912SE: Product Data

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

9

Maximum Equivalent Vent Length - Ft. (M) 

NOTE: 

Maximum Equivalent Vent Length (MEVL) includes standard and concentric vent termination and does NOT include elbows. Use Deductions

from Maximum Equivalent Vent Length to determine allowable vent length for each application.

1. 40K Inducer Outlet Restrictor disk (P/N 337683-401; 1.25-in. (32 mm) Dia.) shipped in the loose parts bag or available through Replacement Components required under 10-ft. (3 M)

TEVL in all orientations. Required for installations from 0 - 2000 ft. (0 to 610 M) above sea level. Failure to use an outlet restrictor may result in flame disturbances or flame sense

lock-out. 

2. 60K Inducer Outlet Restrictor disk (P/N 3337683-401; .25-in. (32 mm) Dia. available through Replacement Components) required for less than 5-ft. (1.5 M) TEVL in downflow and

horizontal orientations only.  Required for installations from 0 - 2000 ft. (0 to 610 M) above sea level.

3.

120K Inducer Outlet Restrictor disk (P/N 

337683-402

; 1.50-in. (38 mm) Dia. available through 

Replacement Components

) required for less than 5-ft. (1.5 M) TEVL in downflow and

horizontal orientations only. Required for installations from 0 - 2000 ft. (0 to 610 M) above sea level.

A13110

Deductions from Maximum Equivalent Vent Length - Ft. (M)

NOTE: 

1. Use only the smallest diameter pipe possible for venting. Over-sizing may cause flame disturbance or excessive vent terminal icing or freeze-up.

2. NA - Not allowed. Pressure switch will not close, or flame disturbance may result.
3. Vent sizing for Canadian installations over 4500 ft (1370 M) above sea level are subject to acceptance by local authorities having jurisdiction.
4. Size both the combustion air and vent pipe independently, then use the larger size for both pipes.
5. Assume the two 45

_

 elbows equal one 90

_

 elbow. Wide radius elbows are desirable and may be required in some cases.

6. Elbow and pipe sections within the furnace casing and at the vent termination should not be included in vent length or elbow count.
7. The minimum pipe length is 5 ft. (2 M) linear feet (meters) for all applications.
8. Use 3-in. (76 mm) diameter vent termination kit for installations requiring 4-in. (102 mm) diameter pipe

Unit Size 

40,000

 1

60,000 

2

80,000

100,000 

3

120,000

Altitude 

(feet)

Pipe Dia. 

(in)

½

2

½

½

2

½

3

½

2

½

3

4

2

½

3

4

½

3

4

0-2000

20

85

185

20

100 175 200

15

55

130 175 200

20

80

175 200

10

75

185

2001-3000

15

80

175

95

165 185

10

49

125 165 185

15

75

165 185

70

175

3001-4000

70

160

16

90

155 175

115 155 175

155 175

5

65

165

4001-4500

10

155

15

85

150 170

44

110 150 165

10

70

170

N/A

60

160

4501-5000

145

80

145 165

145 160

65

150 165

5001-6000

60

130

75

140 155

41

100 135 150

140 155

155

6001-7000

5

55

120

13

70

130 145

N/A

38

90

125 140

60

135 145

50

140

7001-8000

50

110

10

65

120 135

36

120 125

N/A

55

125 135

46

130

8001-9000

N/A

30

95

5

60

115 125

33

80

110 115

50

115 125

43

120

9001-10000

25

85

N/A

55

105 115

30

75

100 105

45

100 115

39

115

Maximum Equivalent Vent Length - Meters

Unit Size 

40,000 

1

60,000 

2

80,000

100,000 

3

120,000

Altitude 

(meters)

Pipe Dia. 

(mm)

38

51

64

38

51

64

76

38

51

64

76

102

51

64

76

102

64

76

102

0-610

6.0 25.9 56.3 6.0 30.4 53.3 60.9 4.5 16.7 39.6 53.3 60.9 6.0 24.3 53.3 60.9 3.0 22.8 56.3

611-914

4.5 24.3 53.3

28.9 50.2 56.3

3.0

14.9 38.1 50.2 56.3 4.5 22.8 50.2 56.3

21.3 53.3

915-1219

21.3

48.7 4.8 27.4 47.2 53.3

35.0 47.2 53.3

47.2 53.3 1.5 19.8 50.2

1220-1370

3.0

47.2

4.5

25.9 45.7 51.8

13.4 33.5 45.7 50.2

3.0

21.3

51.8

NA

18.2 48.7

1371-1524

44.1

24.3 44.1 50.2

44.1 48.7

19.8 45.7 50.2

1525-1829

18.2 39.6

22.8 42.6 47.2

12.4 30.4 41.1 45.7

42.6 47.2

47.2

1830-2134

1.5 16.7 36.5 3.9 21.3 39.6 44.1

NA

11.5 27.4 38.1 42.6

18.2 41.1 44.1

15.2 42.6

2135-2438

15.2 33.5 3.0 19.8 36.5 41.1

10.9

36.5 38.1

NA

16.7 38.1 41.1

14.0 39.6

2439-2743

N/A

9.1 28.9 1.5 18.2 35.0 38.1

10.0 24.3 33.5 35.0

15.2 35.0 38.1

13.1 36.5

2744-3048

7.6 25.9 NA 16.7 32.0 35.0

9.1 22.8 30.4 32.0

13.7 30.4 35.0

11.8 35.0

Pipe Diameter (in):

1-1/2

2

2-1/2

3

4

Mitered 90º Elbow

8

(2.4)

8

(2.4)

8

(2.4)

8

(2.4)

8

(2.4)

Medium Radius 90º Elbow

5

(1.5)

5

(1.5)

5

(1.5)

5

(1.5)

5

(1.5)

Long Radius 90º Elbow

3

(0.9)

3

(0.9)

3

(0.9)

3

(0.9)

3

(0.9)

Mitered 45º Elbow

4

(1.2)

4

(1.2)

4

(1.2)

4

(1.2)

4

(1.2)

Medium Radius 45º Elbow

2.5

(0.8)

2.5

(0.8)

2.5

(0.8)

2.5

(0.8)

2.5

(0.8)

Long Radius 45º Elbow

1.5

(0.5)

1.5

(0.5)

1.5

(0.5)

1.5

(0.5)

1.5

(0.5)

Tee

16

(4.9)

16

(4.9)

16

(4.9)

16

(4.9)

16

(4.9)

Concentric Vent Termination

NA

0

(0.0)

NA

0

(0.0)

NA

Standard Vent Termination

0

(0.0)

0

(0.0)

0

(0.0)

0

(0.0)

0

(0.0)

Long

Medium

Mitered

Concentric

Standard 2-in., 3-in., or 
optional 4-in. termination.

ELBOW CONFIGURATIONS

VENT TERMINAL CONFIGURATIONS

Summary of Contents for 912SE

Page 1: ...rimary heat exchanger Stainless steel condensing secondary heat exchanger INSTALLATION FLEXIBILITY 4 way multipoise design for upflow downflow or horizontal installation with unique vent elbow for 12 different venting options including optional venting through the cabinet downflow venting capability On board NFC antenna makes setup a tap away when using the Bryant service technician app Factory co...

Page 2: ...2 7 1 8 181 122 55 36040M17 17 1 2 445 15 7 8 403 16 406 8 3 4 222 123 56 36060M14 14 3 16 361 12 1 2 319 12 9 16 322 7 1 8 181 128 58 42060M17 17 1 2 445 15 7 8 403 16 406 8 3 4 222 136 62 48080M17 17 1 2 445 15 7 8 403 16 406 8 3 4 222 144 65 60080M21 21 533 19 3 8 492 19 1 2 495 10 1 2 267 153 69 60100M21 21 533 19 3 8 492 19 1 2 495 10 1 2 267 160 73 66100M21 21 533 19 3 8 492 19 1 2 495 10 1 ...

Page 3: ...esulting failure damage or repairs may impact warranty coverage 1 Heat Exchanger 9 2 Tier NOx 8 3 AFUE NOx 7 4 Heating Stages M 5 Major Series B 6 7 Cooling Capacity CFM 42 8 10 Heat Input 060 11 Motor Type C 12 13 Width 17 14 Voltage 1 phase A 15 Un used 16 Minor Series A A B C 14 14 2 17 17 5 21 21 0 24 24 5 C Constant Airflow Variable Speed VCA ECM V Variable Speed VCT PWM M Multi 18 Speed Cons...

Page 4: ...ency media filter Heating 730 760 1090 935 1320 1390 1620 1600 1830 Cooling 195 1090 140 1100 320 1285 200 1340 270 1790 275 1890 295 1870 295 2220 355 1930 Direct Drive Motor HP 1 2 1 2 1 2 1 2 3 4 3 4 3 4 1 3 4 Motor Full Load Amps 6 7 6 7 6 7 6 7 8 8 8 8 8 8 11 7 8 8 Heating Blower Control Htg OFF Delay Adjustable 90 120 factory set 150 180 seconds Cooling Blower Control Clg OFF Delay Adjustabl...

Page 5: ...10 15 1060 1025 995 965 930 895 865 835 800 765 16 1110 1080 1050 1020 985 955 925 895 865 835 17 1165 1135 1105 1080 1045 1020 990 960 930 900 18 Cooling 1225 1195 1165 1135 1100 1060 1020 985 945 910 36060M14 1 Cont Fan 585 515 445 380 320 260 195 145 2 630 570 510 440 380 330 270 205 160 3 695 635 580 520 460 405 355 300 240 180 4 735 685 630 575 510 460 410 360 310 250 5 780 725 675 620 565 51...

Page 6: ...95 18 Cooling 2050 2010 1970 1930 1890 1845 1795 1745 1690 1635 60100M21 1 Cont Fan 740 640 545 455 375 295 215 140 2 830 740 650 565 480 410 335 260 190 3 905 825 740 655 575 505 440 375 300 235 4 975 900 820 740 665 585 525 465 400 335 5 1045 975 900 820 750 675 605 550 490 430 6 1130 1065 995 925 850 780 715 650 595 540 7 1210 1145 1080 1015 945 880 815 750 690 640 8 1285 1225 1165 1105 1040 97...

Page 7: ...0 965 900 11 1585 1525 1470 1405 1340 1285 1230 1170 1105 1030 12 1665 1605 1550 1495 1435 1375 1320 1270 1210 1145 13 1750 1700 1645 1595 1535 1480 1425 1375 1320 1270 14 1835 1785 1740 1685 1630 1575 1525 1475 1430 1385 15 Heat 1880 1830 1780 1730 1680 1625 1575 1530 1480 1435 16 1920 1875 1825 1775 1730 1675 1625 1580 1535 1490 17 1995 1945 1900 1855 1810 1760 1715 1670 1625 1585 18 Cooling 211...

Page 8: ... 20 45 35 25 10 10 10 35 25 10 45 30 40 10 5 20 25 20 10 20 30 25 15 10 5 10 25 15 10 30 20 Winter Design Temp C Unit Size 40 000 BTUH Not all model families have this size 60 000 BTUH Uninsulated 3 8 in Insulation 1 2 in Insulation Uninsulated 3 8 in Insulation 1 2 in Insulation Pipe Dia mm 38 51 64 38 51 64 38 51 64 38 51 64 76 38 51 64 76 38 51 64 76 7 6 1 6 1 6 1 6 1 15 2 13 7 6 1 18 3 15 2 6 ...

Page 9: ...requiring 4 in 102 mm diameter pipe Unit Size 40 000 1 60 000 2 80 000 100 000 3 120 000 Altitude feet Pipe Dia in 1 2 2 1 2 2 3 1 2 2 3 4 2 2 3 4 2 3 4 0 2000 20 85 185 20 100 175 200 15 55 130 175 200 20 80 175 200 10 75 185 2001 3000 15 80 175 95 165 185 10 49 125 165 185 15 75 165 185 70 175 3001 4000 70 160 16 90 155 175 115 155 175 155 175 5 65 165 4001 4500 10 155 15 85 150 170 44 110 150 1...

Page 10: ...ong radius elbows use the highest number of elbows for either the vent or inlet pipe 3 x 3 ft 0 9 M 9 ft 2 7 M From Deductions from Maximum Equivalent Vent Length Ft M Table Add equiv length of 2 45º long radius elbows use the highest number of elbows for either the vent or inlet pipe 2 x 1 5 ft 0 5 M 3 ft 0 9 M From Deductions from Maximum Equivalent Vent Length Ft M Table Add equiv length of fac...

Page 11: ...ntric Vent Kit A93086 A concentric vent kit allows vent and combustion air pipes to terminate through a single exit in a roof or side wall One pipe runs inside the other allowing venting through the inner pipe and combustion air to be drawn in through the outer pipe 60 80 27 C 16 C SUPPLY AIR FIELD SUPPLIED 2 IN 51 mm DIA PVC PIPE FIELD SUPPLIED 2 IN 51 mm DIA MITERED RADIUS PVC 90 ELBOW 12 300 mm...

Page 12: ... X X KGARP0301B14 Return Air Base Upflow Applications 14 wide X X KGARP0301B17 Return Air Base Upflow Applications 17 1 2 wide X X KGADC0101BVC Vent Kit Through the Cabinet X X X X KGAVT0701CVT Vent Terminal Concentric 2 51 mm See Venting Tables KGAVT0801CVT Vent Terminal Concentric 3 76 mm KGAVT0101BRA Vent Terminal Bracket 2 51 mm KGAVT0201BRA Vent Terminal Bracket 3 76 mm KGAAC0101RVC Vent Kit ...

Page 13: ...C0101RVC Polypropylene Inlet Air Pipe Coupling X X X X X KGAHT0101CFP Freeze Protect Kit Condensate Drain Line Tape X X X X X KGAHT0201CFP Freeze Protect Kit Condensate Trap with Heat Pad X X X X X KGAAD0110PVC CPVC to PVC Drain Adapters 1 2 CPVC to 3 4 PVC X X X X X KGACK0101HCK Horizontal Trap Grommet Direct Vent All 2 Pipe Horizontal KGAET0201ETK External Trap Kit X X X X X KGASB0201ALL Downflo...

Page 14: ... 508 mm MERV11 FILXXCAR0120 X Cartridge Media Filter 24 610 mm MERV 8 FILXXCAR0024 X Cartridge Media Filter 24 610 mm MERV11 FILXXCAR0124 X EZ Flex Cabinet Side or Bottom 16 EZXCAB 0016 X X EZ Flex Cabinet Side or Bottom 20 EZXCAB 0020 X X EZ Flex Replacement Filters 16 MERV 10 EXPXXFIL0016 X X EZ Flex Replacement Filters 16 MERV 13 EXPXXFIL0316 X X EZ Flex Replacement Filters 20 MERV 10 EXPXXFIL0...

Reviews: