37
Table 12 – Electrical Data
UNIT SIZE
VOLTS-
HERTZ-
PHASE
OPERATING VOLTAGE
RANGE*
MAXIMUM
UNIT
AMPS
UNIT
AMPACITY#
MINIMUM
WIRE
SIZE
AWG
MAXIMUM
WIRE
LENGTH
FT (M)
}
MAXIMUM
FUSE OR CKT
BKR
AMPS
{
Maximum*
Minimum*
30040
115-60-1
127
104
5.2
7.5
14
49 (14.9)
15
36040
115-60-1
127
104
7.4
10.3
14
36 (11.0)
15
36060
115-60-1
127
104
5.3
7.6
14
48 (14.6)
15
48060
115-60-1
127
104
8.6
11.7
14
31 (9.4)
15
48080
115-60-1
127
104
8.1
11.1
14
33 (10.1)
15
60080
115-60-1
127
104
8.6
11.7
14
31 (9.4)
15
48100
115-60-1
127
104
7.3
10.1
14
36 (11.0)
15
60100
115-60-1
127
104
11.9
15.8
12
36 (11.0)
20
60120
115-60-1
127
104
11.9
15.8
12
36 (11.0)
20
* Permissible limits of the voltage range at which the unit operates satisfactorily.
# Unit ampacity = 125 percent of largest operating component's full load amps plus 100 percent of all other potential operating components' (EAC, humidifier,
etc.) full load amps.
{
Time-delay type is recommended.
}
Length shown is as measured one way along wire path between furnace and service panel for maximum 2 percent voltage drop.
A12226
Fig. 36
−
Installing J
−
Box (When Used)
COPPER
WIRE ONLY
ELECTRIC
DISCONNECT
SWITCH
ALUMINUM
WIRE
GROUND
NEUTRAL
LINE VOLTAGE
A11146
Fig. 37
−
Field
−
Supplied External Electrical Box on Furnace
Casing
912S