Venting System Length Calculations

The Total Equivalent Vent Length (TEVL) for

EACH

combustion air or vent pipe equals the length of the venting system, plus the equivalent

length of elbows used in the venting system from Table 2.
Standard vent terminations or factory accessory concentric vent terminations count for zero deduction.
See vent system manufacturer’s data for equivalent lengths of flexible vent pipe or other termination systems.

DO NOT ASSUME

that one

foot of flexible vent pipe equals one foot of straight PVC/ABS DWV vent pipe.
Compare the Total Equivalent Vent Length to the Maximum Equivalent Vent Lengths in Tables 1 and 3.

Example 1

A direct--vent 60,000 Btuh furnace installed at 2100 ft. (640 M). Venting system includes,

FOR EACH PIPE

, 100 feet (30 M) of vent pipe,

95 feet (28 M) of combustion air inlet pipe, (3) 90

_

long radius elbows, (2) 45

_

long radius elbows and a factory accessory concentric vent

kit.
Can this application use 2--in. (50 mm ND) PVC/ABS DWV vent piping?

Measure the required linear length of air inlet and vent pipe; insert the

longest of the two here:

100 ft

Use length of the longer of the vent

or air inlet piping system

Add equiv length of (3) 90º long-radius elbows

(use the highest number of elbows for either the

vent or inlet pipe)

3

x

3 ft

=

9 ft.

From Table 2

Add equiv length of (2) 45º long-radius elbows

(use the highest number of elbows for either the

vent or inlet pipe)

2

x

1.5 ft

=

3 ft.

From Table 2

Add equiv length of vent termination

0 ft.

From Table 2

Add correction for flexible vent pipe, if any

0 ft.

From Vent Manufacturer’s instructions;

zero for PVC/ABS DWV

Total Equivalent Vent Length (TEVL)

112 ft.

Add all of the above lines

Maximum Equivalent Vent Length (MEVL)

127 ft.

For 2” pipe from Table 1

Is TEVL less than MEVL?

YES

Therefore, 2” pipe may be used

Example 2

A direct--vent 60,000 Btuh furnace installed at 2100 ft. (640 M) Venting system includes,

FOR EACH PIPE

, 100 feet (30 M) of vent pipe,

95 feet (28 M) of combustion air inlet pipe, (3) 90

_

long radius elbows, and a polypropylene concentric vent kit. Also includes 20 feet (6 M)

of flexible polypropylene vent pipe, included within the 100 feet (30 M) of vent pipe.
Assume that one meter of flexible 60 mm or 80 mm polypropylene pipe equals 1.8 meters of PVC/ABS pipe.

VERIFY FROM VENT

MANUFACTURER’S INSTRUCTIONS.

Can this application use 60 mm (O.D.) polypropylene vent piping? If not what size piping can be used?

Measure the required linear length of air inlet and vent pipe; insert the

longest of the two here:

100 ft

Use length of the longer of the vent

or air inlet piping system

Add equiv length of (3) 90º long-radius elbows

(use the highest number of elbows for either the

vent or inlet pipe)

3

x

3 ft

=

9 ft.

From Vent Manufacturer’s instructions

Add equiv length of (2) 45º long-radius elbows

(use the highest number of elbows for either the

vent or inlet pipe)

0

x

=

0 ft.

From Vent Manufacturer’s instructions

Add equiv length of vent termination

9 M

x

3 ft/M

=

18 ft.

From Vent Manufacturer’s instructions

Add correction for flexible vent pipe, if any

1.8

x

20 ft

=

36 ft.

From Vent Manufacturer’s instructions

Total Equivalent Vent Length (TEVL)

163 ft.

Add all of the above lines

Maximum Equivalent Vent Length (MEVL)

127 ft.

For 2” pipe from Table 1

Is TEVL less than MEVL?

NO

Therefore, 60mm pipe may NOT be used;

try 80 mm

Maximum Equivalent Vent Length (MEVL)

250 ft.

For 3” pipe from Table 1

Is TEVL less than MEVL?

YES

Therefore, 80 mm pipe may be used

926T

A

Summary of Contents for 926TA

Page 1: ...t Surface Igniter S SmartEvap technology helps control humidity levels in the home when used with a compatible humidity control system S FanOn Plus technology allows control of continuous fan speed fr...

Page 2: ...and continues Bryant s tradition of technology leadership and innovation in providing a reliable and durable product Full Featured Variable Speed Motors Our variable speed ECM Electronically Commutat...

Page 3: ...U 120 120 000 BTU 140 140 000 BTU Not all familes have these models 0 90 AFUE 2 92 AFUE 3 93 AFUE 5 95 AFUE 6 96 AFUE 7 97 AFUE Example of a Model Number A14367 FURNACE COMPONENTS RATING PLATE NOT SHO...

Page 4: ...peed Selections Variable PWM Blower Wheel Dia x Width in 11 x 7 11 x 8 11 x 7 11 x 8 11 x 8 11 x 10 11 x 10 11 x 11 Air Filtration System Optional Media Cabinet Field Supplied Filter Filter Used for C...

Page 5: ...as Orifice Kit 46 Nat Gas LH32DB208 D D D D D D D D Gas Orifice Kit 47 Nat Gas LH32DB078 D D D D D D D D Gas Orifice Kit 48 Nat Gas LH32DB076 D D D D D D D D Gas Orifice Kit 54 LP LH32DB203 D D D D D...

Page 6: ...ON OFF 770 725 685 640 600 560 515 480 See note 4 OFF ON ON 945 910 875 835 800 770 735 695 665 635 ON OFF OFF 1140 1105 1075 1040 1005 970 930 885 835 790 ON OFF ON 1250 1210 1165 1115 1065 1015 965...

Page 7: ...770 720 660 620 585 ON OFF OFF 1175 1140 1090 1060 1025 980 940 905 855 815 ON OFF ON 1325 1280 1245 1210 1180 1140 1105 1070 1025 990 ON ON OFF 1545 1515 1480 1445 1410 1380 1350 1315 1245 1175 ON O...

Page 8: ...1890 1750 1645 1550 Clg SW2 Maximum Clg Airflow 2 note 8 2375 2300 2205 2115 2010 1890 1750 1645 1550 Heating SW1 High Heat Airflow 3 note 8 2375 2300 2205 2115 2010 1890 1750 1645 1550 Low Heat Airfl...

Page 9: ...2 NA NA 60 000 23 7 0 119 36 3 210 64 0 235 71 6 NA 80 000 15 4 6 59 18 0 155 47 2 210 64 0 232 70 7 100 000 NA 19 5 8 98 29 9 211 64 3 236 71 9 120 000 NA NA 8 2 4 86 26 2 224 68 3 140 000 4 NA NA NA...

Page 10: ...ent Vent Length TEVL 112 ft Add all of the above lines Maximum Equivalent Vent Length MEVL 127 ft For 2 pipe from Table 1 Is TEVL less than MEVL YES Therefore 2 pipe may be used Example 2 A direct ven...

Page 11: ...9 8 63 19 2 8001 to 9000 2438 to 2743 40 000 10 3 0 121 36 9 130 39 6 NA NA 60 000 7 2 1 82 25 0 152 46 3 168 51 2 NA 80 000 NA 35 10 7 111 33 8 148 45 1 156 47 5 100 000 NA NA 67 20 4 157 47 9 170 51...

Page 12: ...44 8 0 20 Ft 20 0 32 0 30 0 22 0 11 0 20 0 70 0 104 0 87 0 67 0 20 0 70 0 124 0 104 0 82 0 M 6 1 9 8 9 1 6 7 3 4 6 1 21 3 31 7 26 5 20 4 6 1 21 3 37 8 31 7 25 0 20 30 Ft 20 0 17 0 14 0 6 0 0 0 20 0 7...

Page 13: ...PLY AIR A10490 MINIMUM CLEARANCES TO COMBUSTIBLE MATERIALS POSITION CLEARANCE Rear 0 0 mm Front Combustion air openings in furnace and in structure 1 in 25 mm Required for service 24 in 610 mm All Sid...

Page 14: ...5 8 600 2 24 1 2 622 Furnace with or without Cased Coil Assembly or Coil Box 22 1 8 562 19 483 23 3 4 603 20 5 8 600 1 The plenum should be constructed 1 4 in 6 mm smaller in width and depth than the...

Page 15: ...FIELD SUPPLIED DISCONNECT AUXILIARY J BOX 24 V TERMINAL BLOCK THREE WIRE HEATING ONLY FIVE WIRE NOTE 1 NOTE 2 FIELD SUPPLIED DISCONNECT CONDENSING UNIT TWO WIRE FURNACE C O N T R O L R G COM W C R G Y...

Page 16: ...IMENSIONS IN INCH MM 22 2 7 8 7 8 22 2 POWER CONN AIR FLOW SEE NOTE 3 NOTES 1 Doors may vary by model 2 Minimum return air openings at furnace based on metal duct If flex duct is used see flex duct ma...

Page 17: ...Casing Casing shall be of 030 in thickness minimum pre painted steel Draft Inducer Motor Draft inducer motor shall be two speed PSC design Primary Heat Exchangers Primary heat exchangers shall be 3 P...

Page 18: ...e or change at any time specifications or designs without notice and without incurring obligations E2014 Bryant Heating Cooling Systems D 7310 W Morris St D Indianapolis IN 46231 Edition Date 09 14 Re...

Reviews: