2
SPECIFICATIONS
Heating Capacity and Efficiency
030040
042060
048080
048100
066120
Input
High Heat
(BTUH)
40,000
60,000
80,000
100,000
120,000
Low Heat
(BTUH)
26,000
39,000
52,000
65,000
78,000
Output
High Heat
(BTUH)
39,000
58,000
78,000
98,000
117,000
Low Heat
(BTUH)
25,000
38,000
52,000
63,000
76,000
Efficiency
AFUE % (ICS)
96.2
96.2
96.2
96.2
96.2
Certified Temperature
Rise Range ºF (ºC)
High Heat
40 - 70
(21-38)
35 - 65
(19-36)
40 - 70
(21-38)
45 - 75
(25-41)
45 - 75
(25-41)
Low Heat
30 - 60
(17-33)
30 - 60
(17-33)
30 - 60
(17-33)
30 - 60
(17-33)
30 - 60
(17-33)
Airflow Capacity and Blower Data
030040
042060
048080
048100
066120
Certified External Static
Pressure (in. w.c.)
Heating
0.10
0.12
0.15
0.20
0.20
Cooling
0.5
0.5
0.5
0.5
0.5
Airflow Delivery
@ Rated ESP (CFM)
High Heat
695
1000
1360
1730
2125
Low Heat
585
780
1100
1380
1610
Cooling
925
1505
1610
1720
2055
Cooling Capacity (tons)
@ 400, 350 CFM/ton
400 CFM/ton
2
3.5
4
4
5
350 CFM/ton
2.5
4
4.5
5
6
Direct-Drive Motor Type
Electronically Commutated Motor (ECM)
Direct-Drive Motor HP
1/2
3/4
3/4
1
1
Motor Full Load Amps
6.8
8.4
8.4
10.9
10.9
RPM Range
600 - 1200
Speed Selections
5
Blower Wheel Dia x Width
in.
11x7
11x8
11x8
11x10
11 x 11
Air Filtration System
Factory Supplied Media Cabinet
Field Supplied Filter
Filter Used for Certified Watt Data
KGAWF1606UFR
KGAWF1306UFR
KGAWF1406UFR
KGAWF1506UFR
KGAWF1506UFR
Electrical Data
030040
042060
048080
048100
066120
Input Voltage
Volts-Hertz-Phase
115-60-1
Operating Voltage Range
Min-Max
104-127
Maximum Input Amps
Amps
8.2
9.8
9.8
12.3
12.3
Unit Ampacity
Amps
11.0
13.0
13.0
16.1
16.1
Minimum Wire Size
AWG
14
14
14
12
12
Maximum Wire Length
@ Minimum Wire Size
Feet
33
28
28
35
35
(M)
(10.1)
(8.5)
(8.5)
(10.7)
(10.7)
Maximum Fuse/Ckt Bkr
(Time-Delay Type Recommended)
Amps
15
15
15
20
20
Transformer Capacity (24vac output)
40 VA
External Control Power
Available
Heating
24.3 VA
Cooling
34.6 VA
Controls
030040
042060
048080
048100
066120
Gas Connection Size
1/2” - NPT
Burners (Monoport)
2
3
4
5
6
Gas Valve (Redundant)
Manufacturer
White Rogers™
Minimum Inlet Gas
pressure (in. W.C.)
4.5
Maximum Inlet Gas
pressure (in. W.C.)
13.6
Gas Conversion Kit - Natural to Propane
KGANP51012SP
Gas Conversion Kit - Propane to Natural
KGAPN43012SP
Manufactured (Mobile) Home Kit
not approved for MH use
Ignition Device
Silicon Nitride
Limit Control
165
180
170
160
160
Heating Blower Control (Heating Off-Delay)
Adjustable: 90, 120, 150, 180 seconds
Cooling Blower Control (Time Delay Relay)
90 seconds
Communication System
none
Thermostat Connections
W2, Y1, DHUM, G C W/W1, Y/Y2, R
Accessory Connections
EAC (115vac); HUM (24vac); 1-stg AC (via Y/Y2)