Fig. 2 -- Clearances to Combustibles

A02055

Fig. 3 -- Return Air Temperature

CODES AND STANDARDS

Follow all national and local codes and standards in addition to

these instructions. The installation must comply with regulations
of the serving gas supplier, local building, heating, plumbing, and

other codes. In absence of local codes, the installation must

comply with the national codes listed below and all authorities
having jurisdiction.
In the United States, follow all codes and standards for the
following:

Safety

S

USA: Current edition of National Fuel Gas Code
(NFGC) NFPA 54/ANSI Z223.1 and the Installation

Standards, Warm Air Heating and Air Conditioning
Systems ANSI/NFPA 90B

General Installation

S

Current edition of the NFGC and the NFPA 90B. For
copies, contact the National Fire Protection Association
Inc., Batterymarch Park, Quincy, MA 02269;

(www.NFPA.org) or for only the NFGC, contact the
American Gas Association, 400 N. Capitol Street,

N.W., Washington, DC 20001 (www.AGA.org).

Combustion and Ventilation Air

S

Current edition of NFGC NFPA54/ANSI Z223.1 Sec-
tion 9.3, Air for Combustion and Ventilation.

Duct Systems

S

Air Conditioning Contractors Association (ACCA)
Manual D, Sheet Metal and Air Conditioning Contract-
ors National Association (SMACNA), or American

Society of Heating, Refrigeration, and Air Condition-
ing Engineers (ASHRAE) 2005 Fundamentals Hand-

book Chapter 35 or 2004 HVAC Systems and Equip-
ment Handbook Chapters 9 and 16.

Acoustical Lining and Fibrous Glass Duct

S

Current edition of SMACNA and NFPA 90B as tested
by UL Standard 181 for Class I Rigid Air Ducts

Gas Piping and Gas Pipe Pressure Testing

S

Current edition of NFGC NFPA54/ANSI Z223.1;
chapters 5, 6, 7, and 8 and National Plumbing Codes.

Electrical Connections

S

Current edition of National Electrical Code (NEC) NF-
PA 70.

Venting

S

Current edition of NFGC NFPA 54 / ANSI Z223.1;
Chapters 12 and 13.

ELECTROSTATIC DISCHARGE (ESD)

PRECAUTIONS PROCEDURE

FURNACE RELIABILITY HAZARD

Improper installation or service of furnace may cause

premature furnace component failure.
Electrostatic discharge can affect electronic components.

Follow the Electrostatic Discharge Precautions Procedure

listed below during furnace installation and servicing to

protect the furnace electronic control. Precautions will

prevent electrostatic discharges from personnel and hand

tools which are held during the procedure. These

precautions will help to avoid exposing the control to

electrostatic discharge by putting the furnace, the control,

and the person at the same electrostatic potential.

CAUTION

!

1. Disconnect all power to the furnace. Multiple disconnects

maybe required. DO NOT TOUCH THE CONTROL OR
ANY WIRE CONNECTED TO THE CONTROL PRIOR

TO DISCHARGING YOUR BODY’S ELECTROSTAT-
IC CHARGE TO GROUND.

2. Firmly touch the clean, unpainted, metal surface of the

furnace chassis which is close to the control. Tools held in
a person’s hand during grounding will be satisfactorily

discharged.

3. After touching the chassis, you may proceed to service the

control or connecting wires as long as you do nothing to

recharge your body with static electricity (for example;
DO NOT move or shuffle your feet, do not touch

ungrounded objects, etc).

4. If you touch ungrounded objects (and recharge your body

with static electricity), firmly touch a clean, unpainted

metal surface of the furnace again before touching control
or wires.

5. Use this procedure for installed and uninstalled

(ungrounded) furnaces.

6. Before removing a new control from its container,

discharge your body’s electrostatic charge to ground to
protect the control from damage. If the control is to be

installed in a furnace, follow items 1 through 4 before
bringing the control or yourself in contact with the

furnace. Put all used and new controls into containers
before touching ungrounded objects.

7. An ESD service kit (available from commercial sources)

may also be used to prevent ESD damage.

Summary of Contents for 830CA

Page 1: ...REQUIREMENTS 23 SIDEWALL VENTING 23 START UP ADJUSTMENT AND SAFETY CHECK 25 GENERAL 25 START UP PROCEDURES 25 ADJUSTMENTS 25 FURNACE SETUP SWITCHES 26 AIR DELIVERY CFM 30 COOLING OR CONTINUOUS AIRFLO...

Page 2: ...ir for Combustion and Ventilation section 4 Combustion products must be discharged outdoors Connect this furnace to an approved vent system only as specified in the Venting section of these instructio...

Page 3: ...M VENT CONNECTION IN MM SIZE SHIP WT LB KG ACCESSORY FILTER MEDIA CABINET SIZE IN MM 36040C17 17 1 2 445 15 7 8 403 11 9 16 294 16 406 4 102 119 54 16 406 48060C17 17 1 2 445 15 7 8 403 11 9 16 294 16...

Page 4: ...Z223 1 Chapters 12 and 13 ELECTROSTATIC DISCHARGE ESD PRECAUTIONS PROCEDURE FURNACE RELIABILITY HAZARD Improper installation or service of furnace may cause premature furnace component failure Electro...

Page 5: ...include fluoride chloride bromide and iodide These elements can corrode heat exchangers and shorten furnace life Air contaminants are found in aerosol sprays detergents bleaches cleaning solvents sal...

Page 6: ...40 25807 7 178 27 17391 6 152 20 12904 5 127 100 000 50 32258 8 203 34 21739 7 178 25 16130 6 152 EXAMPLE Determining Free Area FURNACE WATER HEATER TOTAL INPUT 100 000 30 000 130 000 divided by 4 000...

Page 7: ...NFILTRATION METHOD Outdoor Combustion Air Method 1 Provide the space with sufficient air for proper combustion ventilation and dilution of flue gases using permanent horizontal or vertical duct s or o...

Page 8: ...ements apply to the Standard Method and to the Known Air Infiltration Rate Method 1 Adjoining rooms can be considered part of a space if a There are no closeable doors between rooms b Combining spaces...

Page 9: ...leveling legs 1 Position furnace on its back Locate and drill a hole in each bottom corner of furnace See Fig 10 2 For each leg install nut on bolt and then install bolt and nut in hole Install flat...

Page 10: ...nd RH side The furnace can be hung from floor joists rafters or trusses or installed on a non combustible platform blocks bricks or pad Table 4 Opening Dimensions In mm FURNACE CASING WIDTH APPLICATIO...

Page 11: ...r rack for assembly and installation options AIR DUCTS General Requirements The duct system should be designed and sized according to accepted national standards such as those published by Air Conditi...

Page 12: ...r other accessories All accessories MUST be connected to duct external to furnace casing A190346 Fig 14 Duct Flanges 1 4 6mm THREADED ROD 4 REQ SECURE ANGLE IRON TO BOTTOM OF FURNACE WITH 3 8 x3 4 19m...

Page 13: ...NOT cut into casing sides left or right Side opening is permitted for only upflow and most horizontal furnaces See Fig 19 Bypass humidifier connections should be made at ductwork or coil casing sides...

Page 14: ...hen flexible connectors are used the maximum length shall not exceed 36 inches 915 mm 3 When lever handle type manual equipment shutoff valves are used they shall be T handle valves 4 The use of coppe...

Page 15: ...nit Amps Unit Ampacity Minimum Wire Size AWG Maximum Wire Length ft Maximum Fuse or CKT BKR Amps Maximum Minimum 036040 115 60 1 127 104 11 4 12 6 14 29 15 048060 115 60 1 127 104 11 4 12 6 14 29 15 0...

Page 16: ...ithin furnace away from sharp edges rotating parts and hot surfaces ELECTRICAL CONNECTION TO J BOX Electrical Box on Furnace Casing Side FIRE OR ELECTRICAL SHOCK HAZARD Failure to follow this warning...

Page 17: ...1 4 in female quick connect terminals to the two male 1 4 in quick connect terminals on the control board marked EAC 1 and EAC 2 The terminals are rated for 115VAC 1 0 amps maximum and are energized d...

Page 18: ...CTORY 115 VOLT WIRING Connect Y Y2 terminal as shown for proper operation Some thermostats require a C terminal connection as shown If any of the original wire as supplied must be replaced use same ty...

Page 19: ...sition for heat pump installations 7 Dip switch No 2 on Thermidistat should be set in OFF position for single speed compressor operation This is factory default 8 Dip switch No 2 on Thermidistat shoul...

Page 20: ...local building codes and furnace and vent manufacturers instructions These furnaces are design certified as Category I furnaces in accordance with current edition of ANSI Z21 47 CSA 2 3 and operate w...

Page 21: ...CHIMNEY IN2 MM2 12 7741 19 12258 28 18064 38 24516 6 1 8 74 119 178 257 8 2 4 80 130 193 279 10 3 0 84 138 207 299 15 4 5 NR 152 233 334 20 6 0 NR NR 250 368 30 9 1 NR NR NR 404 APPLIANCE APPLICATION...

Page 22: ...22 A180242 Fig 31 Chimney Inspection Chart...

Page 23: ...termine the correct location of the knockout to be re moved 4 Use a hammer and screwdriver to strike a sharp blow be tween the tie points and work the slug back and forth until the slug breaks free CU...

Page 24: ...ove 3 Side outlet vent for upflow and downflow installations must use Type B vent immediately after exiting the furnace except when factory authorized Downflow Vent Guard Kit is used in the downflow p...

Page 25: ...not operate if any thermostat signal is present at the control Refer to service label attached to furnace or See Fig 38 Component test sequence is as follows a Inducer motor turns on at 50 duty cycle...

Page 26: ...26 Table 10 Furnace Setup Switch Description A190351...

Page 27: ...27 A190348 Fig 38 Service Label...

Page 28: ...p NOTE If orifice hole appears damaged or it is suspected to have been redrilled check orifice hole with a numbered drill bit of correct size Never redrill an orifice A burr free and properly sized or...

Page 29: ...onnect an amp meter as shown in Fig 41 across the R and W subbase terminals or R and W wires at wall R Y W G 10 TURNS THERMOSTAT SUBBASE TERMINALS WITH THERMOSTAT REMOVED ANITICIPATOR CLOCK ETC MUST B...

Page 30: ...5 1565 1525 1490 1455 1415 1375 1335 1295 CF Switches SW3 3 SW3 2 SW3 1 Cont Fan Default OFF OFF OFF 530 545 545 535 505 495 485 See Note 4 Continuous Fan Airflow SW3 OFF OFF ON 530 545 545 535 505 49...

Page 31: ...F OFF OFF 1785 1800 1805 1830 1830 1845 1855 1860 1850 1840 Cooling Airflow SW2 Low Cooling Airflow SW3 OFF OFF ON 635 630 See Note 4 OFF ON OFF 785 820 865 See Note 4 OFF ON ON 1040 1045 1070 1085 11...

Page 32: ...n furnace wiring diagram Fig 42 Cooling A C or Continuous Fan Airflow Selection Chart Check Safety Controls 1 Check Main Limit Switch es This control shuts off combustion control system and en ergizes...

Page 33: ...6 94 38 76 192 38 95 189 474 96 38 75 188 39 92 185 462 98 37 74 184 40 90 180 450 100 36 72 180 41 88 176 439 102 35 71 178 42 86 172 429 104 35 69 173 43 84 167 419 106 34 68 170 44 82 164 409 108 3...

Page 34: ...8 1 8 1 9 2 0 1646 925 1 8 1 8 1 8 1 9 950 1 8 1 8 1 8 1 8 975 1 8 1 8 1 8 1 8 1000 1 8 1 8 1 8 1 8 Table 16 Gas Valve Outlet Pressure for Gas Heat Values at Altitude 80 000 Tabulated Data Based on 8...

Page 35: ...TH HAZARD Failure to follow this warning could result in personal injury death and or property damage The ability to properly perform maintenance on this equipment requires certain knowledge mechanica...

Page 36: ...stall blower access door and replace outer door or refer to the SERVICE label on the front of the blower access door for more informa tion Component Self Test Component Test can ONLY be initiated by p...

Page 37: ...ving filter access door 2 Remove filter cabinet door 3 Slide filter out of cabinet 4 If equipped with permanent washable 3 4 in 19 mm fil ter clean filter by spraying cold tap water through filter in...

Page 38: ...n outdoor circuit breaker on after completing cooling cycle FLAME SENSOR CLEANING AND SERVICING IGNITOR Cleaning Flame Sensor The following items must be performed by a qualified service technician If...

Page 39: ...as follows NOTE The materials needed in item 9 can usually be purchased at local hardware stores a Remove metal screw fitting from wire brush to allow in sertion into cable b Insert the twisted wire...

Page 40: ...od If the transducer fails to reach target pressure the inducer motor IDM will remain running until tar get pressure is maintained After the transducer maintains pressure target the furnace control CP...

Page 41: ...he blower motor BLWM is operating When the thermostat is satisfied the R to G and Y circuit are opened The outdoor unit stops and the furnace blower BLWM and electronic air cleaner terminal EAC 1 will...

Page 42: ...cedure enough you will eventually shift the continuous blower airflow to the lowest CF selection as shown in Fig 42 The selection can be changed as many times as desired and is stored in the memory to...

Page 43: ...43 A190249 Fig 45 Wiring Diagram...

Page 44: ...gs for dealer listing by brand name or contact BRYANT HEATING COOLING SYSTEMS Consumer Relations Department P O Box 4952 Syracuse New York 13221 4952 1 800 428 4326 Have available the model number ser...

Reviews: