27

Adjustments

Furnace gas input rate on rating plate is for installations at altitudes up to

2000  ft.  (610  M).  Furnace  input  rate  must  be  within  +/-2  percent  of

furnace rating plate input.

1. Determine the correct gas input rate. 

The  input  rating  for  altitudes  above  2,000  ft.  (610  M)  must  be

reduced by 4 percent for each 1,000 ft. (305 M) above sea level. For

installations below 2000 ft. (610 M), refer to the unit rating plate.

For installations above 2000 ft. (610 M), multiply the input on the

rating  plate  by  the  de-rate  multiplier  in 

Table 10

  for  the  correct

input rate. 

A93059

Fig. 45 – Orifice Hole

 

* Derate multiplier factors are based on midpoint altitude for altitude range.

2. Determine the correct orifice and manifold pressure adjustment.

There are two different orifice and manifold adjustment tables. All

models in all positions, except Low NOx models in downflow or

horizontal positions, use 

Table 11

 (22,000 Btuh/Burner).

Low NOx models in the downflow or horizontal positions must use

Table 12

 (21,000 Btuh/Burner). See input listed on rating plate. 

a. Obtain average yearly gas heat value (at installed altitude) from 

local gas supplier.

b. Obtain average yearly gas specific gravity from local gas 

supplier.

c. Find installation altitude in 

Table 11

 or 

Table 12

.

d. Find closest natural gas heat value and specific gravity in 

Table 11

 or 

Table 12

.

e. Follow heat value and specific gravity lines to point of 

intersection to find orifice size and manifold pressure settings for 

proper operation.

f. Check and verify burner orifice size in furnace. NEVER 

ASSUME ORIFICE SIZE. ALWAYS CHECK AND VERIFY.

NOTE: 

If orifice hole appears damaged or it is suspected to have been

redrilled, check  orifice  hole  with  a  numbered drill  bit  of  correct  size.

Never redrill an orifice. A burr-free and squarely aligned orifice hole is

essential for proper flame characteristics. 

g. Replace orifice with correct size if required by 

Table 10

Table 11

Table 12

 and 

Table 13

. Use only factory-supplied 

orifices. See EXAMPLE 1.

3. Adjust manifold pressure to obtain correct input rate. 

a. Turn gas valve ON/OFF switch to OFF.

b. Remove manifold pressure tap plug from gas valve (see 

Fig. 21

).

c. Connect a water column manometer or similar device to 

manifold pressure tap.

d. Turn gas valve ON/OFF switch to ON.

e. Manually close blower door switch.

f. Set thermostat to call for heat.

g. Remove regulator seal cap and turn regulator adjusting screw 

counterclockwise (out) to decrease input rate of clockwise (in) to 

increase input rate.

NOTE: 

DO NOT set manifold pressure less than 3.2-In. W.C. or more

than  3.8-In. W.C.  for  natural  gas  at  sea  level.  If  manifold  pressure  is

outside  this  range,  change  main  burner  orifices.  Refer  to 

Table 10

,

Table 11

, 

Table 12

 and 

Table 13

.

h. Install regulator seal cap.

i. Leave manometer or similar device connected and proceed to 

Step 4. 

WARNING

!

FIRE HAZARD

Failure  to  follow  this  warning  could  result  in  injury,  death  and/or

property damage.

DO  NOT  bottom  out  gas  valve  regulator  adjusting  screw.  This  can

result in unregulated manifold pressure and result in excess overfire and

heat exchanger failures.

CAUTION

!

FURNACE DAMAGE HAZARD

Failure to follow this caution may result in reduced furnace life.

DO NOT redrill orifices. Improper drilling (burrs, out-of-round holes,

etc.)  can  cause  excessive  burner  noise  and  misdirection  of  burner

flames.  This  can  result  in  flame  impingement  of  heat  exchangers,

causing failures (see 

Fig. 45

).

Table 10 – Altitude Derate Multiplier for U.S.A.

ALTITUDE 

(FT. / M) 

PERCENT 

OF

DERATE 

DERATE

MULTIPLIER 

FACTOR* 

0–2000 (0-610)

1.00 

2001–3000 (610-914)

8–12 

0.90 

3001–4000 (914-1219)

12–16 

0.86 

4001–5000 (1219-1524)

16–20 

0.82 

5001–6000 (1524-1829)

20–24 

0.78 

6001–7000 (1829-2134)

24–28 

0.74 

7001–8000 (2134-2438)

28–32 

0.70 

8001–9000 (2438-2743)

32–36 

0.66 

9001–10,000 (2743-3048) 

36–40 

0.62 

BURNER 

ORIFICE

EXAMPLE 1: (0 to 2000 ft. (0 to 610 M) altitude) 

For 22,000 Btuh per burner application use 

Table 11

Heating value = 1000 Btuh/cu ft. 
Specific gravity = 0.62 
Therefore: Orifice No. 43* 
Manifold pressure: 3.7-In. W.C. 
*Furnace is shipped with No. 43 orifices. 

In this example all main burner orifices are the correct 
size and do not need to be changed to obtain proper input rate. 

WARNING

!

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury or death.

Disconnect  115-v  electrical  power  and  install  lockout  tag  before

changing speed tap.

Summary of Contents for 800SA

Page 1: ...r Hour 21 EXTERIOR MASONRY CHIMNEY FAN NAT INSTALLATIONS WITH TYPE B DOUBLE WALL VENT CONNECTORS NFPA AGA 22 VENTING NOTES FOR Fig 31 Fig 43 25 START UP ADJUSTMENT AND SAFETY CHECK 25 GENERAL 25 Table...

Page 2: ...residential garage must be installed as specified in the warning box in the Location section 9 The furnace may be used for construction heat provided that the furnace installation and operation compli...

Page 3: ...tion in a Garage CODES AND STANDARDS Follow all national and local codes and standards in addition to these instructions The installation must comply with regulations of the serving gas supplier local...

Page 4: ...tic discharge can affect electronic components Follow the Electrostatic Discharge Precautions Procedure listed below during furnace installation and servicing to protect the furnace electronic control...

Page 5: ...a volume of at least 50 cubic feet per 1 000 Btuh input rating for all gas appliances installed in the space Spaces having less than 50 cubic feet per 1 000 Btuh require the OUTDOOR COMBUSTION AIR MET...

Page 6: ...ns from the current edition of National Fuel Gas Code ANSI Z223 1 NFPA 54 1 For other than fan assisted appliances such as a draft hood equipped water heater A04002 1 SQ IN PER 4000 BTUH DUCTS TO OUTD...

Page 7: ...and dilution of flue gases However in buildings with unusually tight construction additional air MUST be provided using the methods described in the Outdoor Combustion Air Method section 4 Unusually...

Page 8: ...Table 3 and Fig 9 3 Construct plenum to dimensions specified see Table 3 and Fig 9 4 If downflow subbase KGASB is used install as shown see Table 10 If Coil Assembly Part No CNPV CNRV CAP and CNR or...

Page 9: ...red 11 13 16 284 19 483 13 7 16 341 20 5 8 600 Downflow Applications on Combustible Flooring with Cased Coil subbase not required 12 5 16 319 19 483 13 5 16 338 20 508 17 1 2 445 Upflow Applications o...

Page 10: ...revent screws from pulling out use 2 8 x 3 4 in 19 mm screws into the side and 2 8 x 3 4 in 19 mm screws in the bottom of the furnace casing for each strap see Fig 14 and Fig 15 If the screws are atta...

Page 11: ...0 ft 3 M of main duct to the first branch take off may require internal acoustical lining As an alternative fibrous ductwork may be used if constructed and installed in accordance with the latest edit...

Page 12: ...915 915 825 785 740 700 48070E21 Gray Cooling Do not use for heating 1735 1685 1640 1595 1545 1495 1450 1405 1360 1310 Yellow Alt Cooling or alt Heating 1480 1435 1395 1340 1290 1240 1190 1135 1085 10...

Page 13: ...side inlets a combination of 1 side and the bottom or the bottom only will ensure adequate return air openings for airflow requirements above 1800 CFM Fig 17 Dimensional Drawing 60110E24 Gray Cooling...

Page 14: ...of Massachusetts 1 Gas supply connections MUST be performed by a licensed plumber or gas fitter 2 When flexible connectors are used the maximum length shall not exceed 36 inches 915 mm 3 When lever h...

Page 15: ...NPT plugged tapping accessible for test gauge connection MUST be installed immediately upstream of gas supply connection to furnace and downstream of manual equipment shutoff valve WARNING FIRE OR EXP...

Page 16: ...electrical circuit with a properly sized fuse or circuit breaker for this furnace See Table 7 for wire size and fuse specifications A readily accessible means of electrical disconnect must be located...

Page 17: ...WITCH WHT BLK WHT BLK NOTES Connect Y terminal in furnace as shown for proper blower operation Some thermostats require a C terminal connection as shown If any of the original wire as supplied must be...

Page 18: ...es into electrical box 9 Remove cover from furnace J Box 10 Route field ground wire through holes in electrical box and casing and into furnace J Box 11 Reattach furnace J Box to furnace casing with s...

Page 19: ...board thermostat strip The HUM terminal is energized when the pressure switch closes during a call for heat see Fig 28 NOTE DO NOT connect furnace control HUM terminal to HUM humidifier terminal on Th...

Page 20: ...or condensation in the venting system These furnaces are approved for common venting and multistory venting with other fan assisted or draft hood equipped appliances in accordance with the NFGC the lo...

Page 21: ...appliances connected to the venting system are not in operation 1 Seal any unused openings in venting system 2 Inspect the venting system for proper size and horizontal pitch as required in the curre...

Page 22: ...on in the furnace and or venting system Derating is permitted only for altitudes above 2000 ft 610 M 3 Adjust the air temperature rise to the midpoint of the rise range or slightly above Low air tempe...

Page 23: ...the furnace being vented Follow all manufacturer s installation requirements for venting and termination included with the listed mechanical venter Caution For the following applications use the mini...

Page 24: ...lication Vent Elbow Left A03208 Fig 36 Upflow Application Vent Elbow Up A03212 Fig 37 Downflow Application Vent Elbow Up then Right A03218 Fig 38 Horizontal Right Application Vent Elbow Right SEE NOTE...

Page 25: ...Data Sheet for accessory listing 6 Factory authorized accessory Downflow Vent Guard Kit required in downflow installations with lower vent configuration See Product Data Sheet for accessory listing 7...

Page 26: ...ure will not operate if any thermostat signal is present at the control 4 Component test sequence is as follows see service label attached to furnace or Fig 44 a LED will display previous status code...

Page 27: ...fices See EXAMPLE 1 3 Adjust manifold pressure to obtain correct input rate a Turn gas valve ON OFF switch to OFF b Remove manifold pressure tap plug from gas valve see Fig 21 c Connect a water column...

Page 28: ...When thermometer readings stabilize subtract return air temperature from supply air temperature to determine air temperature rise NOTE If the temperature rise is outside this range first check 1 Gas i...

Page 29: ...Ammeter WARNING FURNACE OVERHEATING HAZARD Failure to follow this caution may result in reduced furnace life Recheck temperature rise It must be within limits specified on the rating plate Recommende...

Page 30: ...urn thermostat below room temperature or from HEAT to OFF and turn 115v power OFF then back ON 3 Check Pressure Switch This control proves operation of the draft inducer blower a Turn off 115 v power...

Page 31: ...S switch until LED goes out then reconnect it NOTE If wire to LS or DSS is disconnected longer than 4 sec main blower starts and status code is overwritten with a limit circuit 33 code 2 When above it...

Page 32: ...wheel as follows 1 Turn off electrical supply to furnace 2 Remove outer door 3 For downflow or horizontal furnaces having vent pipes within the furnace that pass in front of the blower access door a...

Page 33: ...eavy build up of soot and carbon indicates that a problem exists which needs to be corrected such as improper adjustment of manifold pressure insufficient or poor quality combustion air incorrect size...

Page 34: ...TV sealant G E 162 P771 9003 is available through RCD in 3 oz tubes 12 Apply new sealant to flange of collector box and attach to cell panel using existing screws making sure all screws are secure 13...

Page 35: ...zing the humidifier terminal HUM The inducer motor IDM will remain energized for a 5 second post purge period The blower motor BLWM and air cleaner terminal EAC 1 will remain energized for 90 120 150...

Page 36: ...tart Up Operating and Service and Maintenance Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 36 WIRING DIAGRAM A19...

Page 37: ...f s u o i v e r p o n s a w r a t s l l i w r e c u d n i e h T e c n e u q e s t s e t t n e n o p m o c f e i r b a h g u o r h t o g l l i w n u r d n a t w o l b I S H e h T t s e t t n e n o p m...

Page 38: ...estricted duct system Loose blower wheel Defective switch or connections Defective blower motor or capacitor Inadequate combustion air supply flame rollout switch open Restricted vent Proper vent sizi...

Page 39: ...ealer listing by brand name or contact BRYANT HEATING COOLING SYSTEMS Consumer Relations Department P O Box 4952 Syracuse New York 13221 4952 1 800 428 4326 Have available the model number series numb...

Page 40: ...46231 Edition Date 03 20 Catalog No II800SA 04 Replaces II800SA 03 800SA 801SA Installation Start Up Operating and Service and Maintenance Instructions Manufacturer reserves the right to change at any...

Reviews: