MAXIMUM EQUIVALENT VENT LENGTH -- FT. (M)

NOTE: Maximum Equivalent Vent Length (MEVL) does NOT include elbows or terminations. Use Table 2 - Deductions from

Maximum Equivalent Vent Length to determine allowable vent length for each application.

Table 1 – Maximum Equivalent Vent Length -- Ft. (M)

0 to 4500 Ft. (0 to 1370 M) Altitude

Altitude

FT (M)

Unit Size

BTU/Hr

DIRECT VENT (2-PIPE) AND NON---DIRECT VENT (1---PIPE)

Vent Pipe Diameter (in.)

1-1/2

2

2-1/2

3

4

0 to 2000

(0 to 610)

40,000*

2

50

(15.2)

210

(64.0)

250

(76.2)

NA

NA

60,000

30

(9.1)

135

(41.1)

235

(71.6)

265

(80.8)

NA

80,000

20

(6.1)

70

(21.3)

175

(53.3)

235

(71.6)

265

(80.8)

100,000

NA

25

(7.6)

110

(33.5)

235

(71.6)

265

(80.8)

120,000

NA

NA

15

(4.6)

100

(30.5)

250

(76.2)

2001 to 3000

(610 to 914)

40,000*

45

(13.7)

198

(60.4)

232

(70.7)

NA

NA

60,000

27

(8.2)

127

(38.7)

222

(67.7)

250

(76.2)

NA

80,000

17

(5.2)

64

(19.5)

165

(50.3)

222

(67.7)

249

(75.9)

100,000

NA

22

(6.7)

104

(31.7)

223

(68.0)

250

(76.2)

120,000

NA

NA

11

(3.4)

93

(28.3)

237

(72.2)

3001 to 4000

(914 to 1219)

40,000*

39

(11.9)

184

(56.1)

214

(65.2)

NA

NA

60,000

23

(7.0)

119

(36.3)

210

(64.0)

235

(71.6)

NA

80,000

15

(4.6)

59

(18.0)

155

(47.2)

210

(64.0)

232

(70.7)

100,000

NA

19

(5.8)

98

(29.9)

211

(64.3)

236

(71.9)

120,000

NA

NA

8

(2.4)

86

(26.2)

224

(68.3)

4001 to 4500

(1219 to

1370)

40,000*

36

(11.0)

177

(53.9)

205

(62.5)

NA

NA

60,000

21

(6.4)

115

(35.1)

204

(62.2)

228

(69.5)

NA

80,000

14

(4.3)

56

(17.1)

150

(45.7)

202

(61.6)

224

(68.3)

100,000

NA

17

(5.2)

94

(28.7)

205

(62.5)

229

(69.8)

120,000

NA

NA

NA

83

(25.3)

217

(66.1)

* Not all families have these models.

NOTE: See notes at end of venting tables.
NOTE: See Table 3 for altitudes over 4500 ft. (1370 M)

Table 2 – Deductions from Maximum Equivalent Vent Length -- Ft. (M)

Pipe Diameter (in):

1-1/2

2

2-1/2

3*

4*

Mitered 90º Elbow

8

(2.4)

8

(2.4)

8

(2.4)

NA

NA

NA

NA

Medium Radius 90º Elbow

5

(1.5)

5

(1.5)

5

(1.5)

NA

NA

NA

NA

Long Radius 90º Elbow

3

(0.9)

3

(0.9)

3

(0.9)

3

(0.9)

3

(0.9)

Mitered 45º Elbow

4

(1.2)

4

(1.2)

4

(1.2)

NA

NA

NA

NA

Medium Radius 45º Elbow

2.5

(0.8)

2.5

(0.8)

2.5

(0.8)

NA

NA

NA

NA

Long Radius 45º Elbow

1.5

(0.5)

1.5

(0.5)

1.5

(0.5)

1.5

(0.5)

1.5

(0.5)

Tee

16

(4.9)

16

(4.9)

16

(4.9)

16

(4.9)

16

(4.9)

*Note: 3--- and 4---in. Vent pipe systems require long radius elbows.

Venting System Length Calculations

The maximum length for each vent pipe (inlet or exhaust) equals the Maximum Equivalent Vent Length (MEVL) from Table 1 or Table 3

minus the number of elbows multiplied by the deduction for each elbow in Table 2.
Standard vent terminations and concentric vent terminations count for zero deductions.

Example

A direct--vent 60,000 Btuh furnace installed at 2100 ft. (640 M ) with 2--in. (51 mm) vent piping. Venting system includes,

FOR EACH

PIPE

, (3) 90

_

long radius elbows, (2) 45

_

long radius elbows and a concentric vent kit.

Maximum Equivalent Vent Length

=

127 ft.

(From Table 1)

Deduct (3) 90 long radius

3

x

3 ft.

=

- 9 ft.

(From Table 2)

Deduct (2) 45 long radius

2

x

1.5 ft.

=

- 3 ft.

(From Table 2)

Maximum Vent Length

=

115 ft.

For

EACH

vent or inlet pipe

Summary of Contents for 925TA

Page 1: ...em S Fan On Plus technology allows control of continuous fan speed from a compatible thermostat S External Media Filter Cabinet included S 4 way multipoise design for upflow downflow or horizontal ins...

Page 2: ...ry Supplied Media Cabinet Field Supplied Filter Filter Used for Certified Watt Data KGAWF1606UFR KGAWF1306UFR KGAWF1406UFR KGAWF1506UFR KGAWF1506UFR Electrical Data 030040 042060 048080 048100 066120...

Page 3: ...66 2200 CFM 0 5 ESP 040 40 000 BTU 060 60 000 BTU 080 80 000 BTU 100 100 000 BTU 120 120 000 BTU Not all familes have these models A11164 FURNACE COMPONENTS RATING PLATE NOT SHOWN LOCATED ON BLOWER DO...

Page 4: ...as Orifice Kit 1 30mm LP KGAHA5750130 X X X X X Indoor Air Quality Bryant Perfect Air Purifier 16x25 406x635 mm GAPAAXBB1625 A08 X X X X X Bryant Perfect Air Purifier 20x25 508x635 mm GAPAAXBB2025 A08...

Page 5: ...0 1050 2 Org 1180 1130 1095 1060 1015 975 935 895 850 800 1 Red 1100 1045 1010 970 920 885 845 790 745 690 100000 SIDE BOTTOM 5 Gry 2040 1970 1885 1795 1720 1635 1540 1450 1360 1230 4 Yel 1550 1505 14...

Page 6: ...202 61 6 224 68 3 100 000 NA 17 5 2 94 28 7 205 62 5 229 69 8 120 000 NA NA NA 83 25 3 217 66 1 Not all families have these models NOTE See notes at end of venting tables NOTE See Table 3 for altitude...

Page 7: ...0 39 6 NA NA 60 000 7 2 1 82 25 0 152 46 3 168 51 2 NA 80 000 NA 35 10 7 111 33 8 148 45 1 156 47 5 100 000 NA NA 67 20 4 157 47 9 170 51 8 120 000 NA NA NA 56 17 1 164 50 0 9001 to 10 000 2743 to 304...

Page 8: ...0 125 0 20 0 70 0 175 0 177 0 147 0 M 6 1 19 5 19 5 17 1 14 3 6 1 21 3 52 7 45 7 38 1 6 1 21 3 53 3 53 9 44 8 0 20 Ft 20 0 32 0 30 0 22 0 11 0 20 0 70 0 104 0 87 0 67 0 20 0 70 0 124 0 104 0 82 0 M 6...

Page 9: ...heat exchangers motors and controls 60 80 27 C 16 C SUPPLY AIR A10490 MINIMUM CLEARANCES TO COMBUSTIBLE MATERIALS POSITION CLEARANCE Rear 0 0 mm Front Combustion air openings in furnace and in struct...

Page 10: ...ed Coil Assembly or Coil Box 22 1 8 562 0 19 482 6 23 3 4 603 3 20 3 8 517 5 1 The plenum should be constructed 1 4 in 6 mm smaller in width and depth than the plenum dimensions shown above Concentric...

Page 11: ...ELD SUPPLIED FUSED DISCONNECT JUNCTION BOX 24 VOLT TERMINAL BLOCK THREE WIRE HEATING ONLY FIVE WIRE NOTE 2 NOTE 1 1 STAGE THERMOSTAT TERMINALS FIELD SUPPLIED FUSED DISCONNECT CONDENSING UNIT FURNACE C...

Page 12: ...B OUTLET WIDTH A 22 558 3 14 13 16 376 3 35 889 0 5 8 15 8 1 5 16 33 3 29 1 2 749 3 19 1 8 485 8 VENT AIR INTAKE AIR FLOW AIR FLOW SIDE INLET SIDE INLET CONDENSATE DRAIN TRAP LOCATION THERMOSTAT ENTRY...

Page 13: ...___ Media Filter Casing Casing shall be of 030 in thickness minimum pre painted galvanized steel Draft Inducer Motor Draft inducer motor shall be two speed design Primary Heat Exchangers Primary heat...

Page 14: ...change at any time specifications or designs without notice and without incurring obligations E2011 Bryant Heating Cooling Systems D 7310 W Morris St D Indianapolis IN 46231 Printed in U S A Edition D...

Reviews: