SPECIFICATIONS

The furnace should be sized to provide 100 percent of the design
heating load requirement plus any margin that occurs because of

furnace model size capacity increments. None of the furnace
model sizes can be used if the heating load is 20,000 BTU or

lower. Use Air Conditioning Contractors of America (Manual J

and S); American Society of Heating, Refrigerating, and
Air-Conditioning Engineers; or other approved engineering

method to calculate heating load estimates and select the furnace.
Excessive oversizing of the furnace may cause the furnace and/or

vent to fail prematurely, customer discomfort and/or vent freezing.
Failure to follow these guidelines is considered faulty installation

and/or misapplication of the furnace; and resulting failure, damage,

or repairs may impact warranty coverage.

Heating Capacity and Efficiency

30040

36040

36060

48060

48080

60080

48100

60100

60120

Input

High
Heat

(BTUH)

40,000

40,000

60,000

60,000

80,000

80,000

100,000 100,000 120,000

Output

High
Heat

(BTUH)

37,000

37,000

56,000

56,000

75,000

75,000

93,000

93,000

112,000

Certified Temperature
Rise Range ºF (ºC)

High Heat

40 - 70

(22 - 39)

35 - 65

(19 - 36)

40 - 70

(22 - 39)

35 - 65

(19 - 36)

35 - 65

(19 - 36)

35 - 65

(19 - 36)

40 - 70

(22 - 39)

40 - 70

(22 - 39)

45 - 75

(25 - 42)

Airflow Capacity and Blower Data

30040

36040

36060

48060

48080

60080

48100

60100

60120

Rated External Static
Pressure (in. W.C.)

Heating

0.10

0.10

0.12

0.12

0.15

0.15

0.20

0.20

0.20

Cooling

0.5

0.5

0.5

0.5

0.5

0.5

0.5

0.5

0.5

Airflow Delivery
@ Rated ESP (CFM)

High Heat

910

980

910

980

1030

1115

1480

1550

2070

Cooling

970

1140

1155

1505

1555

1885

1490

1970

2050

Cooling Capacity (tons)

400 CFM/ton

2.5

2.5

2.5

3.5

4

4.5

3.5

5

5

350 CFM/ton

2.5

3

3

4

4.5

5.0

4.0

5.5

5.5

Direct-Drive Motor Type

Permanent Split Capacitor (PSC)

Direct-Drive Motor HP

0.3

0.5

0.3

0.5

0.5

0.75

0.5

0.75

0.75

Motor Full Load Amps

4.6

6.8

4.6

7.9

7.4

7.9

6.5

11.1

11.1

RPM Range

500 - 1150

Speed Selections

4

5

4

4

5

5

4

4

4

Blower Wheel Dia x Width

in.

11 x 7

11 x 8

11 x 7

11 x 8

11 x 8

11 x 10

11 x 10

11 x 10

11 x 11

Air Filtration System

Field Supplied

Filter Used for Certified Watt Data*

KGAWF**06UFR

Electrical Data

30040

36040

36060

48060

48080

60080

48100

60100

60120

Input Voltage

Volts-Hertz-Phase

115-60-1

Operating Voltage Range

Min-Max

104-127

Maximum Input Amps

Amps

5.2

7.4

5.3

8.6

8.1

8.6

7.3

11.9

11.9

Unit Ampacity

Amps

7.5

10.3

7.6

11.7

11.1

11.7

10.1

15.8

15.8

Minimum Wire Size

AWG

14

14

14

14

14

14

14

12

12

Maximum Wire Length
@ Minimum Wire Size

Feet

49

36

48

31

33

31

36

36

36

(M)

(14.9)

(11.0)

(14.6)

(9.4)

(10.1)

(9.4)

(11.0)

(11.0)

(11.0)

Maximum Fuse/Ckt Bkr
(Time-Delay Type Recommen-
ded)

Amps

15

15

15

15

15

15

15

20

20

Transformer Capacity (24vac output)

40 VA

External Control Power
Available

Heating

27.9 VA

Cooling

34.6 VA

Controls

30040

36040

36060

48060

48080

60080

48100

60100

60120

Gas Connection Size

1/2" - NPT

Burners (Monoport)

2

2

3

3

4

4

5

5

6

Gas Valve (Redundant)

Manufacturer

White Rodgers

Minimum Inlet Gas pressure (in. W.C.)

4.5

Maximum Inlet Gas pressure (in. W.C.)

13.6

Ignition Device

Silicon Nitride

Limit Control

195

180

220

190

185

195

220

220

165

Heating Blower Control (Heating Off-Delay)

Adjustable: 90, 120, 150, 180 seconds

Cooling Blower Control (Time Delay Relay)

90 seconds

Communication System

none

Thermostat Connections

Com 24V, R, W, G, Y

Accessory Connections

EAC (115vac); HUM (24vac)

* See Accessory List for part numbers available.

912SC

Summary of Contents for 912SC

Page 1: ...eight 35 cabinet short enough for taller coils but still allows enough room for service S Silicon Nitride Perfect Lightt Hot Surface Igniter S Aluminized steel primary heat exchanger S Stainless steel...

Page 2: ...product a design with more than ten years of field proven performance and success These innovations paired with the continuation of a crimped no weld seam create an efficient robust design for this e...

Page 3: ...970 2050 Cooling Capacity tons 400 CFM ton 2 5 2 5 2 5 3 5 4 4 5 3 5 5 5 350 CFM ton 2 5 3 3 4 4 5 5 0 4 0 5 5 5 5 Direct Drive Motor Type Permanent Split Capacitor PSC Direct Drive Motor HP 0 3 0 5 0...

Page 4: ...U 120 120 000 BTU 140 140 000 BTU Not all familes have these models 0 90 AFUE 2 92 AFUE 3 93 AFUE 5 95 AFUE 6 96 AFUE 7 97 AFUE Example of a Model Number A12374 FURNACE COMPONENTS RATING PLATE NOT SHO...

Page 5: ...Nat Gas LH32DB202 D D D D D D D D D Gas Orifice Kit 44 Nat Gas LH32DB200 D D D D D D D D D Gas Orifice Kit 45 Nat Gas LH32DB205 D D D D D D D D D Gas Orifice Kit 46 Nat Gas LH32DB208 D D D D D D D D...

Page 6: ...nge 3 5 397 1485 1470 1455 1430 1390 1340 1280 1205 1120 1035 Blue 3 2 5 426 1120 1110 1100 1090 1065 1035 990 935 870 805 Red 3 2 0 433 940 920 910 890 865 830 790 745 690 625 048100 SIDE BOTTOM Blac...

Page 7: ...Temp C Unit Size 40 000 BTUH 60 000 BTUH Uninsulated 3 8 in Insulation 1 2 in Insulation Uninsulated 3 8 in Insulation 1 2 in Insulation Pipe Dia mm 38 51 64 38 51 64 38 51 64 38 51 64 76 38 51 64 76...

Page 8: ...ize 40 000 Outlet choke required under 10 ft TEVL 60 000 80 000 100 000 120 000 140 000 Altitude meters Pipe Dia mm 38 51 64 38 5 64 76 38 51 64 76 102 51 64 76 102 64 76 102 64 76 102 0 610 6 26 57 6...

Page 9: ...eters of PVC ABS pipe VERIFY FROM VENT MANUFACTURER S INSTRUCTIONS Can this application use 60 mm O D polypropylene vent piping If not what size piping can be used Measure the required linear length o...

Page 10: ...PLY AIR A10490 MINIMUM CLEARANCES TO COMBUSTIBLE MATERIALS POSITION CLEARANCE Rear 0 0 mm Front Combustion air openings in furnace and in structure 1 in 25 mm Required for service 24 in 610 mm All Sid...

Page 11: ...1 2 YES YES NO YES 60 000 14 3 16 YES YES NO YES 17 1 2 YES NO NO YES 80 000 17 1 2 YES YES NO YES 21 YES YES NO YES 100 000 21 YES YES NO YES 120 000 24 1 2 YES YES NO YES INPUT CASING WIDTH INCHES...

Page 12: ...5 8 600 2 24 1 2 622 Furnace with or without Cased Coil Assembly or Coil Box 22 1 8 562 19 483 23 3 4 603 20 5 8 600 1 The plenum should be constructed 1 4 in 6 mm smaller in width and depth than the...

Page 13: ...SUPPLIED DISCONNECT AUXILIARY J BOX 24 V TERMINAL BLOCK THREE WIRE HEATING ONLY FIVE WIRE NOTE 1 NOTE 2 FIELD SUPPLIED DISCONNECT CONDENSING UNIT TWO WIRE FURNACE C O N T R O L R G COM W C R G Y GND...

Page 14: ...S IN INCH MM 22 2 7 8 7 8 22 2 POWER CONN AIR FLOW SEE NOTE 3 NOTES 1 Doors may vary by model 2 Minimum return air openings at furnace based on metal duct If flex duct is used see flex duct manufactur...

Page 15: ...accessory highly efficient Media Filter is available as an option _____________ Media Filter Casing Casing shall be of 030 in thickness minimum pre painted steel Draft Inducer Motor Draft inducer mot...

Page 16: ...e or change at any time specifications or designs without notice and without incurring obligations E2014 Bryant Heating Cooling Systems D 7310 W Morris St D Indianapolis IN 46231 Edition Date 10 14 Re...