background image

44

The Maximum Vent Length for the vent and combustion air pipe
(when used) is determined from the Maximum Equivalent Vent

Length in Table 17 minus the number of fittings multiplied by the
deduction for each type of fitting used from Table 18.

OPTIONAL CONFIGURATION FOR COMBUSTION

AIR INLET PIPE

In applications where there is a risk of excessive moisture

entering the combustion air inlet pipe, a moisture trap may be

added to the inlet pipe to help prevent moisture from entering

the furnace from the combustion air inlet pipe. See Fig. 59.
When sizing venting systems, the equivalent length of the

optional moisture trap (15 feet/5 M) must be taken into

account.

NOTICE

Recommended Combustion Air Inlet Moisture Trap

Recommended to prevent moisture from trickling into the furnace

vestibule, a trap can be installed in the intake air pipe near the
furnace. To prevent moisture, connecting a drain line to the trap is

recommended as trace amounts of moisture will evaporate into the
intake air stream. If the combustion air inlet is located near a

moisture exhaust duct, or there are other concerns of excessive
moisture being drawn into the combustion air inlet, it is

encouraged to connect a drain line to the trap.
The trap can be constructed from a running tee of the same
diameter of the intake air pipe with

EITHER

a removable cap

attached to a 6-inch long pipe connected to the tee or the External
Vent Trap Kit to help prevent contaminants from entering the

furnace. See Fig. 59.
The External Vent Trap Kit accessory may be used as a trap for the
combustion air inlet pipe if a large amount of moisture must be

removed. The drain line may be connected to the same drain as the
furnace condensate and the evaporator coil condensate line

ONLY

if the inlet air trap drain and the evaporator coil drain empty into an

open segment of pipe above the drain. See Fig.14. When using
the External Vent Trap Kit, refer to those instructions for proper

drain connections.
The tee may also be connected to the intake air pipe on the side of

the casing. See Fig. 59.
In any configuration, it will be necessary to add the equivalent

length of the tee (15 feet/5 M) to the Total Equivalent Vent Length

of the venting system.

ADDITIONAL INFORMATION FOR

POLYPROPYLENE VENTING SYSTEMS

Polypropylene venting systems include flexible vent pipe.

These flexible vent pipes have a different equivalent vent

length than straight sections of PVC/ABS DWV vent pipe. Be

sure to make the appropriate deductions from the Maximum

Equivalent Vent Length (MEVL), or additions to the Total

Equivalent Vent Length (TEVL), when applying flexible vent

pipes

in

polypropylene

venting

systems.

See

the

polypropylene vent system manufacturer’s installation

instructions for details.
When using metric-sized venting systems, use these

equivalencies for obtaining the proper MEVL from the Tables:

Use 2” Vent Tables for 60 mm (o.d.) vent systems

Use 3” Vent Tables for 80 mm (o.d.) vent systems

Use 4” Vent Tables for 100 mm (o.d.) vent systems

NOTICE

The measured length of pipe used in a single or 2--pipe termination
is included in the total vent length. Include deductions from the

Maximum Equivalent Vent Length (MEVL) contained in the
Venting Tables for elbows and flexible vent pipe.

Factory

accessory concentric vent terminations or pipe lengths and elbows

used for “standard” vent terminations do not require a deduction
from the Maximum Equivalent Vent Length. See vent termination

figures associated with Table 17. Include a deduction for a Tee
when used for Alberta and Saskatchewan terminations.

NOTE

: Polypropylene venting systems MAY require additional

deductions from the MEVL, or additions to the TEVL, for vent
terminations and flexible pipe sections. See the polypropylene
venting system manufacturer’s instructions for details on
equivalent lengths of vent terminations and flexible vent pipes,
and for calculating total vent lengths.
To calculate the Total Equivalent Vent Length (TEVL) of the

venting system:

1. Measure the individual distance from the furnace to the ter-

mination for each pipe.

2. Count the number of elbows for each pipe.
3. For each pipe, multiply the number of elbows by the equiv-

alent length for the type of elbow used. Record the equiva-
lent length of all the elbows for each pipe.

4. If a Tee is used on the termination (Alberta and

Saskatchewan, when required) record the equivalent length

of the Tee used.

5. Calculate Total Equivalent Vent Length by adding the

equivalent lengths of the fittings to the lengths of the indi-

vidual vent and combustion air pipes.

6. When using polypropylene venting systems with flexible

vent pipes, perform adjustments for the equivalent length of
the flexible vent pipe to the calculated total equivalent
venting system length. See the polypropylene vent system

manufacturer’s instructions for details.

7. Select a diameter of vent pipe from Table 17 and note the

Maximum Equivalent Vent Length (MEVL) shown for that
application for that specific furnace input size. Compare the
Total Equivalent Vent Length (TEVL) to the MEVL:

8. If the Total Equivalent Vent Length is

shorter

than the

Maximum Equivalent Vent Length for the diameter of pipe

chosen, then that diameter of pipe selected may be used.

9. If the Total Vent Length is

longer

than the Maximum

Equivalent Vent Length for the diameter of pipe chosen,
that diameter pipe MAY NOT be used for venting the fur-
nace. Try the next larger diameter pipe

.

NOTE

: If the calculated Total Equivalent Vent Lengths results in

different diameter pipes for the vent and combustion air, select the
larger diameter for both pipes.

NOTE

: If the Maximum Vent Length for diameter of the pipe

selected is longer than the measured length and the equivalent
length of all the fittings and terminations (TEVL), recalculate
Total Equivalent Vent Length using the next smaller diameter. If
the Maximum Equivalent Vent Length is still longer than the
longer TEVL of the vent pipe or combustion air pipe, then that
diameter of pipe selected may be used.
When installing vent systems pipe lengths of 10 ft. (3 M) or less,

use the smallest allowable pipe diameter. Using a pipe size greater
than required for short venting systems may result in loss of

efficiency, incomplete combustion, flame disturbance, or flame
sense lockout.
For vent systems longer than 10 ft. (3 M), any larger diameter vent

pipe shown in Table 17

FOR THAT SIZE FURNACE

may be

used.

912S

Summary of Contents for 912SB

Page 1: ...ahridirectory org Portions of the text and tables are reprinted from current edition of NFPA 54 ANSI Z223 1E with permission of National Fire Protection Association Quincy MA 02269 and American Gas As...

Page 2: ...aust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF...

Page 3: ...ng on heating equipment observe precautions in literature on tags and on labels attached to or shipped with furnace and other safety precautions that may apply These instructions cover minimum require...

Page 4: ...used if the heating load is 20 000 BTU or lower Use Air Conditioning Contractors of America Manual J and S American Society of Heating Refrigerating and Air Conditioning Engineers or other approved e...

Page 5: ...recharge your body with static electricity firmly touch a clean unpainted metal surface of the furnace again before touching control or wires 5 Use this procedure for installed and uninstalled ungrou...

Page 6: ...1 2 319 12 9 16 322 7 1 8 181 121 0 55 0 36060 125 0 56 8 36040 17 1 2 445 15 7 8 403 16 406 8 3 4 222 132 0 60 0 48060 142 0 64 5 48080 151 0 68 6 60080 21 533 19 3 8 492 19 1 2 495 10 1 2 267 158 5...

Page 7: ...IS LOCATED TO THE LEFT OF THE BURNER SECTION AND CONDITIONED AIR IS DISCHARGED TO THE RIGHT A12181 Fig 2 Multipoise Orientations 60 80 27 C 16 C SUPPLY AIR SEE PRODUCT DATA FOR ACCESSORY CONDENSATE T...

Page 8: ...ution system Refer to Air Ducts section S be provided ample space for servicing and cleaning Always comply with minimum fire protection clearances shown in Table 2 or on the furnace clearance to combu...

Page 9: ...e combustion ventilation and dilution air must be provided in accordance with S U S A Installations Section 9 3 of the current edition of NFPA 54 ANSI Z223 1 Air for Combustion and Ventilation and app...

Page 10: ...oms can be considered part of a space if a There are no closeable doors between rooms b Combining spaces on same floor level Each opening shall havefreeareaofat least1 in 2 1 000Btuh 2 000mm2 kW of th...

Page 11: ...tical Ducts or Openings 60 000 40 000 100 000 divided by 3 000 33 3 Sq In for each Single Duct or Opening 80 000 30 000 110 000 divided by 2 000 55 0 Sq In for each two Horizontal Ducts Table 4 Minimu...

Page 12: ...B C D D E F G L12F012 Fig 6 Air for Combustion Ventilation and Dilution for Outdoors Minimum opening size is 100 sq in 64516 sq mm with minimum dimensions of 3 in 76mm Minimum of 3 in 76mm when type...

Page 13: ...g 10 and 11 A field supplied accessory Horizontal Installation Kit trap grommet is required for all direct vent horizontal installations only The kit contains a rubber casing grommet designed to seal...

Page 14: ...n ports of the collector box Connect relief tube to port on collector box Rotate elbow to desired position and tighten clamp to 15 lb in Slide tube in stand offs to adjust length Connect the new press...

Page 15: ...on Attach condensate trap with screw to collector box Slide relief tube in stand offs to adjust length Vent elbow shown in alternate orientation Tighten clamp on inlet to vent elbow 15 lb in Align tra...

Page 16: ...osition and torque clamp on inlet 15 lb in Slide relief tube in stand offs to adjust length Attach condensate trap with screw to collector box Align trap over middle and right hand port on collector b...

Page 17: ...e not hard piped together and b There is an air gap at the point where the two drain lines meet or c All condensate piping is at least 3 4 in PVC and there is a relief tee at the top of condensate dra...

Page 18: ...in trap grommet is ONLY REQUIRED FOR DIRECT VENT APPLICATIONS It is NOT required for applications using single pipe or ventilated combustion air venting NOTICE TIP FROM CONTRACTORS When installing the...

Page 19: ...e DIRECTION OF AIRFLOW Condensing Furnace Evaporator Coil Blower 3 4 PVC 1 2 3 4 1 2 CPVC or larger Positive pressure Pressure lower than areas with Negative pressure 3 4 PVC DIRECTION OF AIRFLOW 1 2...

Page 20: ...sing Furnace Evaporator Coil Blower 3 4 PVC 3 4 1 2 CPVC or larger Positive pressure Pressure lower than areas with Negative pressure 3 4 PVC DIRECTION OF AIRFLOW 3 4 3 4 3 4 3 4 Open standpipe Option...

Page 21: ...PIPE ORIENTATION FOR CONDENSATE DISCHARGE A170128 Fig 18 Drain Trap Connection and Routing Appearance may vary INSTALLATION Cabinet air leakage is less than 2 at 1 0 in W C Cabinet air leakage is less...

Page 22: ...KC 1 Determine application being installed from Table 8 2 Construct hole in floor per Table 8 and Fig 21 3 Construct plenum to dimensions specified in Table 8 and Fig 21 4 Install special base coil as...

Page 23: ...Bottom Return Air Inlet These furnaces are shipped with bottom closure panel installed in bottom return air opening Remove and discard this panel when bottom return air is used To remove bottom closur...

Page 24: ...05 13 0 07 18 0 08 21 0 13 32 0 29 72 0 20 49 1000 472 0 06 16 0 11 28 0 11 28 0 17 43 0 27 67 1200 566 0 07 18 0 15 37 0 14 36 0 22 56 1400 661 0 08 21 0 19 48 0 18 45 0 28 70 1600 755 0 09 23 0 24...

Page 25: ...E RETURN BOTTOM RETURN 14 3 16 360 16 x 25 x 3 4 406 x 635 x 19 14 x 25 x 3 4 356 x 635 x 19 Washable 17 1 2 445 16 x 25 x 3 4 406 x 635 x 19 16 x 25 x 3 4 406 x 635 x 19 Washable 21 533 16 x 25 x 3 4...

Page 26: ...2 419 19 5 8 498 Downflow applications on combustible flooring KGASB sub base required 15 1 8 384 19 483 16 3 4 425 20 5 8 600 Downflow Applications on Combustible Flooring with CNPV CNRV CAR or CAP C...

Page 27: ...CLOSURE Representative drawing only some models may vary in appearance A170123 Fig 23 Removing Bottom Closure Panel 2 Screws BOTTOM PLATE SCREWS 4 1 Lay furnace on the back or side 2 Remove the four 4...

Page 28: ...L MIN 1 4 IN 6 MM TO 1 2 IN 13 MM MAX A11237 Fig 26 Furnace Pitch Requirements ANY COMBINATION OF 1 2 OR 3 PERMITTED A11036 Fig 27 Upflow Return Air Configurations and Restrictions A11037 Fig 28 Downf...

Page 29: ...N OF 1 2 40 000 14 3 16 YES YES NO YES 17 1 2 YES YES NO YES 60 000 14 3 16 YES YES NO YES 17 1 2 YES NO NO YES 80 000 17 1 2 YES YES NO YES 21 YES YES NO YES 100 000 21 YES YES NO YES 120 000 24 1 2...

Page 30: ...Installation 2 IN 51 mm COMBUSTION AIR PIPE SEE VENTING SECTION Install 12 x 22 204 x 559 mm sheet metal in front of and above the burner compartment area The sheet metal MUST extend above the furnac...

Page 31: ...ections to furnace with code approved tape or duct sealer NOTE Flexible connections should be used between ductwork and furnace to prevent transmission of vibration Ductwork passing through unconditio...

Page 32: ...1135 Orange 3 5 397 1485 1470 1455 1430 1390 1340 1280 1205 1120 1035 Blue 3 2 5 426 1120 1110 1100 1090 1065 1035 990 935 870 805 Red 3 2 0 433 940 920 910 890 865 830 790 745 690 625 048100 SIDE BOT...

Page 33: ...e a new listed connector Do not use a connector which has previously served another gas appliance Black iron pipe shall be installed at the furnace gas control valve and extend a minimum of 2 in 51 mm...

Page 34: ...y death or property damage Before servicing disconnect all electrical power to furnace When servicing controls label all wires prior to disconnection Reconnect wires correctly Verify proper operation...

Page 35: ...ket and screws are shipped in the loose parts bag included with the furnace See Fig 36 for J Box mounting locations The J Box mounting bracket and green ground screw is used as a grounding point for a...

Page 36: ...drill into blower shelf of furnace to route control wiring Route any control or accessory wiring to the blower compartment through external knockouts on the casing WARNING 24 V Wiring Make field 24 v...

Page 37: ...36 11 0 15 60100 115 60 1 127 104 11 9 15 8 12 36 11 0 20 60120 115 60 1 127 104 11 9 15 8 12 36 11 0 20 Permissible limits of the voltage range at which the unit operates satisfactorily Unit ampacity...

Page 38: ...NECT CONDENSING UNIT TWO WIRE FURNACE C O N T R O L R G COM W C R G Y GND GND FIELD 24 V WIRING FIELD 115 208 230 460 V WIRING FACTORY 24 V WIRING FACTORY 115 V WIRING 208 230 OR 460 V THREE PHASE 208...

Page 39: ...EUTRAL CONNECTIONS COOL HEAT SPARE 1 SPARE 2 BLOWER SPEED SELECTION TERMINALS EAC 1 TERMINAL 115 VAC 1 0 AMP MAX 115 VAC L1 LINE VOLTAGE CONNECTION PL2 HOT SURFACE IGNITER INDUCER MOTOR CONNECTOR PL1...

Page 40: ...used with this system must be UL listed material Acceptability under Canadian standard CAN CSA B149 is dependent upon full compliance with all installation instructions Under this standard it is recom...

Page 41: ...for single pipe or ventilated combustion air option A furnace shall not be connected to a chimney flue serving a separate appliance designed to burn solid fuel Other gas appliances with their own ven...

Page 42: ...e to the outdoors is not required for a single pipe vent system A 12 in 304 mm long pipe with a 2 in 51 mm tight radius 90 degree elbow is required to be attached to the combustion air pipe adapter on...

Page 43: ...air pipe terminates in a well ventilated attic or crawl space Follow the clearances as shown in Fig 57 The combustion air pipe cannot terminate in attics or crawl spaces that use ventilation fans des...

Page 44: ...vent length Include deductions from the Maximum Equivalent Vent Length MEVL contained in the Venting Tables for elbows and flexible vent pipe Factory accessory concentric vent terminations or pipe le...

Page 45: ...e the vent elbow 1 Loosen the clamp on the inlet of the vent elbow attached to the inducer 2 Rotate the vent elbow to the required position There are rounded notches on the vent elbow to align it with...

Page 46: ...e supported to prevent sagging Space combustion air piping and vent piping hangers as shown in Table 14 Support pipes using perforated metal hanging strap or commercially available hangers or straps d...

Page 47: ...s shown in Fig 54 and all clearance shown in Fig 52 NOTE Follow the instructions of the vent terminal manufacturer These instructions are provided as a reference only Cut one 4 in 102 mm diameter hole...

Page 48: ...lame sense lockout Table 15 Approved Combustion Air and Vent Pipe Fitting and Cement Materials U S A Installations MATERIALS USA 1 All pipe fittings primers and solvents must conform to American Natio...

Page 49: ...gn Temp C Unit Size 40 000 BTUH 60 000 BTUH Uninsulated 3 8 in Insulation 1 2 in Insulation Uninsulated 3 8 in Insulation 1 2 in Insulation Pipe Dia mm 38 51 64 38 51 64 38 51 64 38 51 64 76 38 51 64...

Page 50: ...pped in the loose parts bag or available through Replacement Components required under 10 ft 3 M TEVL in all orientations Required for installations from 0 2000 0 to 610 M above sea level Failure to u...

Page 51: ...EVL 95 ft 29 M For 2 pipe from Table 17 Is TEVL less than MEVL YES Therefore 2 pipe MAY be used Example 2 A direct vent 60 000 BTUH furnace installed at 2100 ft 640M Venting system includes FOR EACH P...

Page 52: ...THE INDUCER FOR USAGE SEE MAXIMUM EQUIVALENT VENT LENGTH TABLE 10FT 3 1 M OF VENT OR LESS ONLY A170006 Fig 42 Inducer Vent Elbow Avoid short horizontal offsets with 90 deg Elbows Short offsets can be...

Page 53: ...items refer to the Inside Corner Clearance Table 3 ft 1 M to 6 ft 2 M Notes For this illustration Wall A is the wall adjacent to the wall the vent termination is located Wall B is the wall the vent t...

Page 54: ...he vent termination within a horizontal distance of 2 ft 61 cm from the centerline of the vent termination 6 ft 2 M Clearance to a ventilation exhaust including HRV ERV on either Wall A or Wall B 12 i...

Page 55: ...combustion air connection UPFLOW VERTICAL VENT A11310A Fig 46 Upflow Configurations Appearance may vary See Notes for Venting Options 1 2 3 4 5 6 7 5 Rotate vent elbow to required position DOWNFLOW L...

Page 56: ...T RIGHT VENT CONFIGURATION A11329A Fig 48 Horizontal Left Appearance may vary See Notes for Venting Options ALTERNATE COMBUSTION AIR CONNECTIONS HORIZONTAL RIGHT VERTICAL VENT CONFIGURATION A11337 Req...

Page 57: ...VENT PIPE FLUSH SHOWING COUPLING VENT PIPE FLUSH WITH ADAPTER VENT PIPE ADAPTER WITH GASKET INSTALLED ON FURNACE VENT PIPE IS CUT FLUSH WITH TOP OF ADAPTER PRIME AND CEMENT VENT PIPE TO ADAPTER ALLOW...

Page 58: ...a minimum of two sides beneath the floor See Note 4 Manufacturer s Recommendation See Notes 3 8 M Clearance to each side of the centerline extended above or below vent terminal of the furnace to a dr...

Page 59: ...y open on a minimum of two sides beneath the floor See Note 4 Manufacturer s Recommendation See Notes 3 8 M Clearance to each side of the centerline extended above or below vent terminal of the furnac...

Page 60: ...termination with 2 elbows preferred 12 in min 305 mm from overhang or roof Maintain 12 in 305mm minimum clearance above highest anticipated snow level or grade whichever is greater 6 in 152mm minimum...

Page 61: ...305 MM CLEARANCE ABOVE HIGHEST ANTICIPATED SNOW LEVEL OR GRADE WHICHEVER IS GREATER COMBUSTION AIR ELBOW PARALLEL TO WALL OVERHANG 12 IN 305 MM MIN GROUND LEVEL OR ANTICIPATED SNOW LEVEL EXHAUST CLEA...

Page 62: ...ipe hangar Ventilated Combustion Air intake termination in crawl space Ventilated Combustion Air intake pipe CRAWL SPACE ATTIC highest level of insulation A10497 Fig 57 Vent Terminations for Ventilate...

Page 63: ...some models may vary in appearance TO CODE APPROVED DRAIN OR CONDENSATE PUMP Tee Dry Well Cap water tight and removable Tee Dry Well Cap water tight and removable Tee Dry Well Cap water tight and rem...

Page 64: ...r operates HUM 24vac terminal is only energized when the draft inducer is energized in heating Prime Condensate Trap with Water CARBON MONOXIDE POISONING HAZARD Failure to follow these warnings could...

Page 65: ...e the factory orifice to a different orifice Tables have been provided in the furnace installation instructions to match the required orifice to the manifold pressure to the heat content and specific...

Page 66: ...If clocked rate does not match required input from Step 1 increase manifold pressure to increase input or decrease manifold pressure to decrease input Re peat steps b through e of Step 1 until correc...

Page 67: ...on thermostat per thermostat instruc tions and install on subbase or wall 5 Install blower access door Electronic thermostat Set cycle rate for 3 cycles per hr Check Safety Controls The flame sensor g...

Page 68: ...drawing only some models may vary in appearance A11153 Fig 60 Gas Valve without Tower Pressure Ports ON OFF SWITCH 1 8 NPT INLET PRESSURE TAP REGULATOR SEAL CAP REGULATOR ADJ UNDER CAP 1 2 NPT OUTLET...

Page 69: ...69 338309 201 Rev E A11602 Fig 64 Service Label Information 912S...

Page 70: ...23 157 313 783 66 54 109 273 24 150 300 750 68 53 106 265 25 144 288 720 70 51 103 257 26 138 277 692 72 50 100 250 27 133 267 667 74 48 97 243 28 129 257 643 76 47 95 237 29 124 248 621 78 46 92 231...

Page 71: ...3 3 7 43 3 8 42 3 2 850 44 3 8 43 3 5 43 3 6 43 3 7 875 44 3 6 44 3 7 43 3 4 43 3 5 4000 900 44 3 4 44 3 5 44 3 7 44 3 8 1219 925 44 3 2 44 3 4 44 3 5 44 3 6 950 44 3 1 44 3 2 44 3 3 44 3 4 750 42 3 3...

Page 72: ...2 3 2 725 44 3 8 43 3 4 43 3 5 43 3 6 750 44 3 5 44 3 7 44 3 8 43 3 4 8000 775 44 3 3 44 3 4 44 3 5 44 3 7 2438 800 44 3 1 44 3 2 44 3 3 44 3 4 825 44 2 9 44 3 0 44 3 1 44 3 2 625 42 3 4 42 3 5 42 3 6...

Page 73: ...he maximum make point of the switch is 0 83 in W C ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death There may be more than one electrical supply to the f...

Page 74: ...erify that there is nothing plugged into the PLT connector Note If there is a jumper connector plugged into PLT remove it and discard See Fig 40 3 Verify that the Blower Heat Off Delay jumpers are set...

Page 75: ...abinet 7 Replace filter cabinet door 8 Turn on electrical supply to furnace Blower Motor and Wheel Maintenance To ensure long life economy and high efficiency clean accumulated dirt and grease from bl...

Page 76: ...or damaging the mounting to the burner assembly ELECTRICAL SHOCK AND FIRE HAZARD Failure to follow this warning could result in personal injury death and or property damage Turn off the gas and electr...

Page 77: ...ontrol door Flushing Collector Box and Drainage System ELECTRICAL SHOCK AND FIRE HAZARD Failure to follow this warning could result in personal injury death and or property damage Turn off the gas and...

Page 78: ...intricate design A build up of soot and carbon indicates that a problem exists which needs to be corrected such as improper adjustment of manifold pressure insufficient or poor quality combustion air...

Page 79: ...MAGE HAZARD Failure to follow this caution may result in damage to the furnace and other property damage Do not use ethylene glycol automotive antifreeze coolant or equivalent Failure of plastic compo...

Page 80: ...GROMMET SCREW LOCATION BLOWER HSG ASSY BRACKET BRACKET ENGAGEMENT SEE DETAIL A CAPACITOR OR POWER CHOKE WHEN USED BRACKET SCREW GND BLOWER HSG ASSY MOTOR BLOWER WHEEL BLOWER CUTOFF BLOWER DETAIL A A11...

Page 81: ...y If the burner flame is proven the blower motor is energized on HEAT speed 25 sec after the gas valve GV is energized Simultaneously the electronic air cleaner terminal EAC 1 is energized and remains...

Page 82: ...ious fault or status code 11 1 short and 1 long flash if there was no previous fault After the control repeats the code 4 times the control will go through a brief component test sequence The inducer...

Page 83: ...sequence 3 more times before lockout 14 occurs If flame signal is lost during the blower on delay period blower will come on for the selected blower off delay Check the following items first before pr...

Page 84: ...84 A12420 Fig 73 Wiring Diagram 912S...

Page 85: ...g by brand name or contact BRYANT HEATING COOLING SYSTEMS Consumer Relations Department P O Box 4952 Syracuse New York 13221 4952 1 800 428 4326 Have available the model number series number and seria...

Reviews: